Aspen Manufacturing AAN, AEN Installation Manual

INSTALLATION GUIDE
AAN & AEN Series - Manufactured Housing
Electric Furnace
1. Safety Instruction
Potential safety hazards are alerted using the following symbols. The symbol is used in conjunction with terms that indicate the intensity of the hazard.
`
!
This symbol indicates a potentially hazardous situation, which if not avoided, could result in serious injury, property damage, product damage or death.
CAUTION
!
Certied technicians or those individuals
!
and product damage or personal injury hazard may occur without such background.
!
age.
!
installer’s responsibility to ensure that product is installed in strict compliance with national and local codes. Manufac­turer takes no responsibility for damage (personal, product or property) caused due to installations violating regula­tions. In absence of local/state codes, refer to National Elec­tric Code: NFPA 90A & 90B Uniform Mechanical Code.
meeting the requirements specied by
NATE may use this information. Property
All power sources should be disconnect­ed prior to servicing. Failure to do so may cause personal injury or property dam-
Product designed and manufactured to permit installation in accordance with lo­cal and national building codes. It is the
This symbol indicates a potentially hazardous situation, which if not avoided, may result in moderate injury or property damage.
2. Inspection
ü On receiving the product, visually inspect it for any major shipping related damages. Shipping damages are the carrier’s responsibility. Inspect the product labels to verify the model number and options are in accordance with your order. Manufacturer will not accept dam­age claims for incorrectly shipped product.
3. Installation Preparation
Read all the instructions in this guideline carefully while paying spe­cial attention to the WARNING and CAUTION alerts. If any of the
instructions are unclear; clarify with certied technicians. Gather all
the tools needed for successful installation of the unit prior to begin­ning the installation.
3A. Clearances
This unit is designed for zero clearance installation on three sides and adequate clearance to provide access for service in the front. A minimum of 18” (alcove) or 6” (closet) clearance is recommended on the front end (Fig 3A-1).
0”
6”
0”
When this unit is installed in an enclosed
!
(i.e. automobile, space heater, water heater etc.) ensure that the enclosed area is properly ventilated.
CAUTION
!
these instructions. Some localities may require a licensed installer/service personnel.
!
!
damages caused due to modication of the unit to operate
with alternative power sources.
# 123117
area, such as a garage or utility room with any Carbon Monoxide producing devices
Only factory authorized kits and acces­sories should be used when installing or modifying this unit unless it is so noted in
Unit is not approved for outdoor installa­tions.
The unit is designed for operation with 208/240 V, single phase, 60 Hz power supply. Aspen will not be responsible for
6” for Closet
18” for Alcove
Fig 3A-1. Minimum Clearance for Electric Furnace
For closet installation, the return air opening can be on the front door, above the furnace casing on a wall, or on the electric door’s louvered door (If applicable.)
A minimum clearance of six inches is required, on the return side, in
order to allow for proper airow.
1
Ensure that the unit is adequately sized.
CAUTION
!
These units are designed to be installed in a closet or an alcove.
If installing the electric furnace into a closet or an alcove, the unit must leave front clearance to service the unit. The bottom of the unit
should also rest on a sturdy platform or oor.
The tonnage of the outdoor unit should never exceed the tonnage of this unit.
3C. Ductwork and Duct Connector3B. Closet and Alcove Installation
Duct systems should be installed in accordance with standards for air-conditioning systems, National Fire Protection Association Pam­phlet No. 90A or 90B. They should be sized in accordance with Na­tional Environmental System Contractors Association Manual K, or whichever is applicable. It is recommended that installers refer to
the “Manufactured Housing Duct System Guide to Best Practices”
by MHI-MHRA.
On any job, non-ammable exible collars should be used for the
return air and discharge connections to prevent transmission of vi­bration. Although these units have been specially designed for quiet, vibration-free operation, air ducts can act as soundboards if poorly installed.
All main supply and return air drops should be properly sized as determined by the designer of the duct system and should not nec-
essarily be the size of the duct ange openings of the unit. (The duct size should never be smaller than the ange openings of the electric
furnace supply and return air openings.)
To install the duct connector:
- Attach duct connector foam gasket along the perimeter of the duct opening to seal the duct connector to the top of the duct.
- To connect the duct connector, insert it into the oor opening and
bend back the tabs inside the duct. Fold the tabs over 90 degrees to ensure a secure connection. Seal around the duct connector.
