Installation manual
Manuel d'installation
Installationshandbuch
DP-IM14152.R4
INSTALLATION
GB
FR
DE
SUMMARY
SOMMAIRE
INHALT
Page Seite
English version _____________________________________________________ 3
Version française ___________________________________________________ 11
Deutsche Version ___________________________________________________ 19
IM14152-2
Control
D
GB
Controller Module
Series 603
for Proportional Valve Control
Installation manual
DP-IM14152-GB.R4
INSTALLATION
GB
ESD
!
CONTENTS
1. Description .................................................................................................................................................. 5
1.1 Catalogue numbers ............................................................................................................................ 5
1.2 Operating elements ............................................................................................................................ 5
1.3 Manual adjustment ............................................................................................................................ 6
1.3.1 Manual operation ......................................................................................................................... 6
1.3.2 Auto-adapt ................................................................................................................................... 6
1.4 Operating modes ............................................................................................................................... 6
2. Electrical connection ....................................................................................................................................6
3. Factory settings ............................................................................................................................................ 7
4. Field-programmable settings ........................................................................................................................ 8
5. Technical characteristics ............................................................................................................................. 8
5.1 General ..............................................................................................................................................8
5.2 Construction ....................................................................................................................................... 8
5.3 Electrical characteristics .................................................................................................................... 8
6. Accessories .................................................................................................................................................. 8
7. Maintenance and care ..................................................................................................................................9
8. Dimensions and weights ..............................................................................................................................9
This product contains electronic components sensitive to electrostatic
CAUTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC SENSITIVE
DEVICES
CAUTION! Dangerous operating conditions may occur when using the programming interface on the valve as the valve may possibly not react to the analog setpoint any more. Provide for protection against uncontrolled movement of equipment when putting the valve into operation and before making any modifications to the valve settings.
We herewith declare that the version of the product described in this installation manual is intended to be incorporated into or assembled with other machinery and that it must not be put into service until the machinery into which it is to be incorporated has been declared in conformity with the provisions of Council Directive 2006/42/EC. Handling, assembly and putting into service and all settings and adjustments must be done by qualified, authorised personnel only.
discharge. An electrostatic discharge generated by a person or object coming in contact with the electrical components can damage or destroy the product. To avoid the risk of electrostatic discharge, please observe the handling precautions and recommendations contained in standard EN 100015-1. Do not connect or disconnect the device while it is energised.
This product complies with the essential requirements of the EMC Directive 2014/30/EU and its amendments. It is CE-approved. A separate Declaration of Conformity is available on request. Please provide ordering code and serial numbers of products concerned.
NOTICE
The information in this manual is subject to change without notice.
In no event shall ASCO NUMATICS be liable for technical or editorial errors or omissions. Neither is any liability assumed for accidental or consequential damages arising out of or in connection with the supply or use of the information contained herein. THIS MANUAL CONTAINS INFORMATION PROTECTED BY COPYRIGHT. NO PART OF THIS DOCUMENT MAY BE PHOTOCOPIED OR REPRODUCED IN ANY FORM OR MANNER WHATSOEVER WITHOUT PRIOR WRITTEN PERMISSION FROM ASCO NUMATICS.
COPYRIGHT © 2016 - ASCO NUMATICS - All rights reserved.
DP-IM14152-4
INSTALLATION
GB
Control
Control
CONTROL CONTROL CONTROL
1. DESCRIPTION
From open-loop control to closed-loop control to cascaded process control – everything is possible with the controller module. As a stand-alone component, the controller module is designed to control proportional valves by regu­lating the current in the valve’s solenoid coil. The maximum value of the solenoid coil’s current is automatically determined with the auto-adapt function. Higher precision requirements can be met by controlling flow, temperature, pressure, force etc. using additional analog feedback inputs. More complex requirements are satisfied through a cascaded control with feedback from the actuator and a process variable.
The terminals.
