MODEL CXLdp DIFFERENTIAL
– +
+
––
+
P
OWER
SUPPLY
BCS
SPAN
ZERO
0-10 Vdc
0-5 Vdc
Label Par t No. 238A713- 01
SPAN
ZERO
+
–
POWER SUPPLY
V
Out
Vin (V+, Supply)
Common (V
–)
Z
ero adjust
potentiometer
Span adjust
potentiometer
PRESSURE TRANSDUCER
INSTALLATION & MAINTENANCE SHEET
WARNING! READ
Figure 1 Load Limitations 4-20mA Output
Loop Resistance (Ω)
BEFORE INSTALLATION
1. GENERAL:
A failure resulting in injury or damage may be
caused by excessive overpressure, excessive
vibration or pressure pulsation, excessive
instrument temperature, corrosion of the pressure containing parts, or other misuse. Consult Ashcroft Inc., Stratford, Connecticut, USA
before installing if there are any questions or
oncerns.
c
2. OVERPRESSURE:
Pressure spikes in excess of the rated overpressure capability of the transducer may cause irreversible electrical and/or mechanical damage to
the pressure measuring and containing elements.
3. STATIC ELECTRICAL CHARGES:
Any electrical device may be susceptible to damage when exposed to static electrical charges.
To avoid damage to the transducer the
operator/installer should follow proper ESD
(electrostatic discharge) protection procedures
before handling the pressure transducer.
DESCRIPTION
®
The Ashcroft
Model CXLdp is a low differential
pressure transmitter to be used on clean, dry,
non-corrosive gases. It is available in two accuracy
classes and its performance is traceable to the
U. S. National Institute of Standards and Technology (NIST). The 8 or 4 located in the third position
of the product code distinguishes a 0.8% from a
0.4% accuracy transmitter. Both unidirectional
(e.g. 0 to +1.0 IW) or bi-directional (e.g. ±2.0 IW)
models are available. A green LED located on the
front of the transmitter indicates power and operational status. The LED light intensity increases as
pressure increases.
SPECIFICATIONS
Accuracy: (2) options,specified at time of order.
• ±0.8% span
- (±0.128mA for 4-20mA output units)
- (±0.08V for 0-10Vdc output units)
or
• ±0.4% Span
- (±0.064mA for 4-20mA units)
- (±0.04V for 0-10Vdc output units)
Output Signal: Specified at time of order.
• 4-20ma (For symmetric bidirectional ranges
0IW= 12mA
or
• 0-10Vdc; 0-5Vdc User selectable option (For
symmetric bidirectional ranges 0IW= 5 or
2.5Vdc respectively).
Supply Voltage:
• 4-20mA: 12-36 Vdc (no regulation required)
(see Figure 1)
or
• 0-10Vdc (0-5Vdc User selectable option):
14-36 Vdc or 24 Vac (+/- 20%)
• Supply Current: 6mA (4.5mA for 5Vdc
output option)
© 2011 Ashcroft Inc. 250 East Main Street 06614, Tel: 203-378-8281 • Fax: 203-378-0499, All specifications are subject to change without notice.
All sales subject to standard terms and conditions. www.ashcroft.com All rights reserved. I&M011-10130 Rev. A 10/12
F.S. pressure is equivalnt to the span of the transmitter (16mA).
*
Reverse Wiring Protected
Electrical Connection: unpluggable terminal block
accepts 12-26 AWG
Operating Temperature: 0-160°F
Enclosure:
NEMA 1 Fire-retardant ABS Meets UL 94-5VA
Weight: Approx. 2.5 oz.
Pressure Connection Options:
1
⁄4˝ Brass Barbs or
1
⁄8 NPT Female Brass
Optional:
or plenum mounting bracket and
cover available as
separately ordered
kit – part number
101A213-01.
(see Figure 2)
INSTALLATION
Mounting:
The transmitter
can be mounted
on a 35 mm DIN
rail or with #8 or
#10 screws using
the 4 mounting
holes provided.
Torque limits on
the mounting
holes provided is
6 inch-pounds.
(see Figure 3)
Electrical Wiring:
1. The use of sheilded cable is recommended for
optimum performance. Connect the shield to the
guard terminal on the reading instrument (meter,
etc.) if available or to ground.
2. Remove the terminal block on the front of the
transmitter.
3. Available electrical versions are:
a.) CURRENT 4-20mA; black terminal block.
b.) VOLTAGE 0-5Vdc/0-10Vdc; green terminal
block.
V
= 12V+ [.022A*(RL)]
min
*includes a 10% safety factor
RL =RS + R
RL = Loop Resistance (ohms)
RS = Sense Resistance (ohms)
RW= Wire Resistance (ohms)
Loop Supply Voltage (Vdc)
Figure 2
1
⁄2˝ conduit
Figure 3
Zero Pot
W
Use
#10
screw
or
Use #8
screw
Green LED
Follow the terminal block label markings on the
CXLdp to identify the terminals;
• 4-20mA Ouput: The left, negative (-), and
right, positive (+) terminals are used, ignore
he center terminal which is not used. Con-
t
nect the power supply positive lead to the
Z
ero adjust
p
otentiometer
S
pan adjust
potentiometer
CXLdp positive terminal, connect the negative
power supply lead to the negative terminal of
the BCS 4-20mA input. Last, connect the (-)
negative terminal on the CXLdp to the (+)
positive BCS input.
