Engineering & Physical Data ACK-E-2009
General Data - Heat Pump (R410A)
MODEL
INDOOR UNIT A5CK 40ER A5CK 40ER
OUTDOOR UNIT A5LC 35CR A5LC 40CR
NOMINAL COOLING CAPACITY - 1Ø / <3Ø>
Btu/h 29200 / <31000> 39000 / <39000>
W 8558 / <9086> 11430 / <11430>
NOMINAL HEATING CAPACITY - 1Ø / <3Ø>
Btu/h 31800 / <33400> 39000 / <39500>
W 9320 / <9789> 11430 / <11577>
NOMINAL TOTAL INPUT POWER (COOLING) - 1Ø / <3Ø> W 2820 / <2770> 3920/ <3840>
NOMINAL TOTAL INPUT POWER (HEATING) - 1Ø / <3Ø> W 2550 / <2550> 3740 / <3610>
NOMINAL RUNNING CURRENT (COOLING) - 1Ø / <3Ø> A 13.6 / <5.2> 17.8 / <6.9>
NOMINAL RUNNING CURRENT (HEATING) - 1Ø / <3Ø> A 12.7 / <5.0> 17.2 / <6.6>
POWER SOURCE - 1Ø <3Ø>
V/Ph/Hz
220 - 240 / 1 / 50 /
<380 - 415 / 3 / 50>
220 - 240 / 1 / 50 /
<380 - 415 / 3 / 50>
EER - 1Ø / <3Ø> W/W 3.03 / <3.28> 2.92 / <2.98>
COP - 1Ø / <3Ø> W/W 3.66 / <3.84> 3.06 / <3.21>
REFRIGERANT TYPE R410A R410A
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE OUTDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE
4 WAY AUTOMATIC LOUVER
(UP & DOWN)
4 WAY AUTOMATIC LOUVER
(UP & DOWN)
OPERATION
WIRELESS OR WIRED MICRO-
COMPUTER REMOTE CONTROL
WIRELESS OR WIRED MICRO-
COMPUTER REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 490 / 1030 490 / 1030
MEDIUM l/s / CFM 410 / 860 410 / 860
LOW l/s / CFM 350 / 740 350 / 740
EXTERNAL STATIC PRESSURE (H/M/L) Pa (in.wg.) 00
SOUND PRESSURE LEVEL (H/M/L) dBA 44 / 41 / 38 44 / 41 / 38
UNIT DIMENSION
( ) - WITH PANEL
HEIGHT mm/in 300 (375) / 11.81 (14.76) 300 (375) / 11.81 (14.76)
WIDTH mm/in 820 (990) / 32.3 (38.98) 820 (990) / 32.3 (38.98)
DEPTH mm/in 820(990) / 32.3 (38.98) 820(990) / 32.3 (38.98)
PACKING DIMENSION
( ) - PANEL
HEIGHT mm/in 335 (110) / 13.19 (4.3) 335 (110) / 13.19 (4.3)
WIDTH mm/in 916 (1030) / 36.1 (40.6) 916 (1030) / 36.1 (40.6)
DEPTH mm/in 916 (1030) / 36.1 (40.6) 916 (1030) / 36.1 (40.6)
WEIGHT (UNIT + PANEL) kg/lb 42+6 / 92.6+13.2 42+6 / 92.6+13.2
CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75
OUTDOOR UNIT
AIR FLOW l/s / CFM 1605 / 3400 1605 / 3400
SOUND PRESSURE LEVEL dBA 58 58
UNIT DIMENSION
HEIGHT mm/in 850 / 33.5 850 / 33.5
WIDTH mm/in 1030 / 40.6 1030 / 40.6
DEPTH mm/in 400 / 15.8 400 / 15.8
PACKING DIMENSION
HEIGHT
mm/in 1000 / 39.4 1000 / 39.4
WIDTH mm/in 1200 / 47.2 1200 / 47.2
DEPTH mm/in 560 / 22.1 560 / 22.1
UNIT WEIGHT kg/lb 95 / 209 100 / 221
PIPE CONNECTION
TYPE FLARE VALVE FLARE VALVE
SIZE
LIQUID mm/in 9.51 / 3/8 9.5 / 3/8
GAS mm/in 15.9 / 5/8 15.9 / 5/8
REFRIGERANT CHARGE kg/lb 2.175 / 4.80 / <2.15 / 4.74> 2.45 / 5.40 / <2.425 / 4.35>
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.5m BELOW FASCIA.