Ashcroft D400 User Manual

Installation and Maintenance Instructions for
4
.03
(102)
Ø
0. 28X 3 HOLES (7)
0.2 2 (
6)
3. 3 2 (
84 )
3 . 2 6
(83 )
6
. 0 7(1 54 )
1. 57( 4 0 )
0. 50(1 3 ) 1
. 3 9
(3 5)
2. 78
( 71 )
3 . 50
( 89)
Ø5. 1 2
(1 3 0 )
Ø 0. 34 2 HOLES
0. 36 (9)
0. 25 (6)
2. 27
(
58) 1
. 25
(32)
2
. 77
(
70)
5. 62
(
14 3)
3. 0 6 (78)
2. 96 ( 75)
3/4 NPT
1/4 NPT F
EMALE
BRACKETWHEN REQURIED“XBP” VARIATION
5.20
(132)
3.62 (92)
2.18 (55)
0.32 (8)
4.37
(111)
1.37 (35)
Ø0 . 2 8x 3 HOLES
( 7)
1. 93 (49)
2 . 78
(71 )
3. 50
(89)
Ø 5. 1 2
(1 3 0 )
0. 36
(9)
0. 50 ( 13 )
0. 36 (9)
Ø0 . 34X 2 HOLES
(9)
1. 3 9 (3 5)
6.4 3
(1 63 )
1 . 43
(3 6)
Ø3 . 90
(99)
0. 03 (1 )
3. 58
(91 )
0. 3 1(8)
3. 0 6 (78)
5.62
(14 3)
1. 2 2(3 1)
1. 11 (2 8)
1/4 NPT FEMALE HIGH PRESSURE PORT
3/4 NPT 2 HOLES
BRACKETWHEN REQUIRED "XBP" VARIATION
1/4 NPT FEMALE LOW PRESSURE PORT
D400 & D700 ASHCROFT®Snap Action Switches for Low Range Differential Pressure Control
D400
2.7 lb
(1.2 kg)
D700
INTRODUCTION
The Ashcroft differential pressure switch is a precision built con­trol device which features a mechanical snap action switch. Controllers are available for operation on various pressure differ­entials with fixed or variable switching differentials.Also, manual reset types are available for operation on increasing or decreas­ing pressure.The manual reset types remain trlpped until reset by pressing a button on the top of the enclosure.The standard electrical switch Is SPDT and is available with various electrical characteristics.Two SPDT switch elements mounted together are available except on variable deadband and manual reset
© 2007 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M009-10009-10/00 (250-2289E) AMR 12/07
STANDARD RANGES
30, 60, 100, 150 ˝H2O Diff.
3.6 lb
(1.6 kg)
types.Various wetted material constructions for compatibility with a wide r
The Ashcroft snap action differentiaI pressure switch is fur nished in the standard NEMA 4 and explosion proof NEMA 7 and 9 enclosure styles alumin
All D400 Series controls with the suffix XG5 as part of their catalog n oil ser on both the high and low side.Controls marked XG5HX are constr
ange of pressure media ma
um castings
.
umber are Underwr
y control so mar
An
.
vice ucted to increase the pressure limit to 40 psi.
ybe obtained.
Both enclosures are epo
.
ies listed for gas and
iters Labor
ed has a pressure limit of 5.4 psi
k
ator
xy coated
-
Installation and Maintenance Instructions for
T
ERMINAL BLOCK
S
WITCH A
TERMINAL BLOCK SWITCH B
2
1
3
2
1
3
NC
NO
C
NC
NO
C
D400 & D700 ASHCROFT®Snap Action Switches for Low Range Differential Pressure Control
INSTALLATION
These controls are precision instruments and should never be
eft with internal components exposed. After installation, ensure
l that the covers are in place and the conduit openings are closed.
OUNTING 0400 AND 0700 SERIES
M
There are three holes external to the enclosure for surface mounting.The locations of these holes are shown on the general
imension drawing.The controls may also be mounted directly
d on the pressure line using the pressure connection.When tight­ening the control to the pressure line, always use the wrench
lats or the hex on the lower housing.
f
For operation as a pressure control, connect the pressure source to the lower port marked “H.” If venting is required, con­nect the vent line to the side port marked “L.” If no venting is required, side port “L” must be left open.
For operation as a differential pressure control, connect the high pressure source to the lower port marked “H” and connect the low pressure source to the side port marked “L.”
