• Suitable for J and K thermocouple
• IN / OUT / supply galvanic isolation
• 8 programmable temperature ranges
• 3 programmable output ranges
• Simple programming, self calibrating
• Availabe version with 24-240 Vac/dc supply voltage
24 Vac/dc supply voltage
24-240 Vac/dc supply voltage
(1) Adjustable via rotary-switch
(2) Adjustable via dip-switch
CWTH 6-0844 cod. X756844
The modules convert and isolate
signals generated by thermocouples type J (FeCuNi) or K (NiCrNi)
into an analogue signal; can be
set into 8 temperature input ranges, and can be set for up to 3
most importante analog ranges.
The set up is possible by setting
a dip-witch on one side of the
module.
The modules provide input and
output isolation, assuring high
signal accuracy, and can be used
with isolated and not isolated
sensors.
FeCuNi (J type) and NiCrNi (K type) thermocouple
according to DIN/IEC584-1
-50…+200°C (-58…+392°F)
-50…+350°C (-58 …+662°F)
0…+200°C (+32…+392°F)
0…+400°C (+32…+752°F)
0…+600°C (+32…+1112°F)
0…+800°C (+32…+1472°F)
0…+1000°C (+32…+1832°F)
0…+1200°C (+32…+2192°F)
–
0–10 V
0–20 / 4–20 mA
55 Ω with output voltage,
400 Ω with output current
Input signal
Temperature range (1)
Supply current
Output signal (2)
Applicable load
INPUT TECHNICAL DATA
OUTPUT TECHNICAL DATA
APPROVALS
GENERAL TECHNICAL DATA
VERSIONS
NOTES
BLOCK DIAGRAM
Thermocouple
converters
and isolators
APPLICATIONS
Supply voltage
Max. rated current
Accuracy
Transmission frequency
Temperature coefficient
Isolation
EMC Standard
Reference Standard
Overvoltage category
Pollution degree
Protection degree
Operating temperature
Connection terminal blocks
Housing material
Approximative weight
Mounting information
Mounting rail
according to IEC60715/TH35-7,5
24 Vac/dc (16.8 – 30 Vdc / 19.2 – 28.8 Vac)
35 mA ± 10% @ 24 Vdc
<0.5% + 2K full range
<0.1% full range
0.015% / K full range
1.5 kVac / 60 s (IN / OUT / supply volatage)
EN 50081-2, EN 50082-2
IEC 664-1, DIN VDE
III
2
IP20
-25 … +60°C (-13 … +140°F)
2.5
mm2, screw type
Noryl UL94 V-0
600 g (21.16 oz)
on rail adjacent without gap
PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
CWTH 6-0847 cod. X756847
FeCuNi (J type) and NiCrNi (K type) thermocouple
according to DIN/IEC584-1
-50…+200°C (-58…+392°F)
-50…+350°C (-58 …+662°F)
0…+200°C (+32…+392°F)
0…+400°C (+32…+752°F)
0…+600°C (+32…+1112°F)
0…+800°C (+32…+1472°F)
0…+1000°C (+32…+1832°F)
0…+1200°C (+32…+2192°F)
–
0–10 V
0–20 / 4–20 mA
55 Ω with output voltage,
400 Ω with output current
BLOCK DIAGRAM
24-240 Vac/dc (16.8 – 264 Vdc / 19.2 – 264 Vac)
35 mA ± 10% @ 24 Vdc
<0.5% + 2K full range
<0.1% full range
0.015% / K full range
4 kVac / 60 s (IN / OUT / supply volatage)
EN 50081-2, EN 50082-2
IEC 664-1, DIN VDE
III
2
IP20
-25 … +60°C (-13 … +140°F)
2.5
mm2, screw type
Noryl UL94 V-0
600 g (21.16 oz)
on rail adjacent without gap
PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
pending pending
84
79
17,5
84
79
17,5
Wide range input
voltage 24-240 Vac/dc
Input voltage
24 Vac/dc
Wide range input voltage 24-240 Vac/dc