● Mechanical and electrical life: 10,000 times
● Wiring
○ Tunnel terminal blocks
○ Terminal connection area: Apply to the 10mm2~ 50 mm
2
○ Terminal screw: M7, torque: 3.5N.m
5. Normal Working Environment
● Ambient temperature: -35℃~+70℃
● Relative air humidity: ≤95%
● Altitude: ≤2000m
● Environment with the pollution level of 3
● Working site without obvious vibration and shock
6. Tripping Characteristics
● Type C curve
○ Protect the conventional load and distribution cable
○ Rated current: 50~125A
○ Tripping characteristics: Range of instantaneous tripping (5~10) In
● Type D curve
○ Protect the impact load with the large starting current (such as motor, transformer)
○ Rated current: 50~125A
○ Tripping characteristics: Range of instantaneous tripping (10~14) In
High Current UL1077
Circuit Breakers
NDB1-125
• 1, 2, 3 and 4 Poles
• 50, 63, 80, 100, and 125 Amps
• C and D Trip Curves
• UL1077
• Red visual trip indicator
• Easy to Wire, Screw-Clamp Connections
• Standard 35mm DIN Rail Mounted
The NDB1 series of circuit breakers provide the short
circuit and overload protection, control and isolation
functions. Applicable to the low-voltage terminal
distribution in the industry, civil buildings, energy,
communication, infrastructure and other elds.
Specications
Wire Size:
Terminal Screw:
Torque:
Interupt Capacity:
Mechanical Life:
Operating Temperature Range:
Max Voltage:
#8 - 1/0 AWG
M7
3.5N-m (31 lbin)
10kA
10,000 Operations
-35C to 70C
240/480 Vac
C - Trip Curve D - Trip Curve
Automation Systems Interconnect, Inc
Innovative Interconnect and Interface Solutions
7. Product Outline and Installation Dimensions
1P 2P
NDB1 Series MCB
7. Wiring Diagram
● NDB1-32 Connecting
● NDB1-125 Connecting
LoadLoadLoad
Wiring Diagrams
High Current UL1077
Circuit Breakers
NDB1-125
Dimensions