Modular 
multi-pole 
terminal blocks
with UL94V-0 polyamide 
insulating body
• UL94V-0
• 
CESI 03 ATEX 164 U Ex e   certificate 
I M2 / II 2 G D operating temperature range: 
–40 ÷ +80 °C
 panel mount by means of screws
•
beige version
BPL.4
Cat. No.  BP100
TPL.4
Cat. No.  TP100
BPL/R
TECHNICAL CHARACTERISTICS
function / type 
rated cross-section  (mm2) 
connecting capacity 
 flexible  (mm2) 
 rigid  (mm2)
max. flexible with ferrule (mm2)-ferrule type 
rated voltage / rated current / gauge  co 
rated voltage / rated current / AWG 
(Ex e) rated voltage /  (V) 250 V 250 V 250 V 
rated impulse withstand voltage / pollution degree 
insulation stripping length  (mm) 
tightening torque value (test / recommended)  (Nm) 
fixing screw (*)  (Ø) 
height / width / thickness 26 / 24 / 20 26 / 30 / 20 26 / 24 / 13
nf. to IEC 60947-7-1
/ tightening torque value UL
APPROVALS
Normal compositions
No of 
poles
 2  B  20 
 3  T  30 
 4  B+B  40 
 5  B+T  50 
 6  T+T  60 
 7  B+T+B  70 
 8  T+B+T  80 
 9  T+T+T  90 
 10  T+B+B+T  100 
 12  T+T+T+T  120 
 14  T+T+B+T+T  140 
 15  T+T+T+T+T  150 
 16  T+T+B+B+T+T  160 
 18  T+T+T+T+T+T  180 
 20  T+T+T+B+T+T+T  200
BPL.4 and TPL.4
configurations
two-pole three-pole two-pole reduced pitch 
444
0,5 ÷ 6 
0,5 ÷ 6 
4 - WP40/16 
500 V / 32 A / A4 
300 V / 20 A / 12 ÷ 18 AWG / 4,4 lb.in.
6 KV / 3 6 KV / 3 6 KV / 3 
12 12 12 
0,5 / 0,8 0,5 / 0,8 0,5 / 0,8 
M3 (Ø head 5.6 mm max) M3 (Ø head 5.6 mm max) -
Total length
mm
0,5 ÷ 6 
0,5 ÷ 6 
4 - WP40/16 
500 V / 32 A / A4 
300 V / 20 A / 12 ÷ 18 AWG / 4,4 lb.in.
 (*)  (*)  (*)
(*) NOTE:
when using BPL.4 and TPL.4 terminal blocks in Ex e classified installations, the use of 
the insulated fixing screw is required.
0,5 ÷ 6 
0,5 ÷ 6 
4 - WP40/16 
500 V / 32 A / A4 
300 V / 20 A / 12 ÷ 18 AWG / 4,4 lb.in.
Cat. No.  BP200