ELECTRICAL CONNECTIONS
Remove Cover
D400 Series – two screws hold cover to enclosure D700 Series – cover unscrews
700 SERIES
D SPDT
– Wire directly to the switch according to circuit requirements. 2-SPDT – Wire to front switch terminal block (left) and rear switch terminal block (right) as marked.Strip insulation insert in proper terminal connector, and tighten clamping screw to secure.
D400 AND D700 SERIES Adjustment of Setpoint
7
) is located centrally at the bottom on the inside of the
(
8˝
enclosure.The direction of turning is indicated on a label affixed to the inside of the control enclosure. XG5 controls have a set­point indication scale adjacent to the adjustment nut.To adjust the control, align the top of the adjustment nut hex with the indi­cator line on the scale. Do no force adjustment or attempt to exceed the maximum setting shown on the scale or nameplate.
For accurate setpoint calibration or for controls without a scale mount the control on a calibration stand so that the HIGH and LOW pressures expected under operating conditions may be obtained. Suitable reference standards are necessary for each pressure. Note – Due to the sensitivity of these controls it Is imperative that the LOW pressure side volume be large to prevent a set­point shift between calibration and field installation. If this is not possible, an approximate setpoint under operating conditions can be obtained by setting the operating point with the low side open to atmosphere. A final setpoint adjustment can be made after installation.
Apply the LOW pressure.Then apply the HIGH pressure to the required setpoint and turn the adjustment nut until the switch operates.When the setpoint has been achieved, raise and lower HIGH pressure to ensure that the differential pres­sure between the HIGH and LOW pressures is correct.
After installation of the control, replace the cover to ensure electrical safety and to protect the internal parts from the environment.
CONDUIT CONNECTIONS Note
– It is recommended that Teflon tape or other sealant be used on the conduit, bushing, or plug threads to ensure the integrity of the enclosure.
D400 Series Standard – one 3⁄ D700 Series Standard– tw
4 NPT conduit hole right side.
3
o
4 NPT conduit holes with one
permanent plug. NEMA7 and 9 enclosures require proper con­duit seals and breathers as per the National Electrical Code. D400 and D700 Series – XJL v holes with two
3
1
4 to
2 NPT reducing bushings.
D400 Series – XJK variation – two 3⁄
ariation – tw
4 NPT conduit holes.
3
o
4 NPT conduit
D400 SERIES SPDT
– Wire directly to the switch according to circuit require-
. On controls with pilot lights, wire lights according to
ments circuit diagram on the inside of the cover. See special wiring instruction tag for single switches with two pilot lights and dual switches with one or more pilot lights.
2-SPDT – Dual switching elements consist of two SPDT switches mounted together in a bracket.The switches are calibrated to have simultaneous operation within 1% of range either on increasing or on decreasing pressure, but not in both directions. Wire directly to the front and rear switches according to circuit
uctions f
or pilot light hook up.
requirements. Leads provided on the rear switch and leads provided for hermetically sealed switch elements are color coded as follows: Common – White Normally Closed – Red Normally Open – Blue
See SPDT instr
© 2007 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M009-10009-10/00 (250-2289E) AMR 12/07
D400 AND D700 VARIABLE DEADBAND SWITCHES
Deadband is varied by rotating the wheel on the precision switch.When viewed from the front of the enclosure, rotation to the left increases deadband and rotation to the right decreases deadband.The letters on the wheel may be used as a refer-
Deadbands obtainab
.
ence pressure range depending on the range segment and the type of diaphragm.
Adjustment of Setpoint – As received, the pressure switch wiIl normally be set to approximately 90% of range.Rotate the wheel on the MICRO SWITCH all the way to the right.This will provide the smallest deadband. Pressurize the system to the required setpoint and turn the adjustment nut until the switch changes mode. Lower the pressure to reset the switch. Rotate the wheel on the MICRO SWITCH until the desired deadband is obtained.The upper setpoint will be changing upward with this adjustment. Lower the pressure to reset the switch. Increase the pressure to the desired setpoint and turn the adjusting nut until the switch changes mode.Lower the pres­sure and check the re-setpoint and dead band.
Note – As indicated abo use of the
7
ut.The precision s
8˝ n
screws and bracket adjusting screw are factory sealed and should not be tampered with.
5
16˝,
– A Single setpoint adjustment nut
le will vary from 2% to 9% of the
ve, adjustment of setpoint is made by
witch element mounting