ascon e33 Operating Instructions Manual

Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 1
e33
DIGITAL ELECTRONIC
TEMPERATURE CONTROLLER
WITH DEFROSTING FUNCTION
OPERATING INSTRUCTIONS
Vr 01 (ENG) - 17/06 - cod.: ISTR-Me33ENG01
Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY Tel.: +39 0381 69871 - Fax: +39 0381 698730
http:\\www.ascontecnologic.com info@ascontecnologic.com
PREFACE
This manual contains the information necessary for the product to be installed correctly and also instruc­tions for its maintenance and use; we therefore recom­mend that the utmost attention is paid to the following instructions and to save it
This document is the exclusive property of Ascon Tecnologic S.r.l. which forbids any reproduction and divulgation, even partially, of the document, unless expressly authorized.
Ascon Tecnologic
S.r.l. reserves the right to make any formal
or functional changes at any moment and without any notice. Ascon Tecnologic S.r.l. and its legal representatives do not
assume any responsibility for any damage to people, things or animals deriving from violation, wrong or improper use or in any case not in compliance with the instrument features.
Whenever a failure or a malfunction of the device may cause dangerous situations for persons, thing or animals, please remember that the plant has to be equipped with additional electromechanical devices which will guarantee safety.
1. INSTRUMENT DESCRIPTION
1.1 General description
The model e33 is a microprocessor based digital electronic temperature controller that is typically used in cooling ap­plications with ON/OFF temperature control and defrost control at time intervals, by arrival at temperature or by length of time of continuous compressor operation through stopping the compressor, electric heating or hot gas/cycle inversion.
The instrument has up to 3 relay outputs and up to 3 NTC
temperature probes inputs one of which can be config­ured as digital input; it can also be equipped with a built-in
buzzer for alarms acoustic report.
Index
1. Instrument description ............................................... 1
1.1 General description ........................................................... 1
1.2 Front panel pescription .....................................................2
2. Programming ............................................................... 2
2.1 Fast Set Point programming ..............................................2
2.2 Standard mode parameters programming ........................ 2
2.3 Parameter protection using the password ......................... 3
2.4 Customized mode parameter programming (parameters
programming level) ...........................................................3
2.5 Reset parameters to default value ....................................3
2.6 Keyboard lock function ...................................................... 3
3. Usage warnings ........................................................... 3
3.1 Admitted use ..................................................................... 3
4. Installation warnings ................................................... 4
4.1 Mechanical mounting ........................................................ 4
4.2 Electrical connections ....................................................... 4
5. Functions ..................................................................... 5
5.1 ON/Stand-by function ........................................................5
5.2 Normal, Economic and Turbo operation ............................ 5
5.3 Measure and display configuration ...................................5
5.4 Digital input configuration .................................................. 6
5.5 Outputs and buzzer configuration ..................................... 6
5.6 Temperature control .......................................................... 7
5.7 Compressor protection function and power-on delay ........ 8
5.8 Defrost control ................................................................... 8
5.9 Evaporator fans control ...................................................10
5.10 Alarm functions ............................................................... 10
5.11 Function of keys / and /Aux ................................ 12
6. Accessories ............................................................... 12
6.1 Parameters configuration by “A01” ..................................12
7. Programmable parameters table .............................. 13
8. Problems, maintenance and warranty ..................... 16
8.1 Notifications .................................................................... 16
8.2 Cleaning .......................................................................... 16
8.3 Warranty and Repairs .....................................................16
8.4 Disposal .......................................................................... 16
9. Technical data ............................................................ 16
9.1 Electrical characteristics ................................................. 16
9.2 Mechanical characteristics .............................................. 16
9.3 Functional features .........................................................17
10. Instrument ordering code ......................................... 17
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 2
1.2 Front panel pescription
e33
P
U
Aux
1 2
3
4
5
9
7
8
10
6
1 : Used for setting the Set Point (short press) and for
programming the function parameters (pressed for 5 s). In programming mode is used to enter in parameters edit mode and confirm the values. In programming mode can be used together with the key to change the pro­gramming level of the parameters. When the keyboard is locked, the keys and used together (hold pressed for 5 s), unlock the keyboard.
2 /Aux: In programming mode is used for decreasing
the values to be set and for selecting the parameters. If programmed using the tFb parameter, when it is pressed for 1 s during normal operation mode, it can perform other functions such as Eco mode selectionf, Aux output control etc. (see “Functions of keys
/
and /Aux”).
3 / : In normal mode (pressed for 5 s) can be used
to start/stop manual defrosting ( ). In programming mode is used for increasing the values to be set and for selecting the parameters. In programming mode can be used together with key to change parameters level. Pressed together with the key for 5 s allows the key­board unlock.
4 / : Used (short press) for displaying the instrument
variables (measured temperatures etc.). In programming mode can be used to return in normal mode (hold for 2 s).
If programmed using the tUf parameter, when it is pressed for 1 s during normal operation mode allows to turn ON/OFF (Stand by) the control action or other functions like the Aux input control etc. (see “
Functions of
keys
/
and /Aux
”).
5 LED dp: Decimal Point, when the instrument is placed in
Stand by mode, this is the only lighted LED. During the normal operation is the decimal point. In programming mode, while the parameter code is displayed, the dot indicates the parameter protection level: not protected (lit up), protected (flashing) and hidden (turned OFF).
6 LED : Indicates the output status (compressor or
temperature control device) when the instrument is programmed for cooling operation; ON (lit up),
OFF (turned OFF) or inhibited (flashing).
7 LED : Indicates the output status (compressor or temper-
ature control device) when the instrument is programmed for heating operation; ON (lit), OFF (turned OFF) or inhib-
ited (flashing).
8 LED : Indicates the alarm status: ON (lit),
OFF (turned OFF) or silenced or stored (flashing).
9 LED : Indicates that the defrost is in progress (on) or
drainage time in progress (flashing).
10 LED : Indicates fan output status ON (on), OFF (off)
or inhibited (flashing).
2. PROGRAMMING
2.1 Fast Set Point programming
The normal mode to program the setpoint is done by mo­mentarily pressing the key, the display shows SP (or SPE) alternated to the programmed value.
To change it press the key to increase the value or to decrease it.
These keys increase or decrease the value one digit at a time, but if the button is pressed for more than one second the value increase or decreases rapidly and after two seconds the speed increases even more in order to quickly reach the desired value.
However, through ted parameter you can determine if and which Set Point can be set with the key rapid procedure.
The parameter can have the following values: oF The Set Points cannot be changed with the key rapid
procedure (pressing/releasing the key, nothing happens);
1
Only SP can be set with this procedure (Normal Set Point);
2 Only SPE can be set with this procedure (Eco Set Point); 3 Both SP and SPE can be set with this procedure; 4 To select the Active Set Point (SP or SPE); 5 Both SP and SPH can be set with this procedure (SPH:
Set Point Turbo or independent Heating Set Point);
6 All the 3 Set Points (SP/SPE/SPH) can be set with this
procedure.
For example, in case the parameter TEd = 1 or 3, the proce­dure is the following:
Press and release the key, the display shows SP alter­nated to the Set Point value. To change the Set Point, press the key to increase the value or to decrease it
If only Set Point 1 is present (TEd = 1), once the desired value is set, press the button to exit the fast programming mode.
If also the Eco Set Point (TEd = 3) can be set, pressing and releasing again the button the display shows SPE alter­nated to its programmed value. To change the value use the and keys as for the SP Set Point value. Once the desired value is correctly set, press the button to exit the fast Set Point change.
For SPH (TEd = 5 or 6) the procedure is the same of the one used for SPE.
To exit the fast Setpoint programming mode push the key after the last Set Point has been displayed or pressing no buttons for about 10 s, after which the display returns to normal operation.
2.2 Standard mode parameters programming
To access the instrument function parameters when pass­word protection is disabled, press the key and keep it pressed for about 5 seconds, after which the display shows the code that identifies the first programmable parameter
The desired parameter can be selected using the / keys, then, pressing the key, the display shows the parameter code alternated to its value that can be changed with the and keys.
