ASI-Automation Systems Interconnect X756844 Data Sheet

Programmable converters for thermocouples
• Converters for sensors with thermocouples J and K type
• 8 programmable input range
• 3 programmable output range
• Simple programming
• Version with 24-240 Vac/dc supply voltage
17.5 (0.69 in)
84 (3.31 in)
79 (3.11 in)
NOTES
The dimensions include the DIN clamp. (1) Adjustable via rotary-switch (2) Adjustable via dip-switch (3) range
16.8…30 Vdc / 19.2…28.8 Vac
(4) range
16.8…264 Vdc / 19.2…264 Vac
(5)
“3-way isolation: IN/OUT/power supply
VERSIONS
24 Vac/dc supply voltage 24-240 Vac/dc supply voltage
Supply voltage
24 Vac/dc
Cat. No. X756844 Cat. No. X756847
CWTH 6-0844
BLOCK DIAGRAM
Supply voltage
24…240 Vac/dc
CWTH 6-0847
INPUT TECHNICAL DATA
Input signal
Temperature range (1)
Supply current
thermocouples FeCuNi (J type) e NiCrNi (K type)
according to DIN/IEC584-1
-50…+200°C (-58…+392°F)
-50…+350°C (-58 …+662°F) 0…+200°C (+32…+392°F) 0…+400°C (+32…+752°F)
0…+600°C (+32…+1112°F)
0…+800°C (+32…+1472°F) 0…+1000°C (+32…+1832°F) 0…+1200°C (+32…+2192°F)
thermocouples FeCuNi (J type) e NiCrNi (K type)
according to DIN/IEC584-1
-50…+200°C (-58…+392°F)
-50…+350°C (-58 …+662°F) 0…+200°C (+32…+392°F) 0…+400°C (+32…+752°F)
0…+600°C (+32…+1112°F)
0…+800°C (+32…+1472°F) 0…+1000°C (+32…+1832°F) 0…+1200°C (+32…+2192°F)
APPLICATIONS
The modules convert and isolate signals generated by thermocouples type J (FeCuNi) or K (NiCrNi) into an analog signal; can be set into 8 temperature input ranges, and can be set for up to 3 most important analog ranges. The set up is possible by setting a dip-witch on one side of the module. The modules provide input and output isolation, assuring high signal accuracy, and can be used with isolated and not isolated sensors.
Output signal (2)
Applicable load
0…10 V
0…20 / 4…20 mA
>1 KΩ with output voltage,
<400 Ω with output current
0…10 V
0…20 / 4…20 mA
>1 KΩ with output voltage,
<400 Ω with output current
GENERAL TECHNICAL DATA
OUTPUT TECHNICAL DATA
Supply voltage Rated current ≤ 35 mA ± 10% @ 24 Vdc ≤ 35 mA ± 10% @ 24 Vdc Accuracy <0.5% FS <0.5% FS Trasmission frequency <30 Hz <30 Hz Temperature coefficient Isolation 1.5 KVac / 60 s (5) 4 KVac / 60 s (5) ECM standards EN 50081-2, EN 50082-2 EN 50081-2, EN 50082-2 Reference Standard IEC 664-1, DIN VDE IEC 664-1, DIN VDE Overvoltage category/Pollution degree III / 2 III / 2 Protection degree IP20 IP20 Operating temperature range -20…+60°C -20…+60°C Connection terminal 2.5 mm² fixed screw type 2.5 mm² fixed screw type Housing material Noryl UL94V-0 Noryl UL94V-0 Approx. weight 65 g (2.29 oz) 75 g (2.65 oz) Mounting information
24 Vac/dc (3) 24-240 Vac/dc (4)
0.015% / K FS 0.015% / K FS
vertical on rail adjacent without gap vertical on rail adjacent without gap
MOUNTING ACCESSORIES
Mounting rail type according to IEC60715/TH35-7.5 PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB Mounting rail type according to IEC60715/G32 — Plug-in jumper red (16 poles, 16 A) white
blue
— — —