ASCO Maintenance Guide: I&M RCS 2oo3B Sheet | ASCO Manuals & Guides

I&M V_9958_AA
ASCO Redundant Control System
2oo3B Enclosure without Diagnostics 2oo3BP Panel Mount without Diagnostics
Operation & Maintenance Guide
ASCO Valves® E301722 - 10/2020 All Rights Reserved. I&M V_9958_AA
©
ASCO, L.P. 160 Park Avenue, Florham Park, New Jersey 07932 www.emerson.com Page 1 of 7
Redundant Control System
Table of Contents
PRODUCT DESCRIPTION.................................3
GENERAL SPECIFICATIONS ..............................4
INSTALLATION ..........................................4
Section 1. - Normally Closed............................... 6
1. General Operation and Testing ..........................................6
2. Maintenance: Valve Replacement........................................6
Section 2................................................ 7
1. Functional Test Certication ...........................................7
2. Spare Parts .........................................................7
3. Packaging ..........................................................7
4. Disclaimer .........................................................7
Page 2 of 7 I&M V_9958_AA
©
ASCO, L.P. 160 Park Avenue, Florham Park, New Jersey 07932 www.emerson.com
Documentation Conventions
MOUNTING BRACKETS TOP (2)
PNEUMATIC MANIFOLD
MOUNTING BRACKETS BOTTOM (2)
PNEUMATIC CONNECTIONS
BREATHER/DRAIN
EXTERNAL GROUNDING/
EARTHING CONNECTION
INTERNAL GROUNDING/
EARTHING CONNECTION
FIELD WIRING TERMINAL BLOCK
ENCLOSURE NEMA 4, 4X
SIZE: 20" x 16" x 8"
SOLENOID OPERATED VALVE (S0V 1)
SOLENOID OPERATED VALVE (S0V 2)
SOLENOID OPERATED VALVE (S0V 3)
This guide uses the following typographic conventions:
EXAMPLE
NOTE
Notes containing supplementary information.
This symbol precedes information about potential equipment damage.
This symbol precedes information about potential personnel hazards.
Description
User Experience Prerequisites
To eectively use the Pneumatic RCS, users should have some experience with pneumatic systems.
Warnings!
READ THIS ENTIRE MANUAL AND ALL RELATED PUBLICATIONS PERTAINING TO THE WORK TO BE PERFORMED BEFORE INSTALLING, OPERATING OR SERVICING THIS EQUIPMENT.
Follow all appropriate safety codes and standards.
Failure to follow instructions may result in personal injury
and/or property damage.
Use extreme caution when working around power­input cables. These cables may have potentially lethal or dangerous voltages.
Prior to energizing the equipment, have qualified personnel verify all wiring and connections against vendor drawings.

PRODUCT DESCRIPTION

The RCS is a Two-Out-Of-Three (2oo3) solenoid operated valve system designed for use as a component in safety instrumented systems. It functions as a redundant pneumatic tripping device to control the pilot air signal to a process valve actuator. The RCS uses 2oo3 voting solenoids to enhance the reliability of the circuit. The RCS consists of three electrically actuated solenoid valves (SOVl, SOV2 & SOV3).
The RCS is available with a NEMA 4, 4x enclosure with terminal strips (2oo3B) or as a stand alone panel mount version without enclosure (2oo3BP).
Under normal operating conditions: The RCS allows for periodic testing of the solenoids by cycling one solenoid valve and then the other either manually or automati-
Incorrect wiring and/or connections can result in equipment damage or serious system failure. If you have questions or need more information on installing and operating ASCO equipment, contact ASCO.
Avertissements!
LISEZ LE MANUEL COMPLET AINSI QUE LES PUBLICATIONS RELATIVE AU TRAVAIL À EFFECTUER AVANT D’INSTALLER, D’UTILISER OU DE MAINTENIR CET ÉQUIPEMENT.
Suivez toutes les procédures et normes relatives à la sécurité appropriées.
Le non-respect des instructions peut entrainer des blessures corporelles et/ou des dommages matériels
Travaillez avec une extrême précaution à proximité des câbles de puissance. Ces câbles peuvent présenter potentiellement des tensions mortelles ou dangereuses.
Avant de mettre l’équipement sous tension, faites vérifier le câblage et les connexions par du personnel qualifié par rapport aux plans du fournisseur. Un câblage et/ou des connexions erronée peuvent endommager l’équipement et provoquer une grave défaillance du système. Si vous aves des questions ou avez besoin de plus d’informations sur l’installation et l’utilisation des équipements ASCO, contactez ASCO.
cally therefore attaining the desired safety availability. This testing is performed online without the need for bypassing of the safety action and without interruption of the process.
Normally Closed Construction: The RCS supplies air to the process valve actuator through the “Process” port when energized.
When a trip occurs: Normally Closed Construction: the RCS blocks the incoming
pneumatic signal and connects the “Process” port to the “Exhaust” port. This vents the air signal from the process valve actuator and allows the actuator return spring to move the process to its fail-safe position.
For proper operation, a pneumatic pressure of 0 -150 PSI must be supplied to the RCS INLET connection, and a pressure of 40 -150 psi supplied to the PILOT connection.
Figure 1A. RCS 2oo3B with Enclosure Components (Approx. Weight 29.5 kg., 65 lbs.)
Page 3 of 7 I&M V_9958_AA
©
ASCO, L.P. 160 Park Avenue, Florham Park, New Jersey 07932 www.emerson.com
Loading...