Once the desired value has been set, press the key again: the new value is stored and the display shows only the code of the selected parameter
Pressing the and keys, it is possible to select another parameter and change it as described.
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 3
To exit the programming mode, press no keys for about 30 s or keep the key pressed for 2 s.
Previous Param.
Normal mode
Parameter select (Program mode)
Parameters set
Next Param.
2 s
5 s
Increase value
Decrease value
-25.5
sLs -30.0
2.3 Parameter protection using the password
The instrument has a parameter protection function using a password that can be personalised through the tPP parameter
To protect the parameters, set the desired password number in the parameter tPP.
When the protection is active, press the key to access the parameters and keep it pressed for about 5 s, after which the display shows r.p.
Press the key, the display shows 0, using the / keys, insert the programmed password number and press the key
again.
If the password is correct the instrument displays the code of the first parameter and it will be possible to program the in­strument in the same way described in the previous section.
The password protection can be disabled by setting tPP = oF.
Normal
mode
2 s
5 s
Increase value
Decrease value
-25.5
rp 0
sls
Note: If the Password gets lost, just switch OFF and ON the
instrument, push key during the initial test keeping it pressed for 5 s. In this way it is possible to access all the parameters, verify and modify the parameter tPP.
2.4 Customized mode parameter programming
(parameters programming level)
The password hides all the configuration parameters behind a factory set password to avoid unwanted changes to the con­troller parameters.
To make a parameter accessible without having to enter the password when tPP password protection is activate, use the procedure that follows:
Enter the program mode using the tPP Password and select the parameter that must be accessible (no password protection).
Once a parameter is selected, if the dp LED flashes the parameter is programmable by entering the password (is “protected”). If the dp LED is steady ON the parameter is programmable without password (is “unprotected”).
To change the parameter visibility, press the key and keeping it pressed also press the button.
The dp LED changes its state indicating the new level of parameter accessibility (ON = not protected; flashing = password protected).
In case some parameters are not protected, accessing the the programming mode the display first shows the not protected parameters, then the r.p parameter (through which will be possible to access the “protected” parameters).
Normal
mode
2 s
5 s
Increase value
Decrease value
-25.5
r.p
Previous Param.
Not protected
parameter
Parameters set
Password
request
Insert
password
Password OK,
Program Mode
Next Param.
Increase value
Decrease value
AHA 35.0
0 sls
2.5 Reset parameters to default value
The instrument allows the reset of the parameters to values programmed in factory as default
To restore the default parameters value set value -48 at r.p password request Therefore, to make the reset to the default parameters, enable the Password using the tPP parameter so that the r.p setting is requested, at this point insert -48 instead of the programmed access password.
Once confirmed the password with the key the display shows “---” for 2 s therefore the instrument resets all the parameters to factory default setting.
2.6 Keyboard lock function
On the instrument it is possible to completely lock the keyboard. This function is useful when the controller is in an accessible
area and the changes must be avoided. To activate the keyboard lock it is enough program the pa-
rameter tLo to a value different from oF. The
tLo
value is the keys inactivity time after which the key-
board will be automatically locked. Therefore, pressing no buttons for the time set at tLo, the in-
strument automatically disable the normal functions of the keys. When the keyboard is locked, if any of the key is pressed,
the display showss Ln to indicate that the lock is active. To unlock the keyboard it is enough to contemporarily push
+ keys and keep them pushed for 5 s, after which the label LF appears on the display and all the key functions will be available again.
3. USAGE WARNINGS
3.1 Admitted use
The instrument has been projected and manufactured as a measuring and control device to be used accord­ing to EN60730-1 at altitudes operation below 2000 m.
Using the instrument for applications not expressly permitted by the above mentioned rule must adopt all the necessary protective measures.
The instrument MUST NOT BE USED in dangerous environ­ments (flammable or explosive) without adequate protections.
The instrument used with NTC 103AT11 probe (identifiable by the printed code “103AT-11” visible on the sensor part) is compliant with standard EN 13485 (“Thermometers for measuring the air and product temperature for the transport, storage and distribution of chilled, frozen, deep-frozen/quick­frozen food and ice cream”) with the following classification:
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 4
[EN13485 air, S, A, 2, -50°C +90°C] Remember that the end user must periodically check and veri-
fy the thermometers in compliance with standard EN 13486. The installer must ensure that the EMC rules are respected,
also after the instrument installation, if necessary using proper filters.
4. INSTALLATION WARNINGS
4.1 Mechanical mounting
The instrument, in case 78 x 35 mm, is designed for flush­in panel mounting. Make a 71 x 29 mm hole and insert the instrument, fixing it with the provided special brackets.
In order to obtain the declared front protection degree, mount the gasket and use the screw type bracket (both optional).
Avoid placing the instrument in environments with very high humidity levels or dirt that may create condensation or intro­duction of conductive substances into the instrument
Ensure adequate ventilation to the instrument and avoid installation in containers that house devices which may overheat or which may cause the instrument to function at a higher temperature than the one permitted and declared.
Connect the instrument as far away as possible from sources of electromagnetic disturbances such as motors, power re­lays, relays, solenoid valves, etc..
4.1.1 Mechanical dimensions, panel cut-out and mounting [mm]
35
28
12.2
14.5
8
6
6478
e33
P
U
Aux
29
+0.6
71
+0.6
mm
RECOMMENDED
PANEL CUTOUT
min. 12 mm
min. 15 mm
Panel + Gasket max. 12 mm
Brackets
34
4.2 Electrical connections
Carry out the electrical wiring by connecting only one wire to each terminal, according to the following diagram, checking that the power supply is the same as that indicated on the instrument and that the load current absorption is no higher than the maximum electricity current permitted.
As the instrument is built-in equipment with permanent con­nection inside housing, it is not equipped with either switches or internal devices to protect against current overloads: the installation will include an overload protection and a two­phase circuit-breaker, placed as near as possible to the in­strument and located in a position that can easily be reached by the user and marked as instrument disconnecting device which interrupts the power supply to the equipment
It is also recommended that the supply of all the electrical cir­cuits connected to the instrument must be protect properly, us­ing devices (ex. fuses) proportionate to the circulating currents.
It is strongly recommended that cables with proper insulation, according to the working voltages and temperatures, be used.
Furthermore, the input cable of the probe has to be kept sepa­rate from line voltage wiring. If the input cable of the probe is screened, it has to be connected to the ground at only one side.
Whether the instrument is a 12 V version (Power supply code F) it is recommended to use an external TCTR transformer, or with equivalent features (class II insulation) and to use only one transformer for each instrument because there is no insulation between supply and input
We recommend that a check should be made that the parameters are those desired and that the application functions correctly before connecting the outputs to the actuators so as to avoid malfunctioning that may cause irregularities in the plant that could cause dam­age to people, things or animals.
4.2.1 Electrical wiring diagram
Internal
Buzzer
Pr1 Pr3Pr2
Digital Input
Power supply
INPUTS
NO
NO
NONC
C
Out2
Out1
Out3
OUTPUTS
(12 A max. for removable connectors models)
16 FLA
96 LRA
15 A Res.
EN
30 (15) A
61810
Out 1 (H):
15 (15) A
5 FLA
30 LRA
12 A Res.16 (9) AOut 1 (R): 10 (4) A
10 A Res.8 (3) AOut 2: 8 (4) A
2 A Gen. Use5 (1) AOut 3: 2 (1) A
60730
EN UL
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 5
5. FUNCTIONS
5.1 ON/Stand-by function
Once powered the instrument can assume 2 different conditions:
ON: Means that the controller uses the control functions. STAND-BY:
Means that the controller uses no control function and the display is turned off except for the Stand-by LED.
The transition between Standby and ON is equivalent to power ON the instrument providing the electrical power
In case of power failure, the system always sets itself in the condition it was in before the black-out
The ON/Stand-by function can be selected:
– With the key / pressed for 1 s if tUF = 3; – With the key /Aux pressed for 1 s if tfb = 3; – Using the Digital Input if parameter iFi = 7;
5.2 Normal, Economic and Turbo operation
This tool allows to pre-set 3 different Setpoints, Normal - SP, Economic (or Eco) - SPE and Turbo SPH.
