Ashcroft KS Operating Manual

KS SANITARY
1000
750
500
250
0
0362010
1182
30
Load Limitations 4-20mA Output Only
(R
LOOP
)
PRESSURE TRANSDUCER INSTRUCTION SHEET
WARNING! READ
m m
BEFORE INSTALLATION
1. GENERAL:
A failure resulting in injury or damage may be caused by excessive overpres­sure, excessive vibration or pressure pulsation, excessive instrument tem­perature, corrosion of the pressure con­taining parts, or other misuse. Consult Ashcroft Inc., Stratford, Connecticut, USA before installing if there are any questions or concerns.
2. OVERPRESSURE:
Pressure spikes in excess of the rated overpressure capability of the transduc­er may cause irreversible electrical and/ or mechanical damage to the pressure measuring and containing elements.
Fluid hammer and surges can destroy any pressure transducer and must al­ways be avoided. A pressure snubber should be installed to eliminate the dam­aging hammer effects. Fluid hammer occurs when a liquid flow is suddenly stopped, as with quick closing solenoid valves. Surges occur when flow is sud­denly begun, as when a pump is turned on at full power or a valve is quickly opened.
Liquid surges are particularly damag­ing to pressure transducers if the pipe is originally empty. To avoid damaging surges, fluid lines should remain full (if possible), pumps should be brought up to power slowly, and valves opened slowly. To avoid damage from both fluid hammer and surges, a surge chamber should be installed.
Symptoms of fluid hammer and surge's damaging effects:
• Pressure transducer exhibits an output
at zero pressure (large zero offset).
• Pressure transducer output remains
constant regardless of pressure
In severe cases, there will be no output.
FREEZING:
Prohibit freezing of media in pressure port. Unit should be drained (mount in vertical position with electrical termination upward) to prevent possible overpressure damage from frozen media.
3. STATIC ELECTRICAL CHARGES:
Any electrical device may be susceptible to damage when exposed to static electrical charges. To avoid damage to the trans­ducer observe the following:
• Ground the body of the transducer
BEFORE making any electrical connections.
• When disconnecting, remove the ground
LAST!
Note: The shield and drain wire in the cable (if supplied) is not connected to the transducer body, and is not a suitable ground.
Mounting
Although the unit can withstand normal vi­bration without damage or significant output effects, it is always good practice to mount the transducer where there is minimum vibration. Be sure to use a gasket that does not interfere with the sanitary diaphragm. If the gasket I.D. is smaller than 1.50 inches, an offset due to clamping force will occur.
Power Supply
The supply voltage for the 1-5 and 1-6 Vdc output transducers must be within the range of 10 to 36 Vdc. The maximum supply voltage for a 4-20mA current output transducer is 36 Vdc while the minimum supply voltage is dependent upon the loop resistance of the circuit. The Load Limita­tion Chart shows the minimum supply voltage (V resistance (R
) required for a given loop
min
).
LOOP
Excitation (Ratiometric Output Only)
For proper operation a voltage within the range of 5 to 10 Vdc must be ap plied between the transducer’s supply terminals.
Noise
For minimum noise susceptibility, avoid running the transducer’s cable in a con­duit that contains high current AC power cables. Where possible avoid running the cable near inductive equipment.
Shield Wiring
Connect the braided shield to the guard terminal on the reading instrument (meter, etc.) if available or to ground or to the power supply negative terminal.
Adjustment Potentiometers
The zero and span pots are accessible through the top of the case. Loosen the four screws and separate the top carefully. The zero pot is marked with a white dot.
Vent Tube
The cable will have a clear Teflon vent tube that's required at pressure below 500 psi to provide atmospheric reference. The open end should be placed in a dry area.
OPERATING REGION
V
= 10V+ (.022A x RL)
min
RL = RS + R
RL = Loop Resistance (ohms)
RS = Sense Resistance (ohms)
RW = Wire Resistance (ohms)
W
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614, USA • Tel: 203-378-8281, Fax: 203-385-0402 • email: info@ashcrfoft.com, www.ashcroft.com. All specifications subject to change without notice. All sales subject to standard terms and conditions of sale. I&M011-10124 (250-3110) Rev. A 5/11
+
+
POWER SUPPLY
(+)
(–)
METER
TRANSDUCER
POWER
OUTPUT
RED
BLACK
+
+
POWER SUPPLY
(Common)
(+ Power)
(+ Output)
METER
TRANSDUCER
GREEN
RED
WHITE
+
+
POWER SUPPLY
(- Power)
(+ Power)
(- Output)
(+ Output)
METER
TRANSDUCER
RED
WHITE
GREEN
BLACK
Dimensions
A
B
C
MODEL A B C D
D
S15 0.8 4.7 0.9 2.0
S20 0.8 4.7 0.9 2.5
KS Sanitary Transducers – Electrical Conn.
Voltage Output Units 1-5, 1-6 Vdc
Cable Type F2
Red = + Power White = Common
Green = Output
Cable Type C1
Red = + Power White = Common
Green = Output
Hirschmann Type
PIN-1 = + Power PIN-2 = Common PIN-4 = Output
Bendix 4-Pin, 6-Pin
Pin A = + Power Pin B = Output Pin D = Common
Current Output Units 4-20 mA
Cable Type F2
Red = + Power Black = – Power
Cable Type C1
Red = + Power Black = – Power
Hirschmann Type
PIN-1 = + Power PIN-2 = – Power
Bendix 4-Pin, 6-Pin
Pin A = + Power Pin B = – Power
Ratiometric (mV/V)
Cable Type F2
Red = + Power White = – Power
Green = + Output
Black = – Output
Cable Type C1
Red = + Power White = – Power
Green = + Output
Black = – Output
Bendix 4-Pin
Pin A = +Power Pin B = +Output Pin C = – Output Pin D = – Power
Bendix 6-Pin
Pin A = +Power Pin D = – Power Pin B = +Output Pin C = – Output Pin E = Shunt Cal. Pin F = Shunt Cal.
Wiring Diagrams for All Transducers
4-Wire Ratiometric (mV/V)
3-Wire Voltage
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614, USA • Tel: 203-378-8281, Fax: 203-385-0402 • email: info@ashcrfoft.com, www.ashcroft.com. All specifications subject to change without notice. All sales subject to standard terms and conditions of sale. I&M011-10124 (250-3110) Rev. A 5/11
4-20 mA
Loading...