ASI-Automation Systems Interconnect X756816 Data Sheet

Programmable converters for RTD sensors
• Converters for PT100 sensors
• 3 ways galvanic isolation
• 8 programmable input range
• 3 programmable output range
• Version with 24-240 Vac/dc supply voltage
17.5 (0.69 in)
84 (3.31 in)
79 (3.11 in)
NOTES
The dimensions include the DIN clamp. (1) Adjustable via rotary-switch (2) Adjustable via dip-switch (3) They can also be used with 2 wire PT100 sensor, connecting
the terminals 1 and 4
(4) range
16.8…30 Vdc / 19.2…28.8 Vac
(5) range
16.8…264 Vdc / 19.2…264 Vac
(6)
3-way isolation: IN/OUT/power supply
VERSIONS
24 Vac/dc supply voltage 24-240 Vac/dc supply voltage
Supply voltage
24 Vac/dc
Cat. No. X756816 Cat. No. X756817
CWPT 6-0816
BLOCK DIAGRAM
Supply voltage
24…240 Vac/dc
CWPT 6-0817
INPUT TECHNICAL DATA
Input signal Temperature range (1)
Supply current 0.5 mA 0.5 mA
PT100 3 wires (3) PT100 3 wires (3)
-50…+50°C (-58…+122°F)
-50…+100°C (-58…+212°F)
-50…+150°C (-58…+302°F) 0…+100°C (+32…+212°F) 0…+150°C (+32…+302°F) 0…+200°C (+32…+392°F) 0…+300°C (+32…+572°F) 0…+400°C (+32…+752°F)
-50…+50°C (-58…+122°F)
-50…+100°C (-58…+212°F)
-50…+150°C (-58…+302°F) 0…+100°C (+32…+212°F) 0…+150°C (+32…+302°F) 0…+200°C (+32…+392°F) 0…+300°C (+32…+572°F) 0…+400°C (+32…+752°F)
OUTPUT TECHNICAL DATA
Output signal (2)
Applicable load
0…10 V
0…20 / 4…20 mA
>1 KΩ with output voltage,
<400 Ω with output current
0…10 V
0…20 / 4…20 mA
>1 KΩ with output voltage,
<400 Ω with output current
APPLICATIONS
The modules convert and isolate signals generated by 3 wire / 2 wire PT100 (RTD) sensors into analog signals; the module can be set into 8 temperature ranges and for up to 3 most important analog ranges. Set up is easily achieved by setting a dip-switch on one side of the module. The modules provide input and output isolation, assuring high signal accuracy, and can be used with isolated and not isolated sensors. Two wire sensors can be used by connecting a jumper wire between 1 and 4 terminal blocks.
GENERAL TECHNICAL DATA
Supply voltage Rated current ≤ 35 mA ± 10% @ 24 Vdc ≤ 35 mA ± 10% @ 24 Vdc Accuracy <0.3% FS <0.3% FS Trasmission frequency <30 Hz <30 Hz Temperature coefficient Isolation 1.5 KVac / 60 s (6) 4 KVac / 60 s (6) ECM standards EN 50081-2, EN 50082-2 EN 50081-2, EN 50082-2 Reference Standard IEC 664-1, DIN VDE IEC 664-1, DIN VDE Overvoltage category/Pollution degree III / 2 III / 2 Protection degree IP20 IP20 Operating temperature range -20…+60°C -20…+60°C Connection terminal 2.5 mm² fixed screw type 2.5 mm² fixed screw type Housing material Noryl UL94V-0 Noryl UL94V-0 Approx. weight 75 g (2.65 oz) 85 g (3.00 oz) Mounting information
24 Vac/dc (2) 24-240 Vac/dc (3)
0.015% / K FS 0.015% / K FS
vertical on rail adjacent without gap vertical on rail adjacent without gap
MOUNTING ACCESSORIES
Mounting rail type according to IEC60715/TH35-7.5 PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB Mounting rail type according to IEC60715/G32 — Plug-in jumper red (16 poles, 16 A) white
blue
— — —