ASI-Automation Systems Interconnect XCSA120BC Data Sheet

DC/DC Insulated converters output power 120 W
DC wide range input
Short circuit, overload, over temperature protection
NOTES BLOCK DIAGRAM
The depth dimension includes the terminal blocks and the DIN clamp. (1) Inrush current is measured with input supplied by a battery;
the current peak vary depending on the internal impedance of the current source and depending on cables and connections
resistance. (2) Over 50°C (122°F) apply a derating -3 W/°C, max 60°C (3) According to EN60950 insulation tests on input side must be made only with DC instruments.
55 (2.17 in)
115
(4.53 in)
130 (5.12 in)
VERSIONS
12 Vdc / 24 Vdc 5 A 24 Vdc / 12 Vdc 7 A 24 Vdc / 24 Vdc 5 A 48 Vdc / 24 Vdc 5 A
Cod. XCSA120BC Cod. XCSA120CB Cod. XCSA120CC Cod. XCSA120DC
CSA120BC
CSA120CB
CSA120CC
CSA120DC
INPUT TECHNICAL DATA
Input rated voltage Current @ Iout max. Inrush peak current Standby power Internal protection fuse External protection on AC line Overvoltage input protection circuit
12 Vdc (range 10.5…18 Vdc) 24 Vdc (range 18…36 Vdc) 24 Vdc (range 18…36 Vdc) 48 Vdc (range 36…72 Vdc)
12 A ±10% 5.1 A ±10% 5.8 A ±10% 2.8 A ±10%
< 60A / < 2ms (1) < 100A / < 2ms (1) < 90A /< 2ms (1) < 120A / < 2ms (1)
<1.5 W @ 12 Vdc <1 W @ 24 Vdc <1.5 W @ 24 Vdc <2 W @ 48 Vdc T 20 A replaceable T 10 A replaceable T 5 A replaceable
≥25 A C characteristic ≥13 A C characteristic ≥6 A C characteristic
Passive varistor and active
shutdown at 19 Vdc
Passive varistor and active shutdown at 38 Vdc Passive varistor and active
shutdown at 76 Vdc
OUTPUT TECHNICAL DATA
Output rated voltage 24 Vdc 12...15 Vdc 24 Vdc 24 Vdc Output adjustable range 22.5...27.5 Vdc 12...15 Vdc 22.5...27.5 Vdc 22.5...27.5 Vdc Continuous current 5 A @ 50°C (2) 7 A @ 50°C (2) 5 A @ 50°C (2) 5 A @ 50°C (2) Overload limit 6.5 A 9.1 A 6.5 A 6.5 A Short circuit peak current 12 A for 300 ms 15 A for 300 ms 12 A for 300 ms 13 A for 300 ms Load regulation <0.5% Ripple @ nominal ratings ≤ 100 mVpp ≤ 150 mVpp ≤ 200 mVpp Hold up time @ In Overload / short circuit protections hiccup at the overload limit with auto reset / over temperature protection Status display “DC OK” green LED Alarm contact threshold — Parallel connection possible
Redundant parallel connection possible with external ORing diode
>1 ms
>2 ms >4.5 ms
GENERAL TECHNICAL DATA
Efficiency (Uin 110 Vdc) > 83% >87% >87% >90% Dissipated power (Uin 110 Vdc) <25 W <16 W <18 W <13 W Operating temperature range –20...+60°C, with derating over 50°C (2) Input/output isolation 2.1 kVdc / 60s (3) Input/ground isolation 1.41 kVdc / 60s (3) Output/ground isolation 0.75 kVdc / 60s (3) Standard/approvals IEC950, EN60950 EMC Standards EN61000-6-2, EN61000-6-4, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-5-5, EN61000-4-6, EN61000-4-11 MTBF @ 25°C @ nominal ratings >500'000 h acc. to SN 29500 / >150'000 h acc. to MIL Std. HDBK 217F Overvoltage category/Pollution degree II / 2 Protection degree IP 20 IEC 529, EN60529 Connection terminal 2.5 mm² pluggable screw type Housing material aluminium Approx. weight 550 g (19.40 oz) Mounting information vertical on rail, allow 10 mm spacing between adjacent components
MOUNTING ACCESSORIES
Mounting rail type according to IEC60715/TH35-7.5 PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB Mounting rail type according to IEC60715/G32
Automation Systems Interconnect - PO Box 1340 - Mechanicsburg, PA 17055 - Phone 717-249-5581 - Fax 717-249-5542