Ashcroft T2, G2 Instruction Manual

Page 1
G2 & T2 PRESSURE TRANSMITTER INSTRUCTION SHEET
WARNING: READ BEFORE INSTALLATION
Fluid hammer and surges can destroy any pressure transducer and must always be avoided. A pressure snubber should be installed to eliminate the damaging hammer effects. Fluid hammer occurs when a liquid flow is suddenly stopped, as with quick closing solenoid valves. Surges occur when flow is suddenly begun, as when a pump is turned on at full power or a valve is quickly opened.
Liquid surges are particularly damaging to pressure transducers if the pipe is originally empty. To avoid damaging surges, fluid lines should remain full (if pos­sible), pumps should be brought up to power slowly, and valves opened slowly. To avoid damage from both fluid hammer and surges, a surge chamber should be installed.
Symptoms of fluid hammer and surge's damaging effects:
a) Pressure transducer exhibits an output at zero pressure (large zero
offset). b) Pressure transducer output remains constant regardless of pressure. c) In severe cases, there will be no output.
WARNING!
A failure resulting in injury or damage may be caused by excessive overpressure, excessive vibration or pressure pulsation, excessive instrument temperature, corrosion of the pressure containing parts, or other misuse. Consult Dresser Instrument, Stratford, Connecticut.
Life Support Policy
Dresser’s products are not authorized for use as critical components in life support devices or systems without the express written approval of the General Manager, Stratford Operations of Dresser Instrument, Dresser, Inc. As used herein:
1. Life support devices or systems are devices or systems which, (a) are intended for surgical implant into the body, or (b) support or sustain life, and whose failure to perform, when properly used in accordance with instructions for use provided in the labeling, can be reasonably expected to result in a significant injury to the user.
2. A critical component is any compo­nent of a life support device or sys­tem whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.
WARNING!
Any electrical device may be suscepti­ble to damage when exposed to static electrical charges. To avoid damage to the transducer observe the following:
• Ground the body of the transducer BEFORE
making any electrical connec-
tions.
• When disconnecting, remove the ground LAST!
Note: The shield and drain wire in the cable (if supplied) is not connected to the transducer body, and is not a suit­able ground.
CAUTION: pressure spikes in excess of the rated overpressure capability of the trans­ducer may cause irreversible electrical and/or mechanical damage to the pres­sure measuring and containing elements.
©Ashrcoft Inc. All rights reserved. 250 East Main Street, Stratford, CT 06614 USA Tel: 203-378-8281, FAX 203-385-0402 www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M011-10129
GBE 02/06
DESCRIPTION
The Ashcroft Model G2 and T2 pressure transducers are high performance instru­ments intended for use in industrial appli­cations where the process media is com­patible with the 17-4PH stainless steel sensor material and the 304 SS process connection.
MECHANICAL INSTALLATION Environmental
The G2 and T2 transducers can be stored and used within the temperature limits of
-40°C to 125°C (-40°F to 257°F). Ingress protection ratings of the units are depend­ent on the electrical termination specified. Refer to the wiring diagrams on the reverse for the IP rating of the unit which is being installed.
Mounting
The G2 and T2 transducers require no special mounting hardware and can be mounted in any orientation with negligible position error. Although the units can with­stand considerable vibration without dam­age or significant output effects, it is always good practice to mount the transducer where there is minimum vibration. For units with NPT type pressure fittings apply sealing tape or an equivalent sealant to the threads before installing. When instal­ling or removing the unit apply a wrench to the hex wrench flats, located above the pres­sure fitting. DO NOT tighten by using a pipe wrench on the housing. A 27mm (1
1
16˝) wrench can be used on the wrench flats of the hex. For G2 models with detachable electrical connectors a 6 point deep socket can also be used to install the unit.
Electro-Magnetic Interference
The circuitry of the G2 and T2 transducers is designed to minimize the effect of elec­tromagnetic and radio frequency interfer­ence. To minimize susceptibility to noise, avoid running the termination wiring in a conduit which contains high current AC power cables. Where possible avoid run­ning the termination wiring near inductive equipment.
