ASCO Safety Manual: Series DPS280 DVS280 Manuals & Guides

Do not use corrosive or flammable gases or liquid with this product.
Please use within the rated pressure range. Do not apply pressure beyond recommended maximum pressure, permanent damage to the pressure sensor may occur.
Do not drop, hit or allow excessive shock. Even if switch body appears undamaged, internal components may be broken and can cause malfunction.
Turn power off before connecting wiring. Incorrect wiring or short circuit will damage and / or cause malfunction.
Do not use in environment where steam or oil vapor is present.
Avoid wiring the sensor cable adjacent to or in the same cable tray with power or high voltage lines. Doing so could cause malfunction due to noise.
This product is not a safety sensor. Its use is not intended to protect life and prevent bodily injury or property damage from dangerous parts or machinery. It is a normal object detection sensor.
SPECIFICATIONS
DPS280
(PRESSURE)
DVS280
(VACUUM)
Rated pressure range
0 ~ 1000 kPa
0 ~ 145 PSIG
0.0 ~ - 101.3 kPa
0 ~ 29.9" Hg Vacuum
Operating / Set pressure range
-100 ~ 1000 kPa
- 14.5 PSIG ~ + 145 PSIG
10.0 ~ - 101.3 kPa
1.45 PSIG ~ 29.9" Hg Vacuum
Maximum pressure 1500 kPa 300 kPa
(Exceeding max pressure could damage switch)
217.5 PSIG 43.5 PSIG
Fluid Air, Non-corrosive gases, incombustible gases
Set pressure resolution
kPa 1 0.1
kgf/cm
2
0.01 0.001
bar 0.01 0.001
psi 0.1 0.01
InHg - 0.1
mmHg - 1
Power supply voltage 12 to 24VDC ± 10 %, Ripple (P-P) 10 % or less
Current consumption 45mA (with no load)
Switch output
Repeatability (Switch output) ± 0.2 % F.S. ± 1 digit
Hysteresis mode Window comparator mode
Adjustable
Response time
2.5ms (chatter-proof function: 24ms, 250ms, 500ms, 1000ms and
1500ms selections)
Output short circuit protection Yes
7 segment LCD display Two color (red/green) display (sampling rate: 5 times/1sec.)
Indicator accuracy ± 2.0 % F.S. ± 1 digit (ambient temp: 77°F ± 5°F / 25°C ± 3°C)
Switch ON Indicator Green OUT Indicator
Environment
Enclosure IP40
Ambient temp. range
Operation: 0°F ~ 122°F / 0°C ~ 50°C, Storage: 14°F ~ 140°F / -10°C ~
60°C
(no condensation or freezing)
Ambient humidity range Operation/Storage: 35 ~ 85% RH (no condensation)
Withstand voltage 1000VAC in 1-min (between case and lead wire)
Insulation resistance 50Mohm min. (at 500 VDC, between case and lead wire)
Vibration
Total amplitude 1.5mm, 10Hz-55Hz-10Hz scan for
1 minute, two hours each direction of X,Y and Z
Shock 100m/s
2
(10G), 3 times each in direction of X,Y and Z
Temperature characteristic
± 2% F.S. of detected pressure (77°F / 25°C) at temp.
Range of 0°F ~ 122°F / 0°C ~ 50°C
Port size 1/8 NPT Male x 10-32 UNF Female, 1/8 PT x M5, G 1/8 x M5
Lead wire Oil-resistant cable (0.15 mm
2
)
Weight
Approx 45g - Switch only
Approx 90g - Switch with 2M mating cable
PNP open collector
Max. load current: 125mA
Max. supply voltage: 24VDC
Residual voltage:  1.5V
(load current 125mA)
NPN open collector
Max. load current: 125mA
Max. supply voltage: 30VDC
Residual voltage:  1.5V
(load current 125mA)
8
6
7
5
4
3
2
DPS280 / DVS280 Series
1
DPS280 / DVS280 Series
1
NPN output
DC (+)(Brown)
OUT (Black)
DC (-)(Blue)
Switch main circuit
PNP output
DC (+)(Brown)
OUT (Black)
DC (-)(Blue)
Switch main circuit
OUTPUT CIRCUIT WIRING
HOW TO ORDER
PANEL INSTRUCTIONS
PINOUT
Pressure Unit Display Section
2 Colors Main Display
Setting Mode Display Section
Button
Button
Set
Button
Key Lock Indicator
Output Indicator
(Green)
(1) Brown (+)
MALE
(switch end)
(2) White (NOT USED) (3) Blue (-) (4) Black (OUT)
2
4
1 3
PINOUT
Type DPS = Digital Pressure Switch DVS = Digital Vacuum Switch
Output Type 280P = PNP Digital Output Only 280N = NPN Digital Output Only
Example: DPS280PNQ8 = Digital Pressure Switch - PNP - 1/8 NPT - 8mm Pico 4 Pin w/ 2M Mating Cable
DPS 280P N Q8
Electrical Connection Q8 = 8mm Pico Quick Connect
4 Pin w/ 2M Mating Cable
Port Type N = 1/8 NPT Male X 10-32 F R = 1/8 PT X M5 G = G 1/8 X M5
emale
ERROR CODE INSTRUCTION
PRESSURE UNIT CONVERSION TABLE
Turn power off and check the cause of overload current or
lower the current load under 125 mA, then restart.
Excess load current error
Residual pressure error
Applied pressure error
System Error
Change input pressure to ambient pressure and perform
zero calibration again.
Adjust the pressure within operating pressure range.
Cycle power and restart. If error condition persists
please contact factory for help.
Output load current is more than 125 mA
During zero calibration, ambient pressure is over ±3% F.S.
Applied pressure exceeds the upper limit of the
operating / set pressure range.
Applied pressure exceeds the lower limit of the
operating / set pressure range.
Internal data error
Internal data error
Internal system error
Internal system error
DPS280 / DVS280 Series
2