Frequency to analog signal
converters
• Adjustable frequency range 0...28.8 Khz
• 3 programmable analog signal output ranges
• 3 ways I/O 2.5 KV isolation
79
(3.11 in)
17.5
(0.69 in)
84
(3.31 in)
NOTES BLOCK DIAGRAM
The dimensions include the terminal blocks and the
DIN clamp.
(1) range 16.8…30 Vdc / 19.2…28.8 Vac
(2)
3-way isolation: IN/OUT
Alimentazione
Voltage supply
24…240 Vac/dc
24…240 Vac/dc
VERSIONS
Cat. No. X756524
CWNFA 6-0524
INPUT TECHNICAL DATA
Input signal (range)
Input signal (type)
Input resistance 50 KΩ
Hysteresis 0.5 Vpp o 5 Vpp adjustable via DIP switch
0…28.8 KHz adjustable via DIP switch
AC/DC 0.6…30 Vpp
APPLICATIONS
This module is used to convert a frequancy signal, with either sinusoidal or
square waveform, into a standard analog signal (eg. 0…10 V, 0..20 mA,
4…20 mA). A microprocessor provides a high resolution, high stability
and accuracy output signal and a dip switch gives the possibility to select
a calibrated range of frequency measurement from 0 … 100 Hz up to
0…28.8 kHz.
OUTPUT TECHNICAL DATA
Output signal 0…10 V, (max. 10.6 V)
Applicable load >1 KΩ with output voltage
Ripple < 5 mVeff
0…20 / 4…20 mA, (max 21 mA)
<400 Ω with output current
GENERAL TECHNICAL DATA
Supply voltage 24 Vac/dc (1)
Rated current 20 mA
Accuracy 0.1 FS (23°C)
Linearity error 0.02%
Ripple 0.1%
Setting time (accuracy 1%) 200 ms
Temperature coefficient 70 ppm/K
Isolation 1.5 KVac / 60 s (2)
ECM standards EN 61000-6-2, EN 61000-6-4
Reference Standard
Overvoltage category
Pollution degree
Protection degree
Operating temperature range
Connection terminal
Housing material
Peso approssmativo
Mounting information
IED 664-1, DIN VDE
III
2
IP 20 IEC 529 EN60529
-25…+60°C
1.5 mm² fixed screw type
PPE
70 g (2.47 oz)
vertical on rail adjacent without gap
MOUNTING ACCESSORIES
Mounting rail type according to IEC60715/TH35-7.5 PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
Mounting rail type according to IEC60715/G32 —
Plug-in jumper red
white
blue
—
—
—