ASF ASC Medicare LSC Surveyor User Manual

AAAASF MEDICARE
ASC
Life Safety Code Section
Version 7.0
AMERICAN ASSOCIATION FOR
ACCREDITATION OF
AMBULATORY SURGERY FACILITIES, INC.
Medicare LSC Checklist for Accreditation of Ambulatory Surgery Facilities
Version 7.0 ● Published December 2018 ● Implement February 2019 ● Approved by CMS
November 2018
American Association for Accreditation of Ambulatory Surgery Facilities, Inc. Content provided by Department of Health and Human Services, Centers for Medicare and Medicaid Services
Notice
The materials included in this handbook are provided to assist the surveyor in
assessing the ASC’s compliance with all applicable codes and requirements. This
manual is intended as a survey guide to facilitate the documentation of surveyor findings. The Life Safety Code surveyor must consider all applicable National Fire Protection Association (NFPA) Life Safety Code (LSC), Health Care Facilities Code (HCFC), and reference document requirements when conducting the survey.
ASC Application pg 289
9999.005
Fire Safety
9999
LIFE SAFETY CODE/ HEALTH CARE FACILITY CODES
9999.000.005
9999.005.005
9999.005.025 Compliant Deficient A,B,C-M,C
9999.005.050 Compliant Deficient A,B,C-M,C
___ Compliant ______ Deficient
416.44 Condition
Compliant
The operating room and recovery room have an emergency power sourcesuch as a generator or battery-powered inverterwith capacity to operate adequate monitoring, anesthesia, surgical equipment, cautery, and lighting for a minimum of 2 hours. If 2 or more operation and recovery rooms are used simultaneously, an adequate emergency power source must be available for each room.).
Sufficient electrical outlets are available, labeled and grounded to suit the location (e.g. wet locations, cystoscopy-arthroscopy) and connected to emergency power supplies where appropriate.
All flammable and combustible materials and supplies are stored and handled in a safe manner with appropriate ventilation according to the most stringent requirements from among the LSC and HCFC requirements, State or local authorities.
Deficient
B,C-M,C
9999.005.060 Compliant Deficient A,B,C-M,C
Except as otherwise provided in section 42 CFR 416.44, the ASC must meet the provisions applicable to Ambulatory Health Care Occupancies, regardless of the number of patients served, and must proceed in accordance with the Life Safety Code (NFPA 101 and Tentative Interim Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4).
416.44.b.1
9999.005.065 Compliant Deficient A,B,C-M,C
In consideration of a recommendation by the State survey agency, CMS may waive, for periods deemed appropriate, specific provisions of the Life Safety Code which, if rigidly applied, would result in unreasonable hardship upon an ASC, but only if the waiver will not adversely affect the health and safety of the patients.
416.44.b.2
Standard
Standard
ASC Application pg 299
9999.005.070 Compliant Deficient A,B,C-M,C The provisions of the Life Safety Code do not apply in a State if CMS finds that a fire
and safety code imposed by State law adequately protects patients in an ASC.
416.44.b.3
Standard
9999.005.075
Compliant Deficient A,B,C-M,C
When a sprinkler system is shut down for more than 10 hours, the ASC must:
i)
Evacuate the building or portion of the building affected by the system outage until the system is back in service, or
ii)
Establish a fire watch until the system is back in service.
416.44.b.5
Standard
416.44.b.5.i Standard
416.44.b.5.ii Standard
9999.005.080 Compliant Deficient A,B,C-M,C
An ASC may place alcohol-based hand rub dispensers in its facility if the dispensers are installed in a manner that adequately protects against inappropriate access.
416.44.b.4 Standard
9999.005.085 Compliant Deficient A,B,C-M,C
Beginning July 5, 2017, an ASC must be in compliance with Chapter 21.3.2.1, Doors to hazardous areas.
416.44.b.6 Standard
ASC Application pg 291
9999.005.090 Compliant Deficient A,B,C-M,C Except as otherwise provided in section 42 CFR 416.44, the ASC must meet the
applicable provisions and must proceed in accordance with the 2012 edition of the Health Care Facilities Code (NFPA 99, and Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and TIA 12-6).