Associated with each Setpoint there is the relative differential (hysteresis): Normal - rd, Eco - rEd and Turbo - rHe. Switch- ing between the various modes can be automatic or manual.
5.2.1 Normal/Eco operation selection
This function can be used when you need to switch two func­tional temperatures (eg. Day/Night or week-day/week-end).
SPE
SP
Door
rd
rEd
iEt
time“Norm.”
DAY (Shop open) DAY (Shop open)NIGHT (Shop closed)
“Norm.” “ECO”
The Normal/Eco operation can be selected in manual mode:
– Using the / key if parameter tUF = 2; – Using the /Aux key if parameter tFb = 2; – Using the Digital Input if parameter iFi = 6.
The Normal/Eco operation can be selected in automatic mode:
– Elapsed the iEt time after the door has been closed
(Normal/Eco switching).
– At door opening if the SPE Setpoint is activated by iEt
parameter (Eco/Normal switching).
– Elapsed the itt time after the door has been closed and
from the activation of SPE Setpoint by iEt parameter (Eco/Normal switching).
To use this function, it is necessary to set the Digital Input as: iFi = 1, 2 or 3.
If iEt = oF the selection of Eco/Normal modes via the digital input is disabled.
If itt = oF the time-out switching from Eco to Normal mode is disabled.
Switching to Economic mode is indicated by the label Eco. When idS = Ec the Economic mode is pointed out with a fixed Eco label otherwise the label Eco appears every 10 s alternated to the display set with parameter idS.
When used as a shop widow light (oFo = 3), Eco mode selection is always associated with the Auxiliary Output turn OFF function.
5.2.2 Turbo/Normal/Eco operation selection
Turbo mode can be selected manually:
– Pressing the / key if parameter tUF = 4; – Pressing the /Aux key if parameter tFb = 4; – From digital input if parameter i.Fi = 8;
Turbo mode can be selected automatically:
– Leaving Eco mode (only if rHC = C3) – Every time the instrument is switched ON (only if rHC = C3
and Pr1 > SPE + rEd)
The instrument quits Turbo mode and returns to normal mode automatically at the end of rtC time or manually using the programmed command (key or digital input).
Setting rHC = C3 gives the following operating cycle: At power ON, the instrument starts in the mode it was in
when it was switched OFF (Normal or “Eco”) unless the tem­perature at power ON is > SPE + rEd. In this case (see fig.) a Turbo cycle is automatically initiated.
After time rtC the instrument automatically swiyches to Nor- mal mode. If the door is opened frequently, the instrument remains in Normal mode. If however the door is not opened for time set at iEt parameter, it automatically switches to Eco mode.
The instrument remains in Eco mode until the door is opened again or, if set, until the time-out itt.
On leaving Eco mode the instrument therefore runs a Turbo cycle to allow product temperature to be restored, after which it reverts to Normal mode and so on.
Temp.
SPE Eco
SP
SPH
Turbo
rHd
rEd
itt (2)
rtCrtC
time
Normal TurboECOTurbo
iEt (1)
rd
Pr1
1 The time iEt is reset every time the door is opened and
in the case shown the door is always closed.
2 The time itt stops when the door is opened and the
instrument immediately switches to Turbo mode. In the case shown, the door is always closed.
When in Turbo mode, the instrument shows the characters trb alternated to the normal display indication.
The normal Set Point SP can be set to a value between the one set with parameter SLS and the one set with parameter SHS while the Economic Set Point SPE can be set to a value between the one set with parameter SP and the one set with parameter SHS; the Turbo Set point (SHP) can be set to a value between the one set with parameter SLS and the one set with parameter Sp.
Note: In the following examples the Set Point is generally
indicated as SP and the differential as rd however the instrument will act according to the Set Point and the differential selected as active.
5.3 Measure and display configuration
With parameter iuP it is possible to select the tempera­ture engineering unit and the desired measure resolution (C0 = °C/1°; C1 = °C/0.1°; F0 = °F/1°; F1 = °F/0.1°).
The instrument allows the measure calibration, which can be used to recalibrate the instrument according to applica-
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 6
tion needs, the calibration is made by using parameters iC1 (input Pr1), iC2 (Pr2 input) and iC3 (Pr3 input).
Parameters iP2 and/or iP2 allows to select the instrument usage of Pr2/Pr3 measure as:
EP Evaporator probe: used to managing the defrost and
the evaporator fans (see relative functions).
Au Auxiliary probe; DG Digital Input (see the Digital input functions).
If Pr2/Pr3 input is not used, set iP2/ip3 = oF. Two inputs cannot set to perform the same function.
If two inputs are set to do the same function, this is done only by the P2 input.
Using iFt parameter can be set a software filter for measur­ing the input values in order to decrease the sensibility to rapid temperature changes (increasing the sampling time).
Through the idS parameter is possible to set the variable normally displayed:
P1 Pr1 probe measurement; P2 Pr2 probe measurement; P3 Pr3 probe measurement; SP Active Set Point; EC
Pr1 probe measure if the instrument is in Normal mode,
the label Eco if the instrument is in (Eco mode); OFF If the numerical display must be switched off (oF). When one of the measures is displayed (idS = P1/P2/Ec)
the iCU parameter allows to set an offset that is to be applied only to the displayed variable (all controls will always made according to the correct temperature value, changed only by the calibration parameters).
Regardless of what is set at idS parameter, all the measure­ment variables can be shown pressing the key.
The display alternately shows the code that identifies the variable and its value. The variables are:
Pr1 Probe 1 measurement; Pr2
Probe 2 measurement (on/oFF if Pr2 is a Digital input); Pr3
Probe 3 measurement (on/oFF if Pr3 is a Digital input);
Lt Minimum stored Pr1 temperature; Ht Maximum stored Pr1 temperature. The Peak (min./max.) temperature values of Pr1 probe are
NOT stored in case of power failure. While the controller is
showing the peak values, these can be reset pressing the key for 3 s. At the end of the key pressure, the display shows “---” for an instant to indicate that the min./max. val­ues have been erased and the new peak is the temperature read in that moment.
The system exits the variable dosplay mode after 15 s from the last
key pressure.
It is also noted that the Pr1 probe display can also be changed by “Defrost display lock” function via the ddL parameter (see the Defrost function).
5.4 Digital input configuration
The digital input function (available on terminal 12 or instead of Pr2 input if ip2 = dg) is defined using the iFi parameter and the action is delayed for the time programmed with pa­rameter iti. The iFi parameter can be configured for the following functions:
0 Digital input not active; 1 Cell door opening with NO contact: at input closure (and
after the iti) the instrument displays alternately oP and the variable set at idS parameter. With this mode of operation of the digital input activates also the time set with parameter AoA elapsed which the alarm is activated to warn that the door has been left open. In addition, at door opening, the instrument returns to Normal opera­tion if it was in Eco mode and the Eco mode activation was enabled through parameter iEt;
2 Cell door opening with NO contact: Similar to iFi = 1
but with evaporator fans stop. In addition, at open door alarm intervention (AoA), the fans are restarted;
3 Cell door opening with compressor and fan outputs lock
and NO contact: similar to iFi = 2 but with compressor and fans lock. At open door alarm intervention (AoA) both the fans and the compressor are re-activated.
4 External alarm signal with NO contact: at input closing
(and after the iti time) the alarm is activated and the instrument alternately shows on the display: AL and the variable set with parameter idS;
5 External alarm signal withall control outputs disabled and
NO contact: at input closing (and after the iti time) all the control outputs are disabled, the alarm is activated and the instrument alternately shows on the display: AL and the variable set with parameter idS;
6 Normal/Eco mode selection with NO contact: at input
clos­ing (and after the iti time) the instrument switches to Economic operation mode. Opening the digital input, the instrument returns in Normal operation mode.
7 Instrument On/Off (stand-by) selection with NO contact:
at input closing (and after the iti time) the instrument is switched ON while it is placed in Stand-by mode when the digital input is open;
8 Turbo cycle activation command with NO contact: at in-
put closing (and after the iti time) the instrument starts a Turbo cycle;
-1, -2, -3, etc. - Features identical to the above but obtained through a NC contact and a reversed logic operation.
