Explosion Proof Differential Pressure
Gauge/Switch, Variation XEK
Types 1130, 1131, 1132
For efficient working of your gauge, please read all instructions
carefully before attempting to install.
CAUTION: Do not exceed maximum operating pressure given
on the gauge label. Check fluid compatibility with wetted parts
before use.
OPERATING PRINCIPLE
Variations in pressure between high and low ports is sensed by
a piston or diaphragm sensor
the pressure difference. A primary magnet
sensor and moves with it in the same proportion. A rotary magnet
with pointer is magnetically coupled with the primary
➂
magnet, and is situated in an isolated cavity. Movement of rotary
magnet with pointer indicates differential pressure on the dial.
Process fluids are isolated from dial case and switch enclosure.
SWITCH: An auxiliary magnet
moves with the pressure sensors. Reed switches mounted on
the extension tube are activated due to interaction between
switch contacts and field of the auxiliary magnet. Switches can
be adjusted to open or close at preset points.
Note: The gauges are calibrated to give ±2%full scale accuracy
on ascending readings.
INSTALLATION
Depressurize the system and connect the high and low pressure lines of your system to the “High” and “Low” ports of the
gauge, respectively.
Apply “High” and “Low” pressures simultaneously, to avoid damage to the internal parts. If pressure exceeds the rated maximum pressure, “O” rings used on male connectors, and the
teflon seal inside the pressure chamber of piston instrument will
be damaged. In diaphragm instrument diaphragm may rupture.
If maximum operating pressure is within the allowable limit, but
the differential pressure exceeds gauge range, there will be no
damage to the gauge. Pointer will only go the extreme right end
of the scale.
which moves in proportion to
➀
situated in the tube extension
➃
is attached to the
➁
EXPLOSION PROOF SWITCH INFORMATION
Switches and electrical connections are mounted in an explosion
proof enclosure with UL, CSA, FM and CENELEC approval. The
enclosure meets Class 1, Groups B, C, D, Class 2, Groups E, F,
3
G, Class, NEMA 7 & 9 and IP66.There are two
⁄4˝ electrical
condiut connections.
PRECAUTIONS
Do not connect “High” and “Low” ports to wrong pipe ends. Do
not subject the gauge to excessive vibration.The gauge is never
to be used in an area where a magnetic field is present. It may
affect readings.
As the gauge works on magnetic coupling principal, use only
non magnetic fittings, parts etc. in areas closer than 2˝ on all
sides, otherwise calibration will be affected.
Do not try to open any part of the gauge for any reason,
because if not reassembled properly, calibration and operation
will be affected.
© 2007 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M008-10100-5/29 AMR 2C09/09
Load
L
(+)
N
(-)
N
(-)
R
R
B
B
Switch #1 Switch
#2
Load
L
(+)
N
(-)
R
B
Switch
#1
6
6
5
5
4
4
3
3
221
1
6
6
5
5
4
4
3
3
221
1
Installation Instructions for ASHCROFT
N
(-)
L
(+)
N
(-)
Load
Load
NC
NO
B
R
Y
6
6
5
5
4
4
3
3
221
1
N
(-)
L
(+)
N
(-)
N
(-)
Load
Load
Load
Load
N
(-)
NC
NC
NO
NO
B
R
Y
Y
B
6
6
5
5
4
4
3
3
221
1
Switch #1
Switch #1 Switch #2
®
Explosion Proof Differential Pressure
Gauge/Switch, Variation XEK
Types 1130, 1131, 1132
WITCH SETTING
S
he switches are normally factory set to save time at customer
T
end. However, they are field adjustable.
CAUTION: Supply voltage should not exceed switch rating. For
higher voltages, the use of relay circuit is recommended.
SWITCH ADJUSTMENT
The following procedure can be done by putting the gauge on a
est bench or while in service.
t
Unscrew the cover of the electrical enclosure. Knurled head set
screws are provided at bottom for setpoint adjustment .
Rotate the screw clockwise (right) to decrease the setpoint and
counter-clockwise (left) to increase the setpoint.
One or two trials may be necessary to attain the exact setpoint.
SPST SWITCH
Specifications
Contact Rating : 10 VA ac (rms) or dc (max)
Switching Current : 0.5 Amp ac (rms) or dc (max)
Switch Voltage : 100 Vac/Vdc (max)
ONE SPST SWITCH
Reed Switches and
Terminal Strip Connection
TWO SPST SWITCHES
Reed Switches and
Terminal Strip Connection
Ground Screw*
SPDT SWITCH
Specifications
Contact Rating : 3 VA ac (rms) or dc (max)
Switching Current : 0.3 Amp ac (rms) or dc (max)
Switch Voltage : 30 Vac/Vdc (max)
Terminal Strip Connection
Switch #1
Set Screws
ONE SPDT SWITCH
Reed Switches and
Switch #2
Set Screws
TWO SPDT SWITCHES
Reed Switches and
Terminal Strip Connection
R = Red; B = Black; Y = Yellow; L = Live or + Supply; N = Neutral or – Supply.
© 2007 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M008-10100-5/29 AMR 2C09/09
Use ground screw to ground enclosure.
*