Data Sheet
AXLdp Low Differential Pressure Transmitter
FEATURES
UL94-V0 rated PBT case
Calibrated ratiometric output
Low voltage power requirement
Easy mounting to PCBs
Available in pressure ranges below 0.5 IWC
TYPICAL USES
Flow Measurements
Room Pressure Control
Energy Management
Fan Control
HVAC and VAV
PERFORMANCE SPECIFICATIONS
Reference
Temperature:
Accuracy Class: ±2.0%, ±1.0% of span
Stability: ≤±0.50% span/year
Media
Compatibility:
ENVIRONMENTAL SPECIFICATIONS
Temperature
Limits:
Thermal Coefficients:
Humidity Effects:
FUNCTIONAL SPECIFICATIONS
Mounting Position: Calibration in vertical position (STD.)
Overpressure
Limits:
Max. Static Line
Pressure:
ELECTRICAL SPECIFICATIONS
Output Signal
(Ratiometric):
Supply Voltage: 4.75 to 5.25 Vdc
70°F ±2°F (21°C ±1°C)
(Terminal Point Method: includes non-linearity,
hysteresis, non-repeatability, zero offset and span
setting errors)
Clean, dry and non-corrosive gas
NOT FOR USE ON LIQUIDS
Storage:
Operating:
Compensated:
Zero & Span: ±0.10% of span/°F (±0.18% Span/°C)
No performance effect at 10-95% R.H.
noncondensing
Proof: Burst:
7.25 psid 11.60 psid
11.60 psi
(10% to 90% of the supplied voltage)
0.5 to 4.5 V with a 5 Vdc supply
–40°F to 158°F (–40°C to 70°C)
–4°F to 140°F (–20°C to 60°C)
37°F to 127°F (3°C to 53°C)
AXLdp
Pressure Transmitter
KEY BENEFITS
• OEM product
• Broad temperature capability
• High performance ASIC based electronics
• Superior long-term stability and repeatability
• Compact design: 1.18” x 1.65” x 0.37”
PHYSICAL SPECIFICATIONS
Pressure Connection:
Mating Electrical
Connection:
Weight: 0.35 oz without leads
Environmental
Rating:
³⁄³²˝ I.D. tubing
JST BHR-03VS-1
IP20, NEMA 1(meets UL94-V0)
All speci fications are subject to change without notice.
All sales subject to standard terms and conditions.
©2019 Ashcroft Inc. AXLdp_transmitter_ds1.0, Rev. B, 07/19
of 31
ashcroft.com
info@ashcroft.com
1.800.328.8258
Data Sheet
AXLdp Low Differential Pressure Transmitter
WETTED MATERIAL
Media
Clean, dry air/gases compatible with Silicon, Glass, Gold, Titanium,
Ceramic, Silicone Rubber, Aluminum and PBT
NOT FOR USE ON LIQUIDS
NON-WETTED
Housing
PBT (meets UL94-VO)
Featuring a highly reliable variable capacitance sensor using the patented
Ashcroft® Si-Glass™ sensor. This ultra-thin single crystal diaphragm provides
inherent sensor repeatability and stability.
Sensor Cross Section
The silicon diaphragm sensor has no glues or
other organics to contribute to drift or
mechanical degradation over time.
ORDERING CODE Example:
Model & Accuracy
AX7 - A XLdp Series, ±1.0% of span
AX9 - A XLdp Series, ±2.0% of span AX9
Pressure Connection
MB3 - 3mm tube stube MB3
Output Signal
RM - 0.5-4.5 Vdc ratiometric ou tput RM
Electrical Termination
NC - No lead s
ST - Leads with JST Connector ST
Pressure Range
Unidirectional Ranges (differential)
P2IW - 0.20 IWD
P25IW - 0.25 IWD
P5IW - 0.50 IWD
P75IW - 0.75 IWD
1IW - 1.00 IWD
2IW - 2.00 IWD 2IW
2P5IW - 2.50 IWD
4IW - 4.00 IWD
5IW - 5.00 IWD
10IW - 10.00 IWD
15IW - 15.00 IWD
20IW - 20.00 IWD
Bi-directional Ranges
P1IWL - ±0.10 IWD
P25IWL - ±0.25 IWD
P5IWL - ±0.50 IWD
1IWL - ±1.00 IWD
2IWL - ±2.00 IWD
2P5IWL - ±2.50 IWD
5IWL - ±5.00 IWD
7P5IWL - ±7.50 IWD
10IWL - ±10.00 IWD
AX9 MB3 RM ST 2IW
Consult factory for custom calibration ranges and other temperature compensation ranges
All speci fications are subject to change without notice.
All sales subject to standard terms and conditions.
©2019 Ashcroft Inc. AXLdp_transmitter_ds1.0, Rev. B, 07/19
of 32
ashcroft.com
info@ashcroft.com
1.800.328.8258