ASI-Automation Systems Interconnect X756524 Data Sheet

Frequency to analog signal converters
• Adjustable frequency range 0...28.8 Khz
• 3 programmable analog signal output ranges
• 3 ways I/O 2.5 KV isolation
79 (3.11 in)
17.5 (0.69 in)
84 (3.31 in)
NOTES BLOCK DIAGRAM
The dimensions include the terminal blocks and the DIN clamp. (1) range 16.8…30 Vdc / 19.2…28.8 Vac (2)
3-way isolation: IN/OUT
Alimentazione
Voltage supply
24…240 Vac/dc
24…240 Vac/dc
VERSIONS
CWNFA 6-0524
INPUT TECHNICAL DATA
Input signal (range) Input signal (type) Input resistance 50 KΩ Hysteresis 0.5 Vpp o 5 Vpp adjustable via DIP switch
0…28.8 KHz adjustable via DIP switch
AC/DC 0.6…30 Vpp
APPLICATIONS
This module is used to convert a frequancy signal, with either sinusoidal or square waveform, into a standard analog signal (eg. 0…10 V, 0..20 mA, 4…20 mA). A microprocessor provides a high resolution, high stability and accuracy output signal and a dip switch gives the possibility to select a calibrated range of frequency measurement from 0 … 100 Hz up to 0…28.8 kHz.
OUTPUT TECHNICAL DATA
Output signal 0…10 V, (max. 10.6 V)
Applicable load >1 KΩ with output voltage
Ripple < 5 mVeff
0…20 / 4…20 mA, (max 21 mA)
<400 Ω with output current
GENERAL TECHNICAL DATA
Supply voltage 24 Vac/dc (1) Rated current 20 mA Accuracy 0.1 FS (23°C) Linearity error 0.02% Ripple 0.1% Setting time (accuracy 1%) 200 ms Temperature coefficient 70 ppm/K Isolation 1.5 KVac / 60 s (2) ECM standards EN 61000-6-2, EN 61000-6-4 Reference Standard Overvoltage category Pollution degree Protection degree Operating temperature range Connection terminal Housing material Peso approssmativo Mounting information
IED 664-1, DIN VDE
III 2
IP 20 IEC 529 EN60529
-25…+60°C
1.5 mm² fixed screw type PPE
70 g (2.47 oz)
vertical on rail adjacent without gap
MOUNTING ACCESSORIES
Mounting rail type according to IEC60715/TH35-7.5 PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB Mounting rail type according to IEC60715/G32 — Plug-in jumper red
white
blue
— — —