Ashcroft CXLdp INSTALLATION & MAINTENANCE SHEET

MODEL CXLdp DIFFERENTIAL
0
10
12 20 30 36
40
1250
1091 1000
750
500
250
0
OPERATING REGION
PRESSURE TRANSDUCER (4-20mA) INSTALLATION & MAINTENANCE SHEET
DESCRIPTION
The Ashcroft
®
Model CXLdp is a low differential pressure transmitter to be used on clean, dry, non-corrosive gases. It is available in two accuracy classes and its performance is traceable to the U. S. National Institute of Standards and Technology (NIST). The 8 or 4 located in the third position of the product code distinguishes a 0.8% from a 0.4% accuracy transmit­ter. Both unidirectional (e.g. 0 to +1.0 IW) or bi-directional (e.g. ±2.0 IW) models are available. A green LED located on the front of the transmitter indicates power and operational status. The LED light intensity increases as
INSTALLATION
Mounting:
The transmitter can be mounted on a 35 mm DIN rail or with #8 or #10 screws using the 4 mounting holes provided. Torque limits on the mounting holes provided is 6 inch­pounds. (see Figure 3)
pressure increases.
Specifications
Accuracy: ±0.8% F.S.* or ±0.128 mA,
±0.4% F.S. or ±0.064 mA
Output Signal: 4-20 mA, For Bidirectional Ranges 0 IW = 12 mA
Safe Overpressure: 15 psi
Supply Voltage: 12-36 VDC (no regulation required (see Figure 1)
1. Remove the black terminal block on the front of the transmitter.
2. Following the markings on the transmitter label to identify the left, nega-
tive (-) and right, positive (+) terminals. (Ignore the center terminal which is not used.) Connect the power supply positive lead to the posi-
Figure 1 Load Limitations 4-20mA Output
Loop Resistance (Ω)
tive terminal on the plug. Connect the negative power supply lead to the negative terminal BCS 4-20 mA input. Last, connect the (-) negative ter­minal on the CXLdp to the (+) positive BCS input.
3. Firmly reinstall the terminal block plug to its mating connector.
Set Up:
The transmitters are calibrated at the factory in the vertical position. Mounting in the horizontal position can cause a zero shift of as much as ±1% F.S. in ranges below 1 IW dp. Any minor zero offset can be minimized using the zero adjust potentiometer located on the front, left side of the instrument.
To find true zero differential pres­sure, pneumatically connect the high
V
= 12V+ [.022A*(RL)]
min
*includes a 10% safety factor
+ R
R
L =RS
W
RL = Loop Resistance (ohms)
= Sense Resistance (ohms)
R
S
R
= Wire Resistance (ohms)
W
Loop Supply Voltage (Vdc)
Reverse Wiring Protected
Electrical Connection: unpluggable terminal block accepts 12-26 AWG
Operating Temperature: 0-160°F
Enclosure: NEMA 1 Fire-retardant ABS Meets UL 94-5VA
Weight: Approx. 2.5 oz.
Pressure Connection Options:
1
4˝ Brass Barbs or 1⁄8 NPT Female Brass
and low pressure connections together using the tubing provided with the transmitter. The barbed connection accept tubing. (see Figure 4)
1
When
8 NPT female brass fittings are used, do not exceed 60 inch­pound torque force on female NPT fitting.
When connecting to the NPT fittings, do not apply torque to the CXLdp fitting. Use a
9
16˝ wrench to hold the
CXLdp.(see Figure 5)
Zero potentiometer adjustment requires using a
1
Optional:
2˝ conduit or plenum mounting bracket and cover available as separately ordered kit – part num­ber 101A213-01. (see Figure 2)
Figure 2
ted or phillips screwdriver. The tub­ing should remain in place until the transmitter is to be connected to the BCS tubing system.
Routine Maintenance:
The CXLdp is a very stable and reliable transmitter incorporating a proven, micro-machined silicon capacitive sensor and a new, state-of-the­art application specific integrated circuit (ASIC). All calibration and temper­ature compensation functions are done with a microprocessor and digital routines.
* F.S. pressure is equivalnt to the span
of the transmitter (16mA).
© Copyright 2006. Ashcroft Inc. 250 East Main Street 06614, Tel: 203-378-8281 • Fax: 203-378-0499, All specifications are subject to change without notice. All sales subject to standard terms and conditions. www.ashcroft.com, All rights reserved. I&M011-10130 GBE 1M 1/06
1
4˝ O.D. 1⁄8˝ I.D.
3
32˝ or 2.5 mm slot-
Figure 3
Use #10
screw
Zero Pot
Figure 4
Figure 5
or
Use #8 screw
Green LED
– +
+
+
POWER
SUPPLY
BCS
MODEL CXLdp DIFFERENTIAL
4.85
2.06
.78
.88
PRESSURE TRANSDUCER (4-20mA) INSTALLATION & MAINTENANCE SHEET
To troubleshoot or verify performance, it is recommended to pneumatically connect the pressure ports to each other and establish a zero offset reading in the as-installed position. Adjusting zero will not affect span calibration.
Adjusting span should only be attempted when a high accuracy pressure standard and high quality electrical meter are able to be used.
DIN Rail Transmitter Removal:
In order to remove the transmitter when it is installed on a DIN rail, it is neces­sary to first unplug the wiring terminal block from the transmitter.
Insert a small slotted screwdriver into the black plastic clip extending
Figure 6
slightly below the transmitter case.
(see Figure 6)
Next, raise the screwdriver handle up thereby forcing the spring clip down.
If questions or concerns need to be addressed, our low pressure Product Manager or Engineering Personnel can be contacted at (203) 378-8281 or visit our website at www.ashcroft.com.
WIRING DIAGRAM FOR MODEL CXLdp
GENERAL DIMENSIONS FOR MODEL CXL
MB2 1⁄
4˝ BARB FITTINGS
"B2" 1/4 BARB FITTINGS
1.45
Ø.20
POWER
HI LO
ZERO
Ø.16
F01 1⁄
.56
HI LO
ZERO
SPAN
2.90
1.89
8 NPT FEMALE FITTINGS
"01" 1/8 FEMALE NPT FITTINGS
1.45
POWER
SPAN
2.90 3.33
ddpp
(in inches)
3.33
.37
1.32
.37
1.32
Zero adjust potentiometer
ZERO
SPAN
Span adjust potentiometer
1.89
ASSEMBLED WITH 101A213-01 CONDUIT KIT
ASSEMBLED WITH 101A213-01 CONDUIT KIT
4.85
2.06
R .88
.78
© Copyright 2006. Ashcroft Inc. 250 East Main Street 06614, Tel: 203-378-8281 • Fax: 203-378-0499, All specifications are subject to change without notice. All sales subject to standard terms and conditions. www.ashcroft.com, All rights reserved. I&M011-10130 GBE 1M 1/06
Loading...