416.44.c Standard
9999.005.095 Compliant Deficient A,B,C-M,C
Chapters 7, 8, 12, and 13 of the adopted Health Care Facilities Code do not apply to an ASC.
416.44.c.1
Standard
9999.005.100 Compliant Deficient A,B,C-M,C
If application of the Health Care Facilities Code required under paragraph (c) of this section would result in unreasonable hardship for the ASC, CMS may waive specific provisions of the Health Care Facilities Code, but only if the waiver does not adversely affect the health and safety of patients.
416.44.c.2
Standard
9999.010
Reference Section
9999.010.010
A,B,C-M,C
The standards incorporated by reference in this section are approved for incorporation by reference by the Director of the Office of the Federal Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. You may inspect a copy at the CMS Information
Resource Center,
7500 Security Boulevard, Baltimore, MD or at the National
Archives and Records
Administration (NARA). For information on the availability of this
material at NARA, call
202-741-6030, or go to: http://www.archives.gov/federal_register/ code_of_federal_regulations/ibr_locations.html. If any changes in this edition of the Code are incorporated by reference, CMS will publish a document in the Federal Register to announce the changes.
(1)
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169,
www.nfpa.org, 1.617.770.3000. (i)
NFPA 99, Standards for Health Care Facilities Code of the National Fire
Protection
Association 99, 2012 edition, issued August 11, 2011.
(ii)
TIA 12-2 to NFPA 99, issued August 11, 2011.
(iii)
TIA 12-3 to NFPA 99, issued August 9, 2012.
(iv) TIA 12-4 to NFPA 99, issued March 7, 2013. (v) TIA 12-5 to NFPA 99, issued August 1, 2013. (vi) TIA 12-6 to NFPA 99, issued March 3, 2014. (vii) NFPA 101, Life Safety Code, 2012 edition, issued August 11, 2011; (viii) TIA 12-1 to NFPA 101, issued August 11, 2011. (ix) TIA 12-2 to NFPA 101, issued October 30, 2012. (x) TIA 12-3 to NFPA 101, issued October 22, 2013. (xi) TIA 12-4 to NFPA 101, issued October 22, 2013.
416.44.f Standard
Statement of Deficiency
Official Forms Only Please
Surveyor:
Facility ID:
Date:
□ Condition Level Deficiency
Standard #:
□ Standard Level Deficiency
Approved: June 5, 2014
Implemented: June 5, 2014
Instructions: Include the facts and findings relevant to the deficient practice must answer the questions: who, what, where, when, and how. Illustrate the entity’s noncompliance with the requirement. The deficiency citation must explain how the entity fails to comply with the regulatory requirements, not how it fails to comply with the guidelines for the interpretation of those requirements. Refer to the CMS Principles of Documentation for further instruction.
This standard was NOT MET as evidenced by… (Describe the deficient practice and identify relevant findings and facts that substantiate the failure of compliance.)
Findings include: (Describe each item of non-compliance as observed during the survey relative to the requirement being cited as not met. Remember to quantify findings where possible, i.e. 4/20 records.)
Statement of Deficiency
Official Forms Only Please
Surveyor:
Facility ID:
Date:
□ Condition Level Deficiency
Standard #:
□ Standard Level Deficiency
Approved: June 5, 2014
Implemented: June 5, 2014
Instructions: Include the facts and findings relevant to the deficient practice must answer the
questions: who, what, where, when, and how. Illustrate the entity’s noncompliance with
the requirement. The deficiency citation must explain how the entity fails to comply with the regulatory requirements, not how it fails to comply with the guidelines for the interpretation of those requirements. Refer to the CMS Principles of Documentation for further instruction.
This standard was NOT MET as evidenced by… (Describe the deficient practice and identify relevant findings and facts that substantiate the failure of compliance.)
Findings include: (Describe each item of non-compliance as observed during the survey relative to the requirement being cited as not met. Remember to quantify findings where possible, i.e. 4/20 records.)