5.5 Outputs and buzzer configuration
The instrument outputs can be configured by the relative parameters oo1, oo2 and oo3.
The outputs can be configured for the following functions: ot To control
the temperature control device (e.g. Compres­sor). To manage the cooling control device for neutral zone control or Cooling/Heating (rHC = nr or HC);
df To control the defrosting device; Fn To control the evaporator fans; Au To control the auxiliary device; At To control a silenceable alarm device through a contact
that is NO in normal operation then closed when the alarm sounds;
AL To control an alarm that cannot be silenced through
a contact that is NO in normal operation then closed
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 7
when the alarm sounds;
An To control an alarm with a memory function through
a contact that is NO in normal operation then closed when the alarm sounds (see alarm memory);
-t To control a silenceable alarm device through a con- tact that is NC in normal operation then closed when the alarm sounds;
-L Control an alarm that cannot be silenced through a contact that is NC in normal operation then closed when the alarm sounds;
-n To control an alarm with a memory function through a contact that is NC in normal operation then closed when the alarm sounds;
on To command a device that must be turned ON when
the instrument is ON. The output is therefore deac­tivated when the instrument is not powered or is in standby mode. This mode of operation can be used as a control of the shop window lighting, anti-fogging resistors or other utilities;
HE To control a heating device in neutral zone or Cooling/
Heating control mode (rHC = nr or HC);
oF Output disabled. If one of the outputs is configured as auxiliary output (oo1/oo2/
oo3 = Au), its function is set by parameter oFo and its opera­tion can be conditioned by the time set to at parameter otu.
Parameter oFo can be configured for the following functions:
oF Auxiliary output not active; 1 Temperature control output delayed with NA contact:
the auxiliary output is activated with a delay that can be set with parameter otu applied to the output configured as ot. The output is then turned OFF at the same time as the ot output is disabled. This func­tion mode can be used as a command for a second compressor or for all other working utilities according to the same ot output conditions, but which must be delayed after the start up of the compressor to avoid excess electricity absorption;
2 Activation by front key ( or ): the output is ac-
tivated by pressing the keys or suitably con­figured (tUF or tFb = 1). These commands have a bi-stable (toggle) function (at first pression the output is activated, at the second is disabled). In this mode, the Aux output can be turned OFF automatically after the time set at parameter otu. When otu = oF the output is activated and deactivated only manually, using the
or keys or via the digital input. Differently, the output, once activated, is turned OFF automatically af­ter the otu time. This mode of operation can be used as a control of the shop window lighting, anti-fogging resistors or other utilities;
3 Shop window light managed by Normal/Eco mode.
This output will be ON in Normal mode and OFF when in Eco mode operation.
4 Internal Light output managed by digital input. This
output will be ON when door is opened (iFi = 1, 2, 3).
If present, the internal buzzer can be configured by param­eter obu for the following functions:
oF Buzzer always disabled; 1 The Buzzer sounds when an alarm is active; 2 The Buzzer sounds when a key pressed (no alarm); 3 The Buzzer sounds when a key pressed and when an
alarm is active.
5.6 Temperature control
The instrument controls the temperature with an ON/OFF action and operates on the outputs configured as ot and HE depending on the PR1 probe measuring, the acive Set Point/s SP/SPE/SPH, the Hysteresis rd/rEd/rHd and the function mode set with rHC parameter. Using the rHC pa­rameter can be obtained the functions that follow.
C Cooling; H Heating.
SP
Temp.
rd
time
offoff
SP
rd
time
ON
rHC =
C
rHC =
H
offoffON ON ON ON ON
output
ot
output
ot
Pr1
Temp.
Pr1
Depending on the function mode programmed with parameter rHC the differential is automatically considered by the control­ler with positive values for a Refrigeration control (rHC = C) or negative values for a Heating control (rHC = H).
nr Neutral Zone
SP
off off
ON
Temp.
time
rd rd
offoff
rHC
= nr
ON
ON
HE
ot
Outputs
Pr1
When rHC = nr, the output configured as ot operates with a cooling action (like rHC = C) while the output configured as HE operates with a heating action both with the active Set Point (SP/SPE/SPH). The intervention differential (rd/rEd/rHd) is au­tomatically assumed by the controller to have positive values for the cooling action and negative values for the heating action.
HC
Cooling and Heating with independent Set Points
SP
SPH
off off off
Temp.
time
rd
rd
offoff
off
RHC = HC
ON ON ON
ONON
HE
ot
Pr1
Outputs
As in the previous case, when rHC = HC the output config­ured as ot operates with cooling action (like rHC = C) while the output configured as HE operates with heating action. In this case, however, the Set Point for the ot output is the active one between SP, SPE or SPH, while for the HE output the Set Point is SPH.
The intervention differential for the ot output is the active between rd, rEd or rHd and is automati­cally assumed by the controller to have positive values for the cooling action while for the output HE the differential is RHd considered with negative values as for the Heating actions.
In this mode, the activation of the Turbo cycle causes the instrument to operate with Neutral Zone and SPH set point. The time protections described in the next paragraph (PP1/ PP2/PP3) always work on the output configured as ot and have no effect on the HE output.
In the event of a probe error, it is possible to set the instru-
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 8
ment so that that the output continues to work in cycles according to the times programmed with parameter rt1 (activation time) and rt2 (deactivation time).
If a Pr1 probe error occurs, the instrument can continue to activate the ot output for rt1 time, then disables it for rt2 time and so on until the error persists.
By programming rt1 = oF the output, in probe error condi­tion, will always be OFF. On the contrary, programming rt1 to any value and rt2 = oF the output, in probe error condi­tions, will always be on.
Remember that the operation of the temperature controller can be conditioned by the following functions: Compressor protection function and power-on delay, Defrost, Open door and External alarm with output block from digital input.
5.7 Compressor protection function and power-on delay
The “Compressor Protection” function aims to avoid repeated compressor start-ups controlled by the instrument in cooling applications or otherwise can be used to add a timed control on the actuator control output
This function foresees 3 time controls on the switching ON of the output configured as ot.
The protection consists of pre­venting the ot output being switched ON during the times set with parameters PP1, pP2 and PP3 and therefore that any activation occurs only after all times are elapsed.
1 First control (parameter PP1) foresees a delay to ot out-
put activation (switching-ON delay).
SP
Temp.
time
offoff off off
ON
ON
r.d
P.P1
P.P1
ot
ON
Pr1
Output
P.P1 P.P1
2 Second control (parameter PP2) foresees an inhibition to
the activation of the output by a time delay that starts when the output is turning OFF (delay after switching-OFF).
offoff off
ON
SP
time
rd
PP2
ON ON
Temp.
ot
Pr1
Output
PP2 PP2 PP2
3 Third control (parameter PP3) foresees an inhibition to
the activation of the output by a time delay that starts when the output was turned ON last time (delay between two switching-ON).
offoffoff
ON
SP
time
rd
PP3
PP3 PP3
PP3
ON ON
Temp.
ot
Pr1
Output
During the output inhibition the LED OUT (Cool or Heat ) blinks. It is also possible to prevent activation of all the outputs after the instrument is turned ON, for the time set in the param­eter Pod.
During the power ON delay phase, the display shows the indication od alternated with the normal visualization.
All these functions are disabled if the relative parameters are set to OFF (oF).
5.8 Defrost control
The defrost control acts on the outputs configured as ot and dF. The type of defrost is set by the parameter ddt: EL With electrical heating (or By stopping compres-
sor): while defrosting, the output ot is deactivated while the output dF is enabled. The defrost will be by Stopping compressor if not using the dF output;
in With hot gas or Cycle inversion: while defrosting
both the ot and dF outputs are enabled:
no Without compressor output conditioning: while de-
frosting, the output ot continuous to operate in order to control thetemperature, also the output dF is enabled;
Et With electrical heating and defrosting temperature
control: during defrosting, the output ot is deactivated while the output dF operate as evaporator temperature control. In this mode the defrost lenght is by time-out (time ddE). During the defrost, the dF output behaves as an heating mode control with Set Point = dtE, dif­ferential fixed at 1°C and operates with the values of the EP evaporator probe.
