ASCO Maintenance Guide: I&M RCS 2oo2D Sheet | ASCO Manuals & Guides

I&M V_9957_AA
ASCO Redundant Control System
2oo2D Enclosure with Proximity Sensor Diagnostics
Operation & Maintenance Guide
ASCO Valves® E301722 - 10/2020 All Rights Reserved. I&M V_9957_AA
©
ASCO, L.P. 160 Park Avenue, Florham Park, New Jersey 07932 www.emerson.com Page 1 of 10
Operation & Maintenance Guide
Redundant Control System
Table of Contents
Table of Contents
PRODUCT DESCRIPTION � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3 GENERAL SPECIFICATIONS � � � � � � � � � � � � � � � � � � � � � � � � � � � � �4 INSTALLATION � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4
Section 1� - Normally Closed � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
1. General Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2. Testing and Maintenance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Section 2� - Normally Open � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
1. General Operation and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2. Testing and Maintenance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Section 3� - Double Acting � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9
1. General Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2. Testing and Maintenance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Section 4� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
1. Functional Test Certication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2. Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4. Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Page 2 of 10 I&M_V_9957_AA
ASCO, L.P. 160 Park Avenue, Florham Park, New Jersey 07932 www.emerson.com
Documentation Conventions
This guide uses the following typographic conventions:
EXAMPLE
NOTE
Notes containing supplementary information.
This symbol precedes information about potential equipment damage.
This symbol precedes information about potential personnel hazards.
Description
User Experience Prerequisites
To eectively use the Pneumatic RCS, users should have some experience with pneumatic systems.
Warnings!
READ THIS ENTIRE MANUAL AND ALL RELATED PUBLICATIONS PERTAINING TO THE WORK TO BE PERFORMED BEFORE INSTALLING, OPERATING OR SERVICING THIS EQUIPMENT.
Follow all appropriate safety codes and standards.
Failure to follow instructions may result in personal injury
and/or property damage.
Use extreme caution when working around power-input cables. These cables may have potentially lethal or dangerous voltages.
Prior to energizing the equipment, have qualified personnel verify all wiring and connections against vendor drawings.
PRODUCT DESCRIPTION
The RCS is a two-out-of-two (2oo2) or one-out-of-one hot standby (1oo1 HS) voting, solenoid-operated valve system designed for use as a component in safety instrumented systems. It functions as a redundant pneumatic tripping device to control the pilot air signal to a process valve actuator. The RCS uses 2oo2 or 1oo1 HS voting solenoids to enhance the reliability of the circuit. The RCS consists of two electrically actuated solenoid valves (SOV1, SOV2) and a pneumatically operated (Manually Controlled) bypass valve, and three proximity sensors. The proximity sensors provide solenoid state feedback and are used during on-line testing of the RCS unit. The bypass valve allows for maintenance of the solenoid valves without having to shut down the process valve. The use of the Maintenance Bypass Valve is not required for functional testing of the RCS unit. The type of operation (2oo2 NC, 2oo2 NO, 2oo2 DA, 1oo1HS NC, 1oo1HS NO) must be specified by the customer at the time of order.
Under normal operating conditions:
The RCS allows for periodic testing of the solenoids by cycling one solenoid valve and then the other either manually or automatically therefore attaining the desired safety availability. This testing is performed online without the need for bypassing of the safety action and without interruption of the process.
For all constructions, three proximity sensors are included to provide indication of each solenoid-operated valve and bypass valve position.
Normally Closed Construction: The RCS supplies air to the process valve actuator through the “Process” port when energized.
Normally Open Construction: the RCS blocks the incoming pneumatic signal and connects the “Process” port to the “Exhaust” port when energized.
Double Acting Construction: the incoming pneumatic control signal passes through the RCS to one side (C2) of the process valve actuator while the other side (C1) of the process valve actuator is vented through the RCS when energized. The 1oo1 HS mode cannot be used with the double acting construction�
Incorrect wiring and/or connections can result in equipment damage or serious system failure. If you have questions or need more information on installing and operating ASCO equipment, contact ASCO.
Avertissements!
LISEZ LE MANUEL COMPLET AINSI QUE LES PUBLICATIONS RELATIVE AU TRAVAIL À EFFECTUER AVANT D’INSTALLER, D’UTILISER OU DE MAINTENIR CET ÉQUIPEMENT.
Suivez toutes les procédures et normes relatives à la sécurité appropriées.
Le non-respect des instructions peut entrainer des blessures corporelles et/ou des dommages matériels
Travaillez avec une extrême précaution à proximité des câbles de puissance. Ces câbles peuvent présenter potentiellement des tensions mortelles ou dangereuses.
Avant de mettre l’équipement sous tension, faites vérifier le câblage et les connexions par du personnel qualifié par rapport aux plans du fournisseur. Un câblage et/ou des connexions erronée peuvent endommager l’équipement et provoquer une grave défaillance du système. Si vous aves des questions ou avez besoin de plus d’informations sur l’installation et l’utilisation des équipements ASCO, contactez ASCO.
When a trip occurs:
Normally Closed Construction: the RCS blocks the incoming
pneumatic signal and connects the “Process” port to the “Exhaust” port. This vents the air signal from the process valve actuator and allows the actuator return spring to move the process to its fail-safe position.
Normally Open Construction: the RCS supplies air to the process valve actuator through the “Process” port. This allows the actuator to move the process to its fail-safe position.
Double Acting Construction: (C2) of the process valve actuator is vented through the RCS while the pneumatic control signal is applied to (C1) of the process valve actuator. This causes the process valve actuator to move from its normal operating position to its fail-safe position.
HARDWARE
For proper operation, a pneumatic pressure of 0-150 PSI must be supplied to the RCS [process connection] while a pressure of 40-150 PSI must be supplied to the [pilot connection]. It is housed in a 20” x 16” x 8” enclosure. The primary components include:
Hard anodized aluminum manifold body
Two low power solenoid-operated ISO-3 valves
A key-actuated bypass valve. (Lever Optional)
Three proximity sensors/switches
An electrical terminal block for wiring termination (ATEX rated Ex e IIC)
Associated wiring.