ASI-Automation Systems Interconnect X756540 Data Sheet

38
47
U,I
DC 24V
21
OUT+
+
_
IN
IN
I
2S11 3 4
Output
0-10V 0-20mA 4-20mA
Input
Switch On
0-1A 0-1A 0-1A
2S11 3 4
Output
0-10V 0-20mA 4-20mA
Input
Switch On
0-5A 0-5A 0-5A
2S11 3 4
Output
0-10V 0-20mA 4-20mA
Input
Switch On
0-10A 0-10A 0-10A
115,5
90
6.2
Range WAA7-0540
Range WAA7-0541
Range WAA7-0542
Current to analog converters
• For AC/DC current measurements
• Protected against transients
• Power supplied LED
• 3 output signals available
VERSIONS
Cod. X756540 Cod. X756541 Cod. X756542
0…1 A input
WAA 7-0540
0…5 A input
WAA 7-0541
0…10 A input
WAA 7-0542
INPUT TECHNICAL DATA
Input signal
0…1 A AC/DC 0…5 A AC/DC 0…10 A AC/DC
Max. input voltage
400 V (1) 400 V (1) 400 V (1)
Current wire connection 1.5 mm² screw type 1.5 mm² screw type 1.5 mm² screw type
OUTPUT TECHNICAL DATA
vOLTAGE CURRENT
Output signal
0…10 V 0…20 mA / 4…20 mA
Max. output signal
11 V 21 mA
Applicable load
>1 KΩ <400 Ω
GENERAL TECHNICAL DATA
Supply voltage 24 Vdc (16.8...30 Vdc) 24 Vdc (16.8...30 Vdc) 24 Vdc (16.8...30 Vdc) Rated current
13 mA 13 mA 13 mA Operating temperature -25…+60°C -25…+60°C -25…+60°C Linearity error < 0.1% FS (23°C) < 0.1% FS (23°C) < 0.1% FS (23°C) Offset error < 0.5% FS (23°C) < 0.5% FS (23°C) < 0.5% FS (23°C) Temperature coefficient
< 150 ppm / K FS < 150 ppm / K FS < 150 ppm / K FS Response time – Protection degree IP20 IP20 IP20 Connection terminal 1.5 mm² screw type 1.5 mm² screw type 1.5 mm² screw type Approx. weight 55 g (1.94 oz) 55 g (1.94 oz) 55 g (1.94 oz) Mounting information
vertical on rail adjacent without gap vertical on rail adjacent without gap vertical on rail adjacent without gap
MOUNTING ACCESSORIES
Mounting rail type according to IEC60715/TH35-7.5 PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB Mounting rail type according to IEC60715/G32 — Plug-in jumper red (16 poles, 16 A) white
blue
CWBK 7-0802 cod. X766802 CWBK 7-0803 cod. X766803 CWBK 7-0804 cod. X766804
NOTES
APPLICATIONS
BLOCK DIAGRAM
The dimensions includes the terminal blocks and the DIN clamp. (1) Do not connect directly to a 400 V line
Through a “HALL” sensor they grant AC/DC current measurements. The presence of current in a circuit indicates not only that power is supplied but also that the circuit is closed and the load connected and active. It’s also possible to know the work conditions of the circuit. The module guarantees galvanic isolation between the current conductor and the analog.
(0.99 in)
(3.70 in)
(3.90 in)
ASI
Automation Systems Interconnect, Inc
Innovative Interconnect and Interface Solutions
Loading...