5.8.1 Starting automatic defrosts
The automatic control of defrost occours:
– By interval times (regular or dynamic); – By Evaporator temperature; – By continuous compressor running time.
In order to avoid unnecessary defrosting when the evapora­tor temperature is high the dtS parameter allows to set the temperature related to the evaporator probe (probe config­ured as EP) under which defrosts are possible.
Defrost by regular interval time
As an alternative to programmable defrosts, the instrument allows to execute the defrosts at programmed interval time.
Through the ddC parameter, can be set the defrost interval counting mode:
rt At real-time power-ON intervals. The ddi interval is
counted as the total ignition time of the instrument. This mode is the one currently used in the refrigera­tion systems.
ct At time intervals of the compressor operation. The
ddi interval is counted as the sum of the operating times of the ot output (ot output activated). This mode is usually used in refrigeration systems with compres­sor stop defrosting.
cS Defrost cycle at each compressor stop. The instrument
starts a defrost cycle every time the ot output is deac­tivated, when the Set Point is reached or at the expira­tion of the interval set with ddi paramreter. If ddi =
oF the defrost happens only at compressor stop. This mode is used only on particular refrigerating ma-
chines in which is required the maximum evaporator efficiency at each compressor cycle.
To enable automatic defrost at intervals, after setting the ddC parameter as desired between rt, ct or cS, with the ddi pa­rameter select the time interval between the end of a defrost and the beginning of the next.
The time that the instrument must wait to perform the first defrost after power ON can be set with parameter dSd. This allows to perform the first defrost to a different interval from ddi time.
To force the instrument to perform a defrost cycle at each
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 9
power ON (as long as the conditions set with parameters dtS and dtE are satisfied) set parameter dSd = oF.
This allows the evaporator to be permanently defrosted, even when frequent interruptions to power supply occur that may cause the cancellation of the various defrosting cycles.
If instead it is desired that all the defrosts are performed at the same interval time, set dSd = ddi.
Setting ddi = oF the Automatic defrost function by interval is totally disabled (including the first, regardless of the time set to the dsd parameter).
Dynamic Defrost Intervals System
If ddd = 0 the Dynamic defrost is disabled. Note: For this function is necessary to use the evaporator
probe.
To enable the Dynamic Defrost Intervals System, program ddC = rt, ct or cS and set ddd = any value.
Setting ddd = 0, the defrost intervals are those set by the user and the Dynamic Defrost Intervals System is disabled.
This mode allows to dynamically reduce the defrost interval counting (ddi or dSd if is the first defrost), anticipating, when necessary, the defrost execution, all based on an algorithm that detects a drop in the refrigerator thermal exchange performance.
The algorithm estimates a reduction in thermal exchange based on the increase in temperature difference between
Pr1 (cell control) and evaporator probe (probe configured as EP). The result is stored by the instrument when the tem-
perature is close to the Set Point setting. The advantage of the Dynamic Defrost Interval is the possi-
bility to program a defrost interval time longer than normal. In this way, when necessary, the instrument has the pos-
sibility to anticipate the defrost or to start the cycle after the programmed time.
If the system results correctly set, it is possible to avoid many unnecessary defrosting cycles (and therefore to obtain aconsistent energy saving) that may occur with normal op­eration when, to ensure more system efficiency, the defrost­ing interval is programmed with a time that is often too short.
Phase
off off
ON
01 2 3
Temp.
ddi/dSd time to defrost Phases 0, 1
Defrost
off off
DT0
dtE
dtS
Cool
ot
Defrost
dF
SP + rd
SP
Pr1
rd
EP
DT1 DT2 DT3
time to defrost Phase 2
time to defrost Phase 3
time
ON ON ON
Example “dynamic defrost intervals system” with a reduction ddd = 40% and end defrost by temperature.
With the parameter ddd - Defrost interval percentage reduc- tion is possible to establish the percentage of reduction of the remaining time to start defrost when the conditions for the reduction happen.
If parameter ddd = 100% at the first increase of the stored difference of temperature (> 1°) between cell (Pr1) and evaporator (EP) probes a defrost starts immediately.
For correct functioning the instrument needs a first reference
value of the temperature difference between cell and evapora­tor, in this way all variations to the Active Set Point value, to the differential rd, the start of a continuous cycle or a defrost execution deletes this reference value and any reduction can­not be performed until the acquisition of a new reference value.
Defrost by evaporator temperature
The instrument starts a defrost cycle when the evaporator temperature (EP probe) goes below the dtF programmed temperature for dSt programmed time.
This system can be used to guarantee a defrost if the evapo­rator reaches very low temperatures that normally result symptomatic of a bad thermal exchange in comparison to the normal working conditions.
When dtF = -99.9 the function is disabled.
Defrost by continuous compressor running time
The instrument start a defrost cycle when the compressor is turned ON continuously for the time dcd.
This function is used because the continuous operation for an extended period of the compressor is usually symptomatic of a bad thermal exchange in comparison to the normal work­ing conditions.
When dcd = oF the function is disabled.
5.8.2 Manual defrost
To start a manual defrost cycle, press the key / when in Normal operation mode and keep it pressed for about 5 s after which, if the conditions are correct, the LED lights up and the instrument performs a defrost cycle.
To stop a defrost cycle, press the key / during the de­frost and keep it pressed for about 5 seconds.
5.8.3 End of defrosts
The defrost cycle duration can be time based, or, using the evaporator probe (configured as EP) when a specific tem­perature is reached.
If the evaporator probe is not used or the thermostated defrost mode is used (ddy = Et), the cycle length is set by parameter dde.
If the Evaporator Probe (EP) is used and the thermostated electric defrost is not selected (ddy = EL, in, no), the defrost time occurs when the temperature measured by EP probe exceeds the temperature at parameter DtE.
If this temperature is not reached in the time set in the pa­rameter ddE, defrost cycle is interrupted.
To avoid unnecessary defrosting when the evaporator tem­perature is high in modes ddC = rt, ct, cS parameter DtS allows to set the temperature related to the EP probe under which defrosts are possible.
Therefore, in the indicated modes, if the temperature meas­ured by the EP probe is higher than the one set at param­eters dtS and also dtE the defrosting is inhibited.
dtE dts
Defrost
dF
offoffoff
ON ON
AB
Temp.
time
C
(NO defrost)
dde
ddi/dSd
(Defrost)
ddi/dSd
ddi/dSd ddi
(Defrost)
EP
Example: Defrost A ends due to reaching of temperature dtE, defrost B ends at the end of the ddE time as the
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 10
temperature dtE is not reached, defrosting C does not take place as the temperature is higher than dts.
dtE
dts
offoffoff off
ddi/dSd
ON ON ON
time
ddi
(Defrost)
dde
Defrost
dF
Temp.
EP
Example of electric defrost with evaporator temperature control: the defrost end after ddE programmed time. During defrost the dF output switch ON/OFF to control evaporator temperature in heating mode with set point dtE and 1° dif­ferential (Hysteresis).
The active defrost is shown on the instrument display with the lighting up of the LED .
At the end of defrosting, it is possible to delay the new com­pressor start up (output ot) at the time set in parameter dtd to allow the evaporator to drain. During this delay, the LED
flashes to indicate the draining state.
5.8.4 Intervals and defrosts duration in case of
evaporator probe error
In event of evaporator probe error the defrosts occur at inter­vals dEi and duration dEE.
In case an error occurs when the time remaining to the start or the end of defrost is lower than the one normally set with the parameters related to error probe conditions, the start or the end takes place with the shortest time.
These functions are provided because when the EP evapo­rator probe is used, the set defrost endurance time is usually longer than necessary (the time ddE is a security time-out) and in case is used the “Dynamic Intervals Defrost System” the interval is usually set more longer than what is normally programmed into instruments that do not have the function.