Field Adjustments
The G2 and T2 transducers are precisely calibrated and temperature compensated at the factory to ensure long and stable performance. There are no field accessible adjustments on the G2 or T2 transducers.
ELECTRICAL INSTALLATION
Please refer to the reverse of this page for power supply requirements and for appro­priate wiring protocol based on the partic­ular output signal and electrical termina­tion features of the unit being installed
Page 2
G2 & T2 PRESSURE TRANSMITTER INSTRUCTION SHEET
Power Supply Requirements
Output Signal Min Max
Ratiometric* 4.5Vdc 5.5Vdc (0.5V to 4.5V) 0-5Vdc 9Vdc 36Vdc 1-5Vdc 9Vdc 36Vdc 1-6Vdc 9Vdc 36Vdc 0-10V 14Vdc 36Vdc 4-20mA** 9Vdc 36Vdc
*0.5Vdc-4.5Vdc output is ratiometric to the
nominal 5Vdc supply
**For transmitters with 4-20mA output signal,
the minimum voltage at the terminals is 9Vdc. However, the minimum supply voltage should be calculated using the adjacent graph and formula.
Pin #
Voltage 4-20mA
Output Output
1V+ V+ 2 Output None 3 Case Gnd. Case Gnd. 4 Common Common
Pin #
Voltage 4-20mA
Output Output
1V+ V+ 2 Common Common 3 Output None
GND Case Gnd. Case Gnd.
Pin #
Voltage 4-20mA
Output Output
AV+ V+ B Output None C Case Gnd. Case Gnd. D Common Common
Wire Voltage 4-20mA
Color Output Output
Red V+ V+ White Output None Black Common Common Green Case Gnd. Case Gnd. Bare** Drain Wire Drain Wire
©Ashrcoft Inc. All rights reserved. 250 East Main Street, Stratford, CT 06614 USA Tel: 203-378-8281, FAX 203-385-0402 www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M011-10129
GBE 02/06
To determine minimum loop supply voltage:
LSV(min)=9(V)+[.022(A)*RL]
Where:
LSV= Loop Supply Voltage (Vdc) RL= RS+ RW (ohms)
RL= Loop Resistance (ohms)
RS= Sense Resistance (ohms) [Measuring Instrument]
RW= Wiring Resistance (ohms)
10
40
9 (min)
36 (max)
Loop Supply Voltage (Vdc) [LSV]
Power Supply Voltage vs. Loop Resistance
(4-20mA ONLY)
Loop Resistance (R
L
-Ohms)
1400
1200
Shielded Cable, PVC Jacket, 24AWG leads
Wire Color Voltage Output 4-20 mA Output*
Red V+ V+
Black Common V-
White Output V-
Bare** Shield Drain Wire Shield Drain Wire
IP67 Ingress rating
Flying Leads 18AWG
Wire Color Voltage Output 4-20 mA Output*
Red V+ V+
Black Common V-
White Output V-
IP67 Ingress rating
Hirschmann G Series
Mates to Optional Hirschmann G4W1F connector, or equal
Pin # Voltage Output 4-20 mA Output*
1V+ V+
2 Common V-
3 Output V-
4 Case Ground Case Ground
IP65 Ingress rating
3-Pin Delphi (Packard) Metri-Pack 150 series
Mates to Optional Metri-Pack connector 12065287
Pin # Voltage Outputs 4-20 mA Output*
A Common V-
BV+ V+
C Output V-
IP67 Ingress rating
Power Supply Voltage vs Loop Resistance
G2 & T2 ELECTRICAL INSTALLATION
G2 ELECTRICAL TERMINATIONS AND WIRING
T2 ELECTRICAL TERMINATIONS AND WIRING
Wiring Diagrams
Mates to optional Hirschmann connector Part 933 172-100 or equa
l
Mates to optional Hirschmann connector GDM 3099 or equa
l
Mates to optional Amphenol Bendix connector PTO6A-8-4-SR or equal
INGRESS RATING OF THE T2 FOR ALL TERMINATION TYPES IS IP65
* Use either V- termination on G2 with 4-20mA output
** Where shielded wiring is being used; Connect the drain wire to the guard terminal on the read out device or measuring instrument if available. In all other cases connect to the ground of the power supply negative terminal.
Loading...