Ashcroft 1132 User Manual

Installation Instructions for ASHCROFT
S
PST OR SPDT
MAGNET
3/4 NPT
CONDUITPORT
AUXILIARY
SWITCH ENCLOSURE
REED SWITCH
ONE OR TWO
ADJUST
ABLE
3/4 NPT
CONDUIT
PORT
SENSING ELEMENT
PRESS UREEXTENSION
TUBE
HIGH PORT
PISTON OR DIAPHRAGM
R
ANGE
S
CALE
RANGE
SPRING
D. P. GAUGE
HOUSING
LOW
PORT
0
5
10
15
20
25
2
1
3
4
®
Explosion Proof Differential Pressure Gauge/Switch, Variation XEK Types 1130, 1131, 1132
For efficient working of your gauge, please read all instructions carefully before attempting to install.
CAUTION: Do not exceed maximum operating pressure given on the gauge label. Check fluid compatibility with wetted parts before use.
OPERATING PRINCIPLE
Variations in pressure between high and low ports is sensed by a piston or diaphragm sensor the pressure difference. A primary magnet sensor and moves with it in the same proportion. A rotary mag­net
with pointer is magnetically coupled with the primary
magnet, and is situated in an isolated cavity. Movement of rotary magnet with pointer indicates differential pressure on the dial. Process fluids are isolated from dial case and switch enclosure.
SWITCH: An auxiliary magnet moves with the pressure sensors. Reed switches mounted on the extension tube are activated due to interaction between switch contacts and field of the auxiliary magnet. Switches can be adjusted to open or close at preset points.
Note: The gauges are calibrated to give ±2%full scale accuracy on ascending readings.
INSTALLATION
Depressurize the system and connect the high and low pres­sure lines of your system to the “High” and “Low” ports of the gauge, respectively.
Apply “High” and “Low” pressures simultaneously, to avoid dam­age to the internal parts. If pressure exceeds the rated maxi­mum pressure, “O” rings used on male connectors, and the teflon seal inside the pressure chamber of piston instrument will be damaged. In diaphragm instrument diaphragm may rupture. If maximum operating pressure is within the allowable limit, but the differential pressure exceeds gauge range, there will be no damage to the gauge. Pointer will only go the extreme right end of the scale.
which moves in proportion to
situated in the tube extension
is attached to the
EXPLOSION PROOF SWITCH INFORMATION
Switches and electrical connections are mounted in an explosion proof enclosure with UL, CSA, FM and CENELEC approval. The enclosure meets Class 1, Groups B, C, D, Class 2, Groups E, F,
3
G, Class, NEMA 7 & 9 and IP66.There are two
4˝ electrical
condiut connections.
PRECAUTIONS
Do not connect “High” and “Low” ports to wrong pipe ends. Do not subject the gauge to excessive vibration.The gauge is never to be used in an area where a magnetic field is present. It may affect readings.
As the gauge works on magnetic coupling principal, use only non magnetic fittings, parts etc. in areas closer than 2˝ on all sides, otherwise calibration will be affected.
Do not try to open any part of the gauge for any reason, because if not reassembled properly, calibration and operation will be affected.
© 2007 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M008-10100-5/29 AMR 2C09/09
Load
L
(+)
N
(-)
N
(-)
R
R
B
B
Switch #1 Switch
#2
Load
L
(+)
N
(-)
R
B
Switch
#1
6
6
5
5
4
4
3
3
221
1
6
6
5
5
4
4
3
3
221
1
Installation Instructions for ASHCROFT
N
(-)
L
(+)
N
(-)
Load
Load
NC
NO
B
R
Y
6
6
5
5
4
4
3
3
221
1
N
(-)
L
(+)
N
(-)
N
(-)
Load
Load
Load
Load
N
(-)
NC
NC
NO
NO
B
R
Y
Y
B
6
6
5
5
4
4
3
3
221
1
Switch #1
Switch #1 Switch #2
®
Explosion Proof Differential Pressure Gauge/Switch, Variation XEK Types 1130, 1131, 1132
WITCH SETTING
S
he switches are normally factory set to save time at customer
T end. However, they are field adjustable.
CAUTION: Supply voltage should not exceed switch rating. For higher voltages, the use of relay circuit is recommended.
SWITCH ADJUSTMENT
The following procedure can be done by putting the gauge on a
est bench or while in service.
t
Unscrew the cover of the electrical enclosure. Knurled head set screws are provided at bottom for setpoint adjustment .
Rotate the screw clockwise (right) to decrease the setpoint and counter-clockwise (left) to increase the setpoint.
One or two trials may be necessary to attain the exact setpoint.
SPST SWITCH
Specifications
Contact Rating : 10 VA ac (rms) or dc (max) Switching Current : 0.5 Amp ac (rms) or dc (max) Switch Voltage : 100 Vac/Vdc (max)
ONE SPST SWITCH
Reed Switches and
Terminal Strip Connection
TWO SPST SWITCHES
Reed Switches and
Terminal Strip Connection
Ground Screw*
SPDT SWITCH
Specifications
Contact Rating : 3 VA ac (rms) or dc (max) Switching Current : 0.3 Amp ac (rms) or dc (max) Switch Voltage : 30 Vac/Vdc (max)
Terminal Strip Connection
Switch #1
Set Screws
ONE SPDT SWITCH
Reed Switches and
Switch #2
Set Screws
TWO SPDT SWITCHES
Reed Switches and
Terminal Strip Connection
R = Red; B = Black; Y = Yellow; L = Live or + Supply; N = Neutral or – Supply.
© 2007 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M008-10100-5/29 AMR 2C09/09
Use ground screw to ground enclosure.
*
Loading...