5.8.5 Display lock during Defrost
Through parameters ddL and AdA it is possible to define the display behaviour during defrost:
on The ddL parameter locks the display at the last tem-
perature reading during all the defrost cycle until, at the end of defrost, the temperature has not reached the lock value or the value [SP + rd] or is elapsed the time set at parameter AdA
Lb Shows the label dEF during the defrost cycle and PdF
after the defrost until, at the end of defrost, the tem­perature has not reached the lock value or the value [SP + rd] or is elapsed the time set on parameter AdA
oF The display continues showing the temperature meas-
ured by the Pr1 probe during the defrost cycle.
5.9 Evaporator fans control
The control of the evaporator fans on the output configured as Fn depends on some specific control statuses of the instrument and the temperature measured by the evaporator probe (EP).
In the case that the evaporator probe is not used or in error, the Fn output is activated only depending on parameters Ftn, FtF and FFE.
Parameters Ftn and FtF can be used to determine the behavior of the evaporator fans when the ot outupt (compressor) is OFF.
When ot output is OFF, it is possible to set the instrument so
that that the Fn output continues working in cycles according to the times programmed at parameters Ftn (fan activation time) and FtF (fan deactivation time).
When output ot is switched OFF the instrument activates the output Fn for the time Ftn, then deactivates it for the time FtF and so on whilst the otuput ot remains OFF.
Programming Ftn = oF the output Fn in ot OFF condition remains switched OFF.
Programming instead Ftn to any value and FtF = oF the output Fn when ot in OFF condition remains switched ON.
The parameter FFE decides whether the fans must always be switched ON independently of the defrosting status (FFE = on) or switched OFF during defrosting (FFE = oF).
In this later case, it is possible to delay the start up of the fans even after the end of the defrosting of the time set in the parameter FFd. When this delay is active the LED flash­ing to point out that the delay is in progress.
When the evaporator probe is used the fans, as well as be­ing conditioned by the parameters Ftn, FtF and FFE, are also conditioned by a temperature control.
It is possible to determine whether the fans should be disabled when the temperature measured by the evaporator probe is higher than the FFL parameter (too hot) or even when it is lower than the FLF parameter (too cold).
The relative differential that can be set in parameter FdF is also associated with these parameters.
FLF
FFL
Temp.
FdF
FdF
time
offoff offON ON
Ep
Fan
Note: It is necessary to pay attention to the correct use of
this fans temperature control functions because in the typical application of refrigeration the stop of the evaporator fans stops also the thermal exchange.
Remember that the fans functioning can be conditioned by the Door open function by the digital input.
5.10 Alarm functions
The alarm conditions of the instrument are:
– Probe errors E1, -E1, E2, -E2 and E3, -E3; – Temperature alarms Hi and Lo; – External alarm AL; – Door open oP.
The alarm functions acts on LED , on the internal buzzer, if present and configured by the obu parameter and on the desired output if configured by parameters oo1, oo2 or oo3.
Any active alarm condition is signaled lighting up the LED , while the acknowledged alarm status is shown by flashing the LED .
The buzzer (if present) can be configured to point out the alarms by programming parameter obu = 1 or 3 and always acts to signal the acknowlegeable alarms. This means that, when activated, it can be switched OFF by briefly pressing any key.
The possible selections of output parameters for the alarm signalling function are:
At
When the output is to be activated in alarm condition
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 11
and can be deactivated manually by pressing any key of the instrument (typical application for an acoustic signal);
AL When the output is to be activated in alarm condition
but cannot be deactivated manually; it is then deac­tivated only when the alarm status ceases (typical application for a light signal);
An When the output is to be activated in alarm condi-
tion and that remains active even when the alarm status has ceased. The disabling action (recognition of stored alarm) can only be carried out manually by pressing any key when the alarm status has removed (typical application for light signal).
-t when one wants the function described as At but with
an inverse function (output activated in normal condi­tion and disabled in alarm status).
-L This alarm function is similar to AL but with inverse
logic (output active in normal conditions and disabled in alarm status).
-n This alarm function is similar to An but with inverse
working logic (output active in normal conditions and disabled in alarm status).
The instrument offers the possibility to have the alarm memory function activated via the parameter AtA.
If AtA = oF, the instrument cancels the alarm signal when the alarm status ends, if instead AtA = on, the instrument maintains the alarm signal also when the alarm status ends.
To cancel the alarm memory signal, press any key. It must be remembered that if an output function is desired
with an alarm memory (oo1/oo2/oo3 = An/-An) it is necessary to set the parameter AtA = on.
5.10.1 Temperature alarms
The temperature alarm works according to Pr1 or AU probes measurement, the type of alarm set in the parameter AAy the alarm thresholds set in parameters AHA (maximum alarm) and ALA (minimum alarm) and the relative differential AAd.
Through parameter AAy it is possible to set the alarm thresh­olds AHA and ALA as absolute or relative to the active Set Point, must be related to Pr1 or Au probes and if the message Hi (High alarm) and Lo (Low Alarm) are to be displayed at alarm intervention.
Depending on the desired alarm operating mode, parameter
AAy
can be set as:
1 Absolute alarms referred to probe Pr1, displays Hi/Lo; 2 Relative Alarms referred to probe Pr1, displays Hi/Lo; 3 Absolute alarms referred to probe Au, displays Hi/Lo; 4 Relative Alarms referred to probe Au, displays Hi/Lo; 5
Absolute alarm referred to probe Pr1, displays no labels;
6
Relative alarm referred to probe Pr1, displays no labels;
7
Absolute alarm referred to probe Au, displays no labels;
8
Relative alarm referred to probe Au, displays no labels
.
Using some parameters it is also possible to delay the ena­bling and the intervention of these alarms.
These parameters are: APA
Temperature alarm exclusion time on switching ON the instrument if the instrument is in alarm status when it is switched ON. If the instrument is not in alarm status when it is switched on the time APA it is not considered.
AdA Temperature alarm exclusion time at the end of de-
frost cycle (and, if programmed, after the draining) or after a continuous cycle.
AAt Temperature alarms delay activation time. Tempera-
ture alarms are enabled at the end of the exclusion times and are activated after the AAt time when the temperature measured by the probe exceeds or goes below the respective maximum and minimum alarm thresholds. The alarm thresholds are those set at parameters AHA and ALA when the alarms are set as absolute (AAy = 1, 3, 5, 7).
Temp.
AHA
AAd
time
AL
ALA
AAd
offoffoff
ON ON
Hi Lo
Pr1
or they assume the values [SP + AHA] and [SP + ALA] if the alarms are relative (AAy = 2, 4, 6, 8).
AHA
SP
ALA
offoffoff
ON ON
Hi Lo
AL
AAd
AAd
Temp.
time
Pr1
The maximum and minimum temperature alarms can be disa­bled by setting the related parameters AHA and ALA = oF.
The temperature alarms are signalled lighting up the alarm LED ( ) and, if configured, also with the buzzer
5.10.2 External alarm from digital input
The instrument can signal an alarm external to the instrument using the digital input setting iFi = 4 or 5. The instrument signals the alarm turning ON the
alarm LED ( )
and display-
ing AL label alternated to the variable set with parameter Ids. Mode iFi = 4 operates no action on the control output, while
iFi = 5 deactivates the control output at digital input inter- vention.
5.10.3 Open door alarm
The instrument can signal the open door alarm coondition using the digital input setting iFi = 1, 2 and 3. As the digital input is activated, the instrument signals that the door is open showing on the display the oP label alternated to the variable set with parameter ids.
After the delay set with parameter AoA the instrument signals the Open Door alarm with the configured devices (buzzer and/ or Output), lighting up the LED while showing the oP label. At the open door alarm intervention are also re-activated the inhibited outputs (compressor).
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 12
5.11 Function of keys / and /Aux
Two of the instrument keys, in addition to their normal func­tions, can be configured to operate other commands. The
/ key function can be defined using the tUF parameter while the /Aux key via parameter TFb. Both parameters have the same possibilities and can be configured to perform the following functions:
oF The key carries out no function; 1 Pressing the key for at least 1 s, it is possible to enable/
disable, if configured, the auxiliary output (oFo = 2);
2 Pressing the key for at least 1 s, can be sequentially
select a normal or eco operating mode (SP/SPE). A selection has been made the display shows for about 1 s the active Set Point code (SP or SPE);
3 Pressing the key for at least 1 s is possible to switch the
instrument from ON to Stand-by state and vice-versa;
4 Pressing the key for at least 1 s activates/deactivates a
Turbo cycle.