Statement of Deficiency
Official Forms Only Please
Surveyor:
Facility ID:
Date:
□ Condition Level Deficiency
Standard #:
□ Standard Level Deficiency
Approved: June 5, 2014
Implemented: June 5, 2014
Instructions: Include the facts and findings relevant to the deficient practice must answer the questions: who, what, where, when, and how. Illustrate the entity’s noncompliance with the requirement. The deficiency citation must explain how the entity fails to comply with the regulatory requirements, not how it fails to comply with the guidelines for the interpretation of those requirements. Refer to the CMS Principles of Documentation for further instruction.
This standard was NOT MET as evidenced by… (Describe the deficient practice and identify relevant findings and facts that substantiate the failure of compliance.)
Findings include: (Describe each item of non-compliance as observed during the survey relative to the requirement being cited as not met. Remember to quantify findings where possible, i.e. 4/20 records.)
Statement of Deficiency
Official Forms Only Please
Surveyor:
Facility ID:
Date:
□ Condition Level Deficiency
Standard #:
□ Standard Level Deficiency
Approved: June 5, 2014
Implemented: June 5, 2014
Instructions: Include the facts and findings relevant to the deficient practice must answer the
questions: who, what, where, when, and how. Illustrate the entity’s noncompliance with
the requirement. The deficiency citation must explain how the entity fails to comply with the regulatory requirements, not how it fails to comply with the guidelines for the interpretation of those requirements. Refer to the CMS Principles of Documentation for further instruction.
This standard was NOT MET as evidenced by… (Describe the deficient practice and identify relevant findings and facts that substantiate the failure of compliance.)
Findings include: (Describe each item of non-compliance as observed during the survey relative to the requirement being cited as not met. Remember to quantify findings where possible, i.e. 4/20 records.)
Page 1
Life Safety Code Survey Guide (10/2016)
PART I Life Safety Code, New and Existing
PART II Health Care Facilities Code, New and Existing
PART III Recommendation for Waiver
PART IV – Crucial Data Extract
Identifying information as shown in applicable records. Enter changes, if any, alongside each item, giving date of change.
2012 LIFE SAFETY CODE
Content provided by the Centers for Medicare & Medicaid Services
2. NAME OF FACILITY
2. (A) MULTIPLE
CONSTRUCTION (BLDGS.)
2. (B) ADDRESS OF FACILITY CODE)
(STATE,
CITY,
ZIP
A. Fully Sprinklered
(All required areas are sprinklered)
B. Partially Sprinklered
(Not all required areas are sprinklered)
C. None (No sprinkler system)
K0180
A. BUILDING B. WING C. FLOOR
K3
Initial Survey Resurvey
Date of Survey
K4
New Existing Number of Stations in ESRD
CHECK ONE Facility is:
DATE OF BLDG. PERMIT OR PLAN APPROVAL
DATE FIRST OCCUPIED AS AMBULATORY SURGICAL CTR.
Physically located in a hospital Free-standing: only occupancy in building
K6
If facility is located in a hospital or hospital owned/operated, was facility surveyed as part of Hospital LSC Survey?
Yes No
Located in an Office Occupancy
Located in a Mercantile/Business Occupancy
Indicate Occupancy
Other (specify) Accredited by Non Accredited
A
The facility MEETS based upon:
1. Compliance with all provisions
2. Acceptance of a Plan of Correction
3. Recommended waivers
4. Performance Based Design
B
The facility DOES NOT MEET THE STANDARD
K9
SURVEYOR (Signature)
TITLE
OFFICE
DATE
SURVEYOR ID
K10
REVIEW AUTHORITY OFFICIAL (Signature)
TITLE
OFFICE
DATE
FORMS SHALL BE COMPLETED AND RETAINED AS PART OF THE SURVEY RECORD.
FIRE SAFETY SURVEY REPORT – AMBULATORY SURGICAL
CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD)
MEDICARE
1. (A) PROVIDER NUMBER
K1
1. (B) MEDICAID I.D. NO.
K2
Name of Facility
2012 LIFE SAFETY CODE
Life Safety Code Survey Guide (10/2016)
Page 2
ID
PREFIX
MET
NOT MET
N/A
REMARKS
PART I – NFPA 101 LSC REQUIREMENTS
(Items in italics relate to the FSES)
SECTION 1
GENERAL REQUIREMENTS
K100
General Requirements – Other
List in the REMARKS section any LSC Section 20.1 and 20.1 General Requirements that are not addressed by the provided K-tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.
