Ashcroft FACTORY SET Operating Manual

Page 1
Installation and Maintenance Instructions for Ashcroft A-Series Miniature Watertight Pressure Switches
ADJUSTMENT COVER
FIELD ADJUSTABLE
FACTORY SET
SLIDE COVER DOWN TO ACCESS SETPOINT ADJUSTMENT SLIDE COVER UP TO CLOSE AND SEAL ADJUSTMENT
ROTATE LEFT TO INCREASE SETPOINT
ROTATE RIGHT TO DECREASE SETPOINT
Ø .095 OR SMALLER TOOL REQUIRED TO ROTATE NUT
INTRODUCTION
The APS and APA pressure switch have NEMA 6, IP 67 Rated 316 stainless steel housing and process connections. The APS has a factory fixed setpoint which cannot be changed in the field. The APA is field adjustable and can easily be adjusted by follow­ing the instructions in the diaphragm above.
ELECTRICAL CONNECTION
The APS and APA switch is available with many various electri­cal connections. Refer to the figures on other side for wiring color codes and identification of terminals. Depending on the configu­ration, the Micro DIN mating connector may or may not be sup­plied with the switch.
• Only trained and skilled personnel are allowed to attach the wires to the electrical terminals of the switch.
<
>
LO OK FO R TH ESE M ARK S ON OU R PRO DU CTS
SI L 3 C AP ABL E
• Cable couplers, glands and conduit connectors must have the correct electrical approvals as required by local electrical codes.
• The ground wire/connector is connected to the switch housing.
• Fully insulated mating spade terminals must be used on all spade terminal connections to prevent a shock hazard and maintain compliance with approvals.
MICRO SWITCH RATINGS
CODE VAC RATING VDC RATING
H 5A @ 125/250VAC 5A @ 28Vdc resistive
3A @ 28Vdc inductive P 3A @ 125VAC 2A @ 30Vdc resistive G 0.1 A @ 125VAC 0.1A @ 30Vdc resistive
L 1A @125VAC 1A @ 28Vdc resistive L 1A @125VAC 0.5A @ 28Vdcinductive
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com All sales subject to standard terms and conditions of sale.
I&M009-10045-10/11 (250-2966) Rev. 07/13
Page 2
Installation and Maintenance Instructions
GROUND
C
NO
N
C
G
ROUND
NC
N
O
C
for Ashcroft A-Series Miniature Watertight Pressure Switches
SPADE TERMINALS
WIRE COLOR/FUNCTION
WIRE COLOR SWITCH FUNCTION
RED SW1 NC
HITE SW1 C
W
BLUE SW1 NO
WHITE/BLACK SW2 C
RED/BLACK SW2 NC
BLUE/BLACK SW2 NO
GREEN Ground
DIN CONNECTOR
1 – COMMON 2 – NORMALLY CLOSED 3 – NORMALLY OPEN
4 – Ground
INSTALLATION
• To minimize the risk of injury, the switch enclosure must be se­lected according to the area classification and installed ac­cording to the required safety and electrical codes.
• Torque should always be applied to the Hex portion of the body, never to any other part of the body for it may alter the setpoint. It is recommended that Teflon tape or other sealant be used on the threads prior to installing to prevent leaks in the system.
• The ambient temperature limits for the switches are –40° to 100°C (varies with seal ordered).
Switch should be protected from excessive shock and vibration.
• The cover of the APA switch should be closed at all times when the switch is in operation.
CAUTIONS
• Always close the cover of the APA switch after making any setpoint adjustments.
• Do not exceed current or voltage limits.
• The protection degree of the switch is only valid when the switch is installed in accordance with all safety and electrical codes and regulations.
CLEANING
• Never use aggressive solvents.
• Do not use high pressure water to clean the switch.
MAINTENANCE/TROUBLESHOOTING
• All Ashcroft switches require little or no maintenance.
• Be sure the cover on the APA switch is closed at all times.
• When the switch is exposed to process media that may harden and/or build up in the pressure port, the switch should be re­moved and cleaned as required.
• If the switch does not function, only trained and skilled person­nel should check on the wiring, power supply and/or mounting.
• If the problem cannot be solved, please contact one of the Ashcroft affiliates or distributors.
FACTORY SETPOINTS
The APS switches and APA switches with a setpoint called out in the product code are set at the factory as follows:
• Increasing Setpoint (R) Rising Pressure or Decreasing Vac­uum – Normally Open contact will close when the pressure is raised from 0 psig to the setpoint. The resetpoint is then meas­ured from the setpoint, reducing the pressure until the Nor­mally Open contact opens.
• Decreasing Setpoint (D) Decreasing Pressure or Increasing Vacuum – Normally closed contact will close when the pres­sure is lowered from full range pressure to the setpoint. The reset is then measured from the setpoint, increasing the pres­sure until the Normally Closed contact opens.
Note: When ordered as a –15/15 psi range switch, depending
on setpoint, the Normally Open contact may be closed as received.
Safety Manual and SIL Certificate, CRN available on
www.ashcroft.com
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com All sales subject to standard terms and conditions of sale.
I&M009-10045-10/11 (250-2966) Rev. 07/13