6. ACCESSORIES
6.1 Parameters configuration by “A01”
The instrument is equipped with a connector that allows the transfer from and toward the instrument of the functioning pa­rameters through the device A01 with 5 poles connector.
This device it is mainly usable for the serial programming of some instruments which need to have the same parameters configuration or to keep a copy of the parameters setting of an instrument and allow its rapid retransmission.
The same device allows to connect a PC via USB with which, through the appropriate configuration software for “AT Univer­salConf tools”, the operating parameters can be configured.
To use the device A01 it is necessary that the device or instru­ment are being supplied directly or through the key.
AC supply
Supply adapter
12 VDC
Power supply
Enter
PWS
12 V
A B C
TTL
+-
USB
to PC
USB
Enter
PWS
12 V
A B C
TTL
+-
USB
to PC
USB
For additional info, please have a look at the A01 instruction manual.
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 13
7. PROGRAMMABLE PARAMETERS TABLE
Here below is a description of all the parameters available on the instrument. Some of them may not be present, either due to the fact they depend on the type of instrument or because they are automatically disabled as unnecessary.
Parameter Description Range Def. Note
1
SLS
Minimum Set Point -99.9... HS -50.0
2
SHS
Maximum Set Point LS... 999 99.9
3
SP
Set Point LS ÷ HS 0.0
4
SPE
Set Point Eco SP ÷ SHS 0.0
5
SPH
Turbo Set Point (or indep. Heating Set Point, HC mode) SLS ÷ SP 0.0
6
iuP
Unit of measurement and resolution (decimal point)
C0 °C, resolution 1°; F0 °F, resolution 1°; C1 °C, resolution 0.1°; F1 °F, resolution 0.1°.
C1
7
iFt
Measurement filter
oF Not used;
0.1 ÷ 20.0 s
2.0
8
iC1
Pr1 Probe Calibration -30.0 ÷ +30.0°C/°F 0.0
9
iC2
Pr2 Probe Calibration -30.0 ÷ +30.0°C/°F 0.0
10
iC3
Pr3 Probe Calibration -30.0 ÷ +30.0°C/°F 0.0
11
iCU
Display offset -30.0 ÷ +30.0°C/°F 0.0
12
iP2
Input Pr2 usage
oF Unused; EP Evaporator probe; Au Auxliary probe; dG Digital Input.
dG
13
iP3
Input Pr3 usage dG
14
iFi
Function and logic functioning of the Digital Input (adding the “-” minus sign the logic is inverted)
0 No function; 1 Open Door; 2 Open Door with Fan Lock; 3 Open Door with Fan and Output Lock; 4 External Alarm; 5 External alarm with control output disabling; 6 Normal/Eco select; 7 On/Stand by select; 8 Start a Turbo cycle.
0
15
iti
Digital Input Delay
oF Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
16
iEt
Eco Mode activation delay at Door closed
oF Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
17
itt
Max. time functioning in Eco Mode
oF Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
18
idS
Variable normally displayed
oF Display not lit; P1 Probe Pr1 measure; P2 Probe Pr2 measure; P3 Probe Pr3 measure; Ec Measure Pr1 in Normal mode + ECO label when in ECO mode; SP Active Set Point.
P1
19
rd
Differential (Hysteresis) 0.0 ÷ 30.0°C/°F 2.0
20
rEd
Differential (Hysteresis) in ECO mode
0.0 ÷ 30.0°C/°F
2.0
21
rHd
Differential (Hysteresis) in Turbo mode or Heating in HC mode
0.0 ÷ 30.0°C/°F
2.0
22
rt1
Output activation time for Pr1 probe error
oF Disabled;
-1 ÷ -59 (s) 1 ÷ 99 (min).
oF
23
rt2
Output deactivation time for Pr1 probe error
oF Disabled;
-1 ÷ -59 (s) 1 ÷ 99 (min).
oF
24
rHC
Output operating mode
H Heating; C Cooling; nr Neutral zone; HC Neutral Zone with indep. Set Point; C3
Cooling with3 autom. switch modes.
C
25
rtC
Lengh of Turbo cycle
oF Function disabled;
-1 ÷ -59 (min) 1 ÷ 99 (h).
oF
26
dtE
Defrost stop temperature -99.9 ÷ +999°C/°F 8.0
27
dtS
Defrost enable temperature -99.9 ÷ +999°C/°F 10.0
28
dtF
Defrost start temperature -99.9 ÷ +999°C/°F -99.9
29
dSt
Delay start Defrost by dtF start temperature
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min)
1
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 14
Parameter Description Range Def. Note
30
ddL
Display Lock during defrost
oF Not active; on Active at last measure; Lb Active with label (dEF during defrost and PdF at defrost).
oF
31
dcd
Defrost activation time for continuous compressor operating
oF Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h)
oF
32
dde
Max. defrost duration
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
33
dtd
Compressor delay after defrost (drainage time)
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min)
20
34
ddt
Defrosting Type
EL Electrical heating/stop compressor; in Hot gas/reverse cycle; no Without compressor output condictioning; Et Electrical heating with evaporator temperature control.
EL
35
ddC
Defrosting starting mode
rt Real time intervals; ct “ot” output on time intervals; cS defrost every “ot” switching off (+ rt intervals); cL Do not use.
rt
36
ddi
Defrosting interval
oF Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
37
dSd
Delay first defrost after power-on
oF Defrost at power-on;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
38
ddd
Dynamic Defrost Percentage reduction
0 ÷ 100% 0
39
dEi
Defrosting interval for evaporator probe error
oF Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h)
6
40
dEE
Lengh of defrost cycle for evaporator probe error
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
10
41
Ftn
Fan time activation with ot output (compressor) OFF
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
5
42
FtF
Fan time deactivation with ot output (compressor) OFF
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
43
FFL
High temperature fan deactivation - 99.9 ÷ 999 °C/°F 10.0
44
FLF
Low temperature fan deactivation - 99.9 ÷ 999°C/°F -99.9
45
FdF
Differential fan control 0.0 ÷ 30.0°C/°F 1.0
46
FFE
Fan status during defrost oF - on oF
47
FFd
Fan delay after defrost
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
48
PP1
ot output delay at switching ON
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
49
PP2
ot output delay after switching OFF
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
50
PP3
Min. time between two ot output switching ON
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
51
Pod
Outputs delay at power ON
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
52
AAy
Temperature Alarm 1 type
1
Absolute for Pr1 with label Hi or Lo;
2
Relative to Pr1 with
label Hi or Lo;
3
Absolute for Au with label Hi or Lo;
4
Relative to Au with
label Hi or Lo;
5 Absolute for Pr1 with no label; 6 Relative to Pr1
with no label;
7
Absolute for Au with no label;
8 Relative to Au
with no label.