• 0-10Vdc; 0-5Vdc Output: Follow label mark-
ings for terminal assignments; COM is for
Common (supply and output negative), V
is for supply positive and VOUT is for output
signal. The CXLdp Voltage Output unit is supplied as standard with 0-10 V output, to convert to 0-5 V output see following
instructions.
- 0-10 Vdc Output: Product is supplied as
standard with 0-10 V output, see instruction
below to access the Voltage Output jumper.
- 0-5 Vdc Output: See below for proper
jumper selection. To convert the unit from a
0-10 V output to a 0-5 V output unit note the
following. Access the jumper by simultaneously pushing both housing tabs away from
the housing, see drawings under “General
Dimensions” for
details. Change
Figure 4
jumper (orange)
into position as
shown below,
carefully reattach
housing cover.
When finished
mark check box
on front label indicating that the
unit now provides
a 0 – 5Vdc output.
IN
Jumper
(orange)

MODEL CXLdp DIFFERENTIAL
1
.45
2.90
ÿ
.20
ÿ
.16
3.33
1.89
"B2" 1/4 BARB FITTINGS
1
.32
.37
POWER
HI LO
S
PAN
ZERO
HOUSING TABS (2)
1.45
2.90 3.33
1.89
"01" 1/8 FEMALE NPT FITTINGS
1.32
.
37
POWER
HI LO
SPAN
Z
ERO
.
56
4.854.85
2.062.06
ASSEMBLED WITH 101A213-01 CONDUIT KIT
.78.78
RR .88.88
PRESSURE TRANSDUCER
INSTALLATION & MAINTENANCE SHEET
4. Firmly reinstall the terminal block plug to its
mating connector.
Set Up:
Note: For best immunity from EMI the pressure
connection fittings on the CXLdp should not be
grounded.
The transmitters are calibrated at the factory in the
vertical position. Mounting in the horizontal position can cause a zero shift of as much as ±1% F.S.
in ranges below 1 IW dp. Any minor zero offset can
be minimized using the zero adjust potentiometer
located on the front, left side of the instrument.
To find true zero differential pressure, pneumatically connect the high and low pressure connections together using the tubing provided with the
transmitter. The
barbed connection
1
⁄4˝ O.D. 1⁄8˝
accept
Figure 5
I.D. tubing.
(see Figure 5)
1
⁄8 NPT fe-
When
male brass fittings
are used, do not
exceed 60 inchpound torque force
on female NPT fitting.
Figure 6
When connecting to
the NPT fittings, do
not apply torque to
the CXLdp fitting.
9
⁄16˝ wrench to
Use a
hold the CXLdp.
(see Figure 6)
3
Zero potentiometer adjustment requires using a
⁄32˝
or 2.5 mm slotted or phillips screwdriver. The tubing should remain in place until the transmitter is
to be connected to the BCS tubing system.
(see Figure 7)
Zero and Span Potentiometers
Figure 7
Z
ero adjust
potentiometer
Span adjust
potentiometer
Routine Maintenance:
The CXLdp is a very stable and reliable transmitter
incorporating a proven, micro-machined silicon capacitive sensor and a new, state-of-the-art application specific integrated circuit (ASIC).
All calibration and temperature compensation functions are done with a microprocessor and
digital routines.
To troubleshoot or verify performance, it is recommended to pneumatically connect the pressure
ports to each other and establish a zero offset
reading in the as-installed position. Adjusting zero
will not affect span calibration.
Adjusting span should only be attempted when a
high accuracy pressure standard and high quality
electrical meter are able to be used.
DIN Rail Transmitter Removal:
In order to remove the transmitter when it is installed
on a DIN rail, it is necessary to first unplug the wiring
terminal block from the transmitter.
Insert a small slotted screwdriver into
Figure 8
the black plastic
clip extending
slightly below the
transmitter case.
(see Figure 8)
Next, raise the
screwdriver handle
up thereby forcing
the spring clip down.
If questions or concerns need to be addressed, our
Low Pressure Product Manager or Engineering
Personnel can be contacted at (203) 378-8281 or
visit our website at www.ashcroft.com.
GENERAL DIMENSIONS FOR
MODEL CXLdp (in inches)
MB2 1⁄
4˝ BARB FITTINGS
F01 1⁄
8 NPT FEMALE FITTINGS
ASSEMBLED WITH 101A213-01
CONDUIT KIT
© 2011 Ashcroft Inc. 250 East Main Street 06614, Tel: 203-378-8281 • Fax: 203-378-0499, All specifications are subject to change without notice.
All sales subject to standard terms and conditions. www.ashcroft.com All rights reserved. I&M011-10130 Rev. A 10/12