Installation and Maintenance Instructions
for Ashcroft A-Series Miniature
Watertight Pressure Switches
ADJUSTMENT
COVER
FIELD ADJUSTABLE
FACTORY SET
SLIDE COVER DOWN TO ACCESS
SETPOINT ADJUSTMENT SLIDE COVER
UP TO CLOSE AND SEAL ADJUSTMENT
ROTATE LEFT
TO INCREASE SETPOINT
ROTATE RIGHT
TO DECREASE SETPOINT
Ø .095 OR SMALLER TOOL
REQUIRED TO ROTATE NUT
INTRODUCTION
The APS and APA pressure switch have NEMA 6, IP 67 Rated
316 stainless steel housing and process connections. The APS
has a factory fixed setpoint which cannot be changed in the field.
The APA is field adjustable and can easily be adjusted by following the instructions in the diaphragm above.
ELECTRICAL CONNECTION
The APS and APA switch is available with many various electrical connections. Refer to the figures on other side for wiring color
codes and identification of terminals. Depending on the configuration, the Micro DIN mating connector may or may not be supplied with the switch.
• Only trained and skilled personnel are allowed to attach the
wires to the electrical terminals of the switch.
<
>
LO OK FO R TH ESE M ARK S ON OU R PRO DU CTS
SI L 3 C AP ABL E
• Cable couplers, glands and conduit connectors must have the
correct electrical approvals as required by local electrical codes.
• The ground wire/connector is connected to the switch housing.
• Fully insulated mating spade terminals must be used on all
spade terminal connections to prevent a shock hazard and
maintain compliance with approvals.
MICRO SWITCH RATINGS
CODE VAC RATING VDC RATING
H 5A @ 125/250VAC 5A @ 28Vdc resistive
3A @ 28Vdc inductive
P 3A @ 125VAC 2A @ 30Vdc resistive
G 0.1 A @ 125VAC 0.1A @ 30Vdc resistive
L 1A @125VAC 1A @ 28Vdc resistive
L 1A @125VAC 0.5A @ 28Vdcinductive
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale.
I&M009-10045-10/11 (250-2966) Rev. 07/13

Installation and Maintenance Instructions
for Ashcroft A-Series Miniature
Watertight Pressure Switches
SPADE TERMINALS
WIRE COLOR/FUNCTION
WIRE COLOR SWITCH FUNCTION
RED SW1 NC
HITE SW1 C
W
BLUE SW1 NO
WHITE/BLACK SW2 C
RED/BLACK SW2 NC
BLUE/BLACK SW2 NO
GREEN – Ground
DIN CONNECTOR
1 – COMMON
2 – NORMALLY CLOSED
3 – NORMALLY OPEN
4 – Ground
INSTALLATION
• To minimize the risk of injury, the switch enclosure must be selected according to the area classification and installed according to the required safety and electrical codes.
• Torque should always be applied to the Hex portion of the
body, never to any other part of the body for it may alter the
setpoint. It is recommended that Teflon tape or other sealant
be used on the threads prior to installing to prevent leaks in
the system.
• The ambient temperature limits for the switches are –40° to
100°C (varies with seal ordered).
•
Switch should be protected from excessive shock and vibration.
• The cover of the APA switch should be closed at all times
when the switch is in operation.
CAUTIONS
• Always close the cover of the APA switch after making any
setpoint adjustments.
• Do not exceed current or voltage limits.
• The protection degree of the switch is only valid when the
switch is installed in accordance with all safety and electrical
codes and regulations.
CLEANING
• Never use aggressive solvents.
• Do not use high pressure water to clean the switch.
MAINTENANCE/TROUBLESHOOTING
• All Ashcroft switches require little or no maintenance.
• Be sure the cover on the APA switch is closed at all times.
• When the switch is exposed to process media that may harden
and/or build up in the pressure port, the switch should be removed and cleaned as required.
• If the switch does not function, only trained and skilled personnel should check on the wiring, power supply and/or mounting.
• If the problem cannot be solved, please contact one of the
Ashcroft affiliates or distributors.
FACTORY SETPOINTS
The APS switches and APA switches with a setpoint called out in
the product code are set at the factory as follows:
• Increasing Setpoint (R) Rising Pressure or Decreasing Vacuum – Normally Open contact will close when the pressure is
raised from 0 psig to the setpoint. The resetpoint is then measured from the setpoint, reducing the pressure until the Normally Open contact opens.
• Decreasing Setpoint (D) Decreasing Pressure or Increasing
Vacuum – Normally closed contact will close when the pressure is lowered from full range pressure to the setpoint. The
reset is then measured from the setpoint, increasing the pressure until the Normally Closed contact opens.
Note: When ordered as a –15/15 psi range switch, depending
on setpoint, the Normally Open contact may be closed
as received.
Safety Manual and SIL Certificate, CRN available on
www.ashcroft.com