DC/DC Insulated converters
output power 240 W
• DC wide range input
Short circuit, overload, over temperature protection
•
•
Already preset with internal ORing diode for redundant
connection
• Compact design
NOTES BLOCK DIAGRAM
The depth dimension includes the terminal blocks and the DIN
clamp.
(1) Inrush current is measured with input supplied by a battery;
the current peak vary depending on the internal impedance of
the current source and depending on cables and connections
resistance.
(2) Over 50°C (122°F) apply a derating -6 W/°C, max 60°C
(3) According to EN60950 insulation tests on input side must be
made only with DC instruments.
73
(2.88 in)
140
(5.52 in)
137
(5.40 in)
VERSIONS
110 Vdc / 24 Vdc 10 A
110 Vdc / 24 Vdc 10 A ridondante
—
Cod. XCSA240FC
CSA240FC
INPUT TECHNICAL DATA
Input rated voltage
Current @ Iout max.
Inrush peak current
Standby power
Internal protection fuse
External protection on AC line
Overvoltage input protection circuit
110 Vdc (range 90…130 Vdc)
2.4 A ±10%
< 150A / < 2ms (1)
<3.4 W @ 110 Vdc
T 5 A replaceable
≥6 A C characteristic
Passive varistor and active
shutdown at 136 Vdc
OUTPUT TECHNICAL DATA
Output rated voltage 24 Vdc
Output adjustable range 22.7…27 Vdc
Continuous current 10 A @ 50°C (2)
Overload limit 15 A
Short circuit peak current 21 A for 300 ms
Load regulation <1.5%
Ripple @ nominal ratings ≤ 100 mVpp
Hold up time @ In (Uin 110 Vdc) >4 ms
Overload / short circuit protections hiccup at the overload limit with auto reset / over temperature protection
Status display “DC OK” green LED / “DC OK” alarm contact / “Overload” red LED
Alarm contact threshold —
Parallel connection possible
Redundant parallel connection
factory provided with internal
ORing diode
GENERAL TECHNICAL DATA
Efficiency (Uin 110 Vdc) >89%
Dissipated power (Uin 110 Vdc) <28 W
Operating temperature range –20...+60°C, with derating over 50°C (2)
Input/output isolation 2.1 kVdc / 60s (3)
Input/ground isolation 1.41 kVdc / 60s (3)
Output/ground isolation 0.75 kVdc / 60s (3)
Standard/approvals IEC950, EN60950
EMC Standards EN61000-6-2, EN61000-6-4, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-5-5, EN61000-4-6, EN61000-4-11
MTBF @ 25°C @ nominal ratings >500'000 h acc. to SN 29500 / >150'000 h acc. to MIL Std. HDBK 217F
Overvoltage category/Pollution degree II / 2
Protection degree IP 20 IEC 529, EN60529
Connection terminal 2.5 mm² pluggable screw type
Housing material aluminium
Approx. weight 800 g (28.24 oz)
Mounting information vertical on rail, allow 10 mm spacing between adjacent components
MOUNTING ACCESSORIES
Mounting rail type according to IEC60715/TH35-7.5 PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
Mounting rail type according to IEC60715/G32 —
Automation Systems Interconnect - PO Box 1340 - Mechanicsburg, PA 17055 - Phone 717-249-5581 - Fax 717-249-5542