1
53
AHA
High temperature Alarm threshold
oF Function disabled;
-99.9 ÷ +999°C/°F.
oF
54
ALA
Low temperature Alarm threshold
oF Function disabled;
-99.9 ÷ +999°C/°F
oF
55
AAd
Temperature Alarms Differential 0.0 ÷ 30.0°C/°F 1.0
56
AAt
Temperature Alarms Delay
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
57
AtA
Alarms memory
oF Alarm memory disabled; on Alarm memory enabled;
oF
58
APA
Temperature Alarms delay at power ON
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
2.00
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 15
Parameter Description Range Def. Note
59
AdA
Temperature Alarms delay and unlock display delay after defrost
oF Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
1.00
60
AoA
Open Door Alarm Delay
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
3.00
61
oo1
OUT1 function
oF No function; ot
Temperature control (compr.);
dF Defrost; Fn Fans; Au Auxiliary; At/-t Silenceable alarm; AL/-L Not silenceable Alarm; An/-n Stored Alarm; on ON when the instrument is ON; HE Heating (Neutral zone control).
ot
62
oo2
OUT2 function dF
63
oo3
OUT3 function Fn
64
obu
Buzzer function mode
oF Function disabled;
1 Active for alarms only; 2
Active for key pressed only
;
3
Active for alarms and key pressed
.
oF
65
oFo
Auxiliary output function
oF Function disabled;
1 Control output ot delayed; 2 Manual activation by key or digital inpu; 3 Shop window light with Eco mode (ON with SP, OFF with SPE); 4 Internal light (OFF with door closed and ON with door opened).
oF
66
otu
Time relative to auxiliary output
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
67
tUF
/ Key Function
oF No function; 1 Auxiliary output command; 2 Normal/Eco Mode selection; 3 Switch ON/Switch OFF (Stand-by); 4 Turbo cycle command.
oF
68
tFb
/Aux Key Function oF
69
tLo
Keyboard lock function delay
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 30 (min).
oF
70
tEd
Set Point visibility with key fast procedure
0 None; 1 SP; 2 SPE; 3 SP and SPE; 4 Active SP; 5 SP and SPH; 6 SP, SPE and SPH.
4
71
tPP
Password to Access Parameter functions
oF Function disabled; 001 ÷ 999.
oF
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 16
8. PROBLEMS, MAINTENANCE AND WARRANTY
8.1 Notifications
8.1.1 Error messages
Error Reason Action
E1 -E1 E2 -E2 E3 -E3
The probe may be interrupted (E) or in short circuit (-E) or may measure a value outside the range allowed
Check the probe connec­tion with the instrument and check that the probe works correctly
epr
Internal EEPROM memory error
Press P key
err
Fatal memory error
Replace the instrument or ship to factory for repair
8.1.2 Other messages
Message Reason
od
Delay at power-on in progress
Ln
Keyboard locked
Hi
Maximum temperature alarm in progress
Lo
Minimum temperature alarm in progress
AL
Digital Input alarm in progress
oP
Door Open
dEF
Defrost in progress with ddL = Lb
PdF
Post-defrosting in progress with ddL = Lb
Eco
Eco Mode in progress
trb
Turbo Mode in progress
8.2 Cleaning
We recommend cleaning of the instrument only with a slightly wet cloth using water and not abrasive cleaners or solvents.
8.3 Warranty and Repairs
The instrument is under warranty against manufacturing flaws or faulty material, that are found within 18 months from deliv­ery date. The warranty is limited to repairs or to the replace­ment of the instrument.
The eventual opening of the housing, the violation of the instru­ment or the improper use and installation of the product will bring about the immediate withdrawal of the warranty effects.
In the event of a faulty instrument, either within the period of warranty, or further to its expiry, please contact our sales department to obtain authorisation for sending the instrument to our company.
The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found, without any fees or charge for Ascon Tecnologic, except in the event of alternative agreements.
8.4 Disposal
The appliance (or the product) must be disposed of separately in compliance with the local standards in force on waste disposal.
9. TECHNICAL DATA
9.1 Electrical characteristics
Power supply: 230 VAC, 115 VAC, 12 VAC/VDC ±10%; AC frequency: 50/60 Hz; Power consumption: about 3.5 VA; Inputs: 3 inputs for temperature probes:
NTC (103AT-2, 10 kW @ 25°C);
1 free of voltage digital input as an alternative
to input probe Pr3;
Output: Up to 3 relay outputs:
EN 61810 EN 60730 UL 60730
Out1 (H) - SPST-NO - 30A ­2HP 250V, 1HP 125 VAC
30 (15) A 15 (15) A 15 A Res.,
96 LRA, 16 FLA
Out1 (R) - SPST-NO - 16A ­1HP 250V, 1/2HP 125 VAC
16 (9) A 10 (4) A 12 A Res.,
30 LRA, 5 FLA
Out2 - SPDT - 8A - 1/2HP 250V, 1/3HP 125 VAC
8 (3) A 8 (4) A 10 A Res.
Out3 - SPST-NO - 5A - 1/10HP 125/250 V
5 (1) A 2 (1) A 2 A Gen.
Use
12 A max. for those with removable terminal model;
Relay output Electrical life: 100000 operations; Action type: Type 1.B (EN 60730-1); Overvoltage category: II; Protection class: Class II; Isolation: Reinforced insulation between the low voltage
parts (type C or D power supply and relay output) and front panel; Reinforced insulation between the low voltage parts (type C or D power supply and relay output) and the extra low voltage section (inputs), No insulation between type F power supply and inputs.
9.2 Mechanical characteristics
Housing: Self-extinguishing plastic, UL 94 V0; Heat and fire resistance category: D; Ball Pressure Test as described in EN60730: accessible
parts 75°C; support live parts 125°C;
Dimensions: 78 x 35 mm, depth 64 mm; Weight: about 190 g; Mounting: Incorporated flush in panel (thickness max. 12 mm)
in a 71 x 29 mm hole;
Connections:
Inputs: fixed or removable screw terminal block for
0.2 ÷ 2.5 mm2/AWG 24 ÷ 14 cables; Power supply and Outputs: fixed or removable screw
terminal block or Faston 6.3 mm for 0.2 ÷ 2.5 mm2/ AWG 24 ÷ 14 cables;
Protection degree: IP65 mounted with gasket and screw type bracket (both optional);
Pollution degree: 2; Operating temperature: 0 ÷ 50°C; Operating humidity: < 95 RH% with no condensation; Storage temperature: -25 ÷ +60°C.
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 17
9.3 Functional features
Temperature Control: ON/OFF mode; Defrost control: Interval cycles or evaporator temperature by
electric heating/stopping compressor or hot-gas/reverse cycle;
Measurement range:
NTC: -50 ÷ +109°C/-58 ÷ +228°F; Display resolution: 1° or 0.1° (range -99.9 ÷ +99.9°); Overall accuracy: ±(0.5% fs + 1 digit); Sampling rate: 130 ms; Display: 3 Digit Red or Blue (optional), height 17.7 mm; Software class and structure: Class A; Compliance: Directive 2004/108/CE (EN55022: class B;
EN61000-4-2: 8kV air, 4kV cont.; EN61000-4-3: 10V/m; EN61000-4-4: 2kV supply and relay outputs, 1kV inputs; EN61000-4-5: supply 2kV com. mode, 1 kV\diff. mode; EN61000-4-6: 3V), Directive 2006/95/CE (EN 60730-1, EN 60730-2-9), Control 37/2005/CE (EN13485 air, S, A, 2, -50°C +90°C with probe NTC 103AT11).
10. INSTRUMENT ORDERING CODE
MODEL e33 - = Instrument with mechanical keyboard
a: POWER SUPPLY D = 230 VAC C = 115 VAC F = 12 VAC/VDC
b: OUTPUT 1 (OUT 1) H =
Out1 Relay
SPST-NO 16A-AC1 (f
or resistive loads
)
R =
Out1 Relay
SPST-NO 30A-AC1 (f
or resistive loads
)
d: OUTPUT 3 (OUT 3) R =
Out3 Relay
SPST-NO 5A-AC1 (f
or resistive loads
)
- = No
c: OUTPUT 2 (OUT 2) R =
Out2 Relay
SPDT 8A-AC1 (f
or resistive loads
)
- = No
i, k: RESERVED CODES; ll, mm: SPECIAL CODES
cae33 -b d
e: BUZZER B = Buzzer
- = No
e
f: POWER SUPPLY AND OUTPUT TERMINALS V = Screw terminals (standard) E = Complete removable screw terminals
(step 5.00)
N = Removable screw terminals (step 5.00) F = Faston 6.3 mm
g: INPUT
TERMINALS V = Screw terminals (standard) E =
Complete removable screw terminals
(step 5.00)
N =
Removable screw terminals (step 5.00)
h: DISPLAY I = Red (standard) C = Blue
fgh ll
mm
i j k
j: PACKAGING + BRACKET TYPE B = At package + “Butterfly” type
brackets (standard) C = At package + gasket + screw type bracket
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 18
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 19
Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 20
Loading...