K111
Building Rehabilitation
Repair, Renovation, Modification, or Reconstruction
Any building undergoing repair, renovation, modification, or reconstruction
complies with both of the following:
Requirements of Chapter 21
Requirements of the applicable Sections 43.3, 43.4, 43.5, and 43.6
20.1.1.4.3, 21.1.1.4.3, 4.6.7, 43.1.2.1
Change of Use or Change of Occupancy
Any building undergoing change of use or change of occupancy
classification complies with the requirements of Section 43.7, unless
permitted by 20.1.1.4.2 or 21.1.1.4.2
20.1.1.4.2, 21.1.1.4.2, 43.1.2.2 (43.7)
Additions
Any building undergoing an addition shall comply with the requirements of
Section 43.8. If the building has a common wall with a nonconforming
building, the common wall is a fire barrier having at least a 2 hour fire
resistance rating constructed of materials as required for the addition.
20.1.1.4.1, 21.1.1.4.1, 4.6.5, 4.6.7, 43.1.2.3 (43.8)
Name of Facility
2012 LIFE SAFETY CODE
Life Safety Code Survey Guide (10/2016)
Page 3
ID
PREFIX
MET
NOT MET
N/A
REMARKS
K131
Multiple Occupancies – Sections of Ambulatory Health Care Facilities
Multiple occupancies shall be in accordance with 6.1.14. Sections of ambulatory health care facilities shall be permitted to be
classified as other occupancies, provided they meet both of the following:
The occupancy is not intended to serve ambulatory health care occupants for treatment or customary access
They are separated from the ambulatory health care occupancy by a 1-hour fire resistance rating
Ambulatory health care facilities shall be separated from other tenants and occupancies and shall meet all of the following:
Walls have not less than 1-hour fire resistance rating and extend from floor slab to roof slab
Doors are constructed of not less than 1-3/4 inches thick, solid-bonded wood core or equivalent and is equipped with positive latches.
Doors are self-closing and are kept in the closed position, except when in use.
Windows in the barriers are of fixed fire window assemblies per 8.3.
Per regulation, ASCs are classified as Ambulatory Health Care Occupancies, regardless of the number of patients served.
20.1.3.2, 21.1.3.3, 20.3.7.1, 21.3.7.1,42 CFR 416.44
Name of Facility
2012 LIFE SAFETY CODE
Life Safety Code Survey Guide (10/2016)
Page 4
ID
PREFIX
MET
NOT MET
N/A
REMARKS
K161
Building Construction Type and Height
Building construction type and stories meet Table 20.1.6.1 or Table
21.1.6.1, respectively.
Any level below the level of exit discharge shall be separated by Type II (111), Type III (211), or Type V (111) construction unless both of the following are met:
1.
Such levels are under the control of the ambulatory health care occupancy.
2.
Hazardous spaces are protected per section 8.7.
Sprinklered stories must be sprinklered throughout by an approved, supervised automatic system in accordance with section 9.7. (See 20.3.5 or
21.3.5, respectively) Give a brief description, in REMARKS, of the construction, the number of
stories, including basements, floors on which patients are located, location of smoke or fire barriers and dates of approval. Complete sketch or attach small floor plan of the building as appropriate.
20.1.6.1, 20.1.6.2, 21.1.6.1, 21.1.6.2
K163
Interior Nonbearing Wall Construction
Interior nonbearing walls in Type I or II construction are constructed of noncombustible or limited-combustible materials.
Interior nonbearing walls required to have a minimum 2-hour fire resistance rating are fire-retardant-treated wood enclosed within noncombustible or limited-combustible materials, provided they are not used as shaft enclosures.
20.1.6.3, 20.1.6.4, 21.1.6.3, 21.1.6.4
Construction Type
1
I (442), I (332), II (222), II (111), III (211), IV (2HH), V (111)
Any number of stories non-sprinklered or sprinklered
2
II (000), III (200), V (000)
One story non-sprinklered Any number of stories sprinklered
Loading...
+ 35 hidden pages