Mechanical and electrical life: 10,000 times
Wiring
Tunnel terminal blocks
Terminal connection area: Apply to the 10mm2~ 50 mm
2
Terminal screw: M7, torque: 3.5N.m
5. Normal Working Environment
Ambient temperature: -35~+70
Relative air humidity: 95%
Altitude: 2000m
Environment with the pollution level of 3
Working site without obvious vibration and shock
6. Tripping Characteristics
Type C curve
Protect the conventional load and distribution cable
Rated current: 50~125A
Tripping characteristics: Range of instantaneous tripping (5~10) In
Type D curve
Protect the impact load with the large starting current (such as motor, transformer)
Rated current: 50~125A
Tripping characteristics: Range of instantaneous tripping (10~14) In
Type C
Type D
High Current UL1077
Circuit Breakers
NDB1-125
• 50, 63, 80, 100, and 125 Amps
• C and D Trip Curves
• UL1077
• Red visual trip indicator
• Easy to Wire, Screw-Clamp Connections
• Standard 35mm DIN Rail Mounted
The NDB1 series of circuit breakers provide the short circuit and overload protection, control and isolation functions. Applicable to the low-voltage terminal distribution in the industry, civil buildings, energy, communication, infrastructure and other elds.
Specications
Wire Size: Terminal Screw: Torque: Interupt Capacity: Mechanical Life: Operating Temperature Range: Max Voltage:
#8 - 1/0 AWG M7
3.5N-m (31 lbin) 10kA 10,000 Operations
-35C to 70C 240/480 Vac
C - Trip Curve D - Trip Curve
ASI
Automation Systems Interconnect, Inc
Innovative Interconnect and Interface Solutions
NDT2230039
Version
1
Implementati
on Date
2016-5-5
7. Product Outline and Installation Dimensions
1P 2P
NDB1 Series MCB
7. Wiring Diagram
NDB1-32 Connecting
NDB1-125 Connecting
LoadLoadLoad
Wiring Diagrams
High Current UL1077
Circuit Breakers
NDB1-125
Dimensions