![](/html/56/5611/5611ac224e832e226187b55b7e393d7cb2570042a4d33dde92a2a596dd30b704/bg1.png)
Programmable converters for
thermocouples
• Converters for sensors with thermocouples J and K type
• 3 ways galvanic isolation
• 8 programmable input range
• 3 programmable output range
• Simple programming
• Version with 24-240 Vac/dc supply voltage
17.5
(0.69 in)
84
(3.31 in)
79
(3.11 in)
NOTES
The dimensions include the DIN clamp.
(1) Adjustable via rotary-switch
(2) Adjustable via dip-switch
(3) range
16.8…30 Vdc / 19.2…28.8 Vac
(4) range
16.8…264 Vdc / 19.2…264 Vac
(5)
“3-way isolation: IN/OUT/power supply
VERSIONS
24 Vac/dc supply voltage
24-240 Vac/dc supply voltage
Supply voltage
24 Vac/dc
Cat. No. X756844 Cat. No. X756847
CWTH 6-0844
BLOCK DIAGRAM
Supply voltage
24…240 Vac/dc
CWTH 6-0847
INPUT TECHNICAL DATA
Input signal
Temperature range (1)
Supply current — —
thermocouples FeCuNi (J type) e NiCrNi (K type)
according to DIN/IEC584-1
-50…+200°C (-58…+392°F)
-50…+350°C (-58 …+662°F)
0…+200°C (+32…+392°F)
0…+400°C (+32…+752°F)
0…+600°C (+32…+1112°F)
0…+800°C (+32…+1472°F)
0…+1000°C (+32…+1832°F)
0…+1200°C (+32…+2192°F)
thermocouples FeCuNi (J type) e NiCrNi (K type)
according to DIN/IEC584-1
-50…+200°C (-58…+392°F)
-50…+350°C (-58 …+662°F)
0…+200°C (+32…+392°F)
0…+400°C (+32…+752°F)
0…+600°C (+32…+1112°F)
0…+800°C (+32…+1472°F)
0…+1000°C (+32…+1832°F)
0…+1200°C (+32…+2192°F)
APPLICATIONS
The modules convert and isolate
signals generated by thermocouples
type J (FeCuNi) or K (NiCrNi) into
an analog signal; can be set into 8
temperature input ranges, and can
be set for up to 3 most important
analog ranges. The set up is
possible by setting a dip-witch on
one side of the module.
The modules provide input and
output isolation, assuring high signal
accuracy, and can be used with
isolated and not isolated sensors.
Output signal (2)
Applicable load
0…10 V
0…20 / 4…20 mA
>1 KΩ with output voltage,
<400 Ω with output current
0…10 V
0…20 / 4…20 mA
>1 KΩ with output voltage,
<400 Ω with output current
GENERAL TECHNICAL DATA
OUTPUT TECHNICAL DATA
Supply voltage
Rated current ≤ 35 mA ± 10% @ 24 Vdc ≤ 35 mA ± 10% @ 24 Vdc
Accuracy <0.5% FS <0.5% FS
Trasmission frequency <30 Hz <30 Hz
Temperature coefficient
Isolation 1.5 KVac / 60 s (5) 4 KVac / 60 s (5)
ECM standards EN 50081-2, EN 50082-2 EN 50081-2, EN 50082-2
Reference Standard IEC 664-1, DIN VDE IEC 664-1, DIN VDE
Overvoltage category/Pollution degree III / 2 III / 2
Protection degree IP20 IP20
Operating temperature range -20…+60°C -20…+60°C
Connection terminal 2.5 mm² fixed screw type 2.5 mm² fixed screw type
Housing material Noryl UL94V-0 Noryl UL94V-0
Approx. weight 65 g (2.29 oz) 75 g (2.65 oz)
Mounting information
24 Vac/dc (3) 24-240 Vac/dc (4)
0.015% / K FS 0.015% / K FS
vertical on rail adjacent without gap vertical on rail adjacent without gap
MOUNTING ACCESSORIES
Mounting rail type according to IEC60715/TH35-7.5 PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
Mounting rail type according to IEC60715/G32 —
Plug-in jumper red
(16 poles, 16 A) white
blue
—
—
—