Wall Mount Return Air Grille
Fig 3B-2. Closet Installation
Airow must be made available to the electric furnace’s return. Not
doing so may cause improper heating as well as premature heating element failure.
Coil
- Slit the corners of the duct connector that stick up above the oor, and then bend the sides over onto the oor surface.
- Insulate between the oor base and the oor when used on a com­bustible oor. Be sure to cut the insulation around the perimeter of
the duct connector opening.
- Install the oor base over the oor opening with the anges on the
11 x 13 inch opening facing down.
- Use four screws to secure the oor base to the oor.
It is recommended that wherever supply and return air sheet metal ducts pass through unconditioned areas, they be insulated to pre­vent excessive heat loss during heating operation. When applied in conjunction with summer air conditioning, sheet metal duct routed through unconditioned areas should be insulated and have an out­side vapor barrier to prevent formation of condensation.
4. Electrical Line Voltage Wiring
These units are designed for single or three phase 208/240 volts, 60 HZ power supply. Wire selection and wiring must be in accordance with the National Electric Code and/or local codes. Unit terminals are designed to accommodate copper and aluminum wiring. If aluminum wiring is used: please observe special precautions relative to sizing, wire connections and corrosion protection.
Wall Mount Return Air Grille
Front of Electric Furnace
Fig 3B-3. Alcove Installation
All models with 5,8 or 10 kW electric heat are arranged for single circuit connections. Models larger than 10 kW are arranged for multi­circuit protection. Refer to top part of wiring diagram at the end of this guide for detailed information.
2
# 123117
Line voltage wiring should be routed through the access holes at the top of the electric fur­nace. Proper electrical conduit
connection ttings should be
used. Connect the power wiring to the line side connections on the electric furnace. The electri­cal ground wire should be con­nected to the grounding lug.
Ensure both the eld supplied
ground wire and electric furnace GREEN ground wire are both secured to the grounding lug of the electric furnace.
208VAC
Tap
240VAC
Tap
If the line voltage being sup­plied to the electric furnace is 208 volt single phase, the line voltage tap on the low voltage transformer needs to be moved from the 240 volt tap to the 208 volt tap. If this is not done, the secondary output voltage of the transformer will be too low.
5. Low Voltage Connections
5A. Single Stage Cooling with Electric Heat
The electric furnace comes factory setup for a single stage cool­ing system. If factory installed accessory electric heaters are prein­stalled, the unit will also have a low voltage wire for the electric heat (Fig 5A-1).
Fig 5A-2.
6. Air Volume Adjustment
Air volume needs to be set to the level recommended by the outdoor unit equipment manufacturer. Most systems will require around 400 CFM of indoor air for every 1 ton of system cooling capacity. The air volume must be set prior to attempting system charge.
This electric furnace uses a 240V PSC motor. The air volume level produced by the electric furnaces at varying external static pressure levels is shown in Table 6-1.
Fig 5A-1.
During cooling mode operation, the indoor blower G wire will ener­gize a time delay relay inside the electric furnace. After a short time delay period, the time delay relay contacts will close and apply power to the blower motor. Fan delay periods are 7 seconds ON delay and 65 seconds OFF delay. (See Schematic) The Y wire from the thermostat is not connected at the electric fur­nace. This wire goes directly to the outdoor unit 24 volt wiring to turn on the outdoor condensing unit when a call for cooling takes place. The 24 volt common for the outdoor unit circuits is connected at the
electric furnace Brown wire.
The electric heater low voltage wiring W terminal is wired directly from the thermostat to the electric furnace. The blower will delay a heat call ON for a period of 5 seconds. The OFF delay period is 60 seconds.
Table 6-1.
Use a Magnehelic Gauge with a 1” scale and two static pressure tips to measure the static pressure during the air volume adjustment procedure. The high port static pressure tip should be placed in the supply duct near the outlet of the electric furnace. The low port static pressure tip should be placed in the return air duct near the entrance
to the electric furnace. The factory provided air lter should be in
place inside of the electric furnace.
1. Select a starting speed tap from the CFM table.
2. Call for fan only operation at the thermostat.
3. Read the external static pressure level on the Magnehelic gauge.
4. Make speed tap selection changes to get the air volume as close
as possible to the required level.
5. If the static pressure is above .5” wc , excessive turbulence or duct friction needs to be reduced. (Obstructions in the duct system can also cause excessive static pressure.)
6. When proper air volume is established, move on to the charging procedure.
# 123117
3
Loading...
+ 5 hidden pages