D
can be installed on a DIN rail in a control cabinet. The analog inputs and outputs are connected with screw
A serial RS232 or a USB interface allows communication with a PC. All configurations (setpoint settings in all commonly used signal variables, open-loop or closed-loop control, cascaded control etc.) are simple to set up with the Windows­based AscoDigiCom software, offering optimum adaptation of the proportional valve to the control system. Visualisation (scope function) of the analog inputs and outputs and the PID control variables allows easy adjustment of the control parameters to match specific applications.
Three buttons and a three-digit LED display on the module enable manual setpoint setting and display of feedback without the need for PLC control during start-up.
Additional LEDs show the operating state and any error messages (e.g. low voltage, overvoltage, setpoint not reached) that may occur.
1.1 CATALOGUE NUMBERS
Description catalogue no.
D
control device - 12 V DC / 2 A
D
control device - 24 V DC / 2 A
D
control device - 24 V DC / 200 mA
60300117 60300118 60300119
D
1.2 OPERATING ELEMENTS
Green LED
Yellow LED
Red LED
Operating buttons
Display
Green LED OFF: Setpoint ≠ feedback ON: Setpoint = feedback Flashing: Overtemperature
Yellow LED OFF: Normal ON: Manual operation Flashing: AUTOSAFE enabled
Red LED OFF: Normal ON: Low voltage Flashing: Overvoltage
DP-IM14152-5
INSTALLATION
GB
1.3 MANUAL ADJUSTMENT
1.3.1 Manual operation
After an interruption in the power supply, press both arrow buttons located beneath the display during power up
to switch to the manual mode. This operating mode is indicated by the letters “H n d” in the display. The "H n d" display disappears when the arrow buttons are released. Press the left arrow button or DOWN arrow to reduce the output value, press the right arrow button or UP arrow
to increase the output value. The yellow LED is on permanently during manual mode. Exit this operating mode by pressing both arrow buttons simultaneously or by turning off the power supply for a
short time.
1.3.2 Auto-Adapt
This function should only be activated when the module is set to current control. In the event of an interruption in
the power supply, the module will enter into the Auto-Adapt mode by pressing the ADAPT button underneath the
display when switching on the power supply. The Auto-Adapt mode is indicated by the letters „AdA“ in the display.
The valve output is supplied with power for 3 seconds. After this period, the maximum current is measured and
displayed for 3 seconds. The module then switches back to the normal operating mode.
Caution: When measuring the maximum current, the output is activated with the supply voltage. The module can
be damaged when using solenoid coils that require a supply voltage of more than 2000 mA.
All parameters must be read, copied and written again on return to the normal operating mode from the Auto-
Adapt mode in order to update max. current, setpoint offset and setpoint span.
1.4 OPERATING MODES
Shut-off: If the setpoint falls below 0.5 %, the valve is switched off.
Overtemperature: If the temperature of the internal control electronics exceeds 120°C, the operating mode is
switched to AUTOSAFE and the green LED starts to flash.
Undervoltage / overvoltage: If the supply voltage is less than 20 V or more than 30 V, the valve is switched off
and fully exhausted. The red LED lights up constantly to indicate undervoltage or flashes to indicate overvoltage.
Autosafe: When autosafe is activated, the pulse width signal for the coil current is limited to a duty cycle of
70% ED after 20 seconds. Every 4 seconds, the duty cycle is switched to 100% ED for 0.5 seconds. The yellow
LED flashes.
2. ELECTRICAL CONNECTION
Pin Description Pin Description
1 V DC IN 11 Setpoint 2 GND IN 12 GND setpoint 3 Protective earth PE 13 Digital input 4 Frequency input 14 GND Digital input 5 Supply voltage sensor + 15 Valve / coil connection 6 Analog input 1 16 GND valve 7 GND sensor supply voltage 17 Digital output 8 Supply voltage sensor + 18 GND Digital output 9 Analog input 2 19 GND Analog output
10 GND sensor supply voltage 20 Analog output
1) The valve must only be supplied with 24V DC at a tolerance of +10%/-10% (12 V: + 15%/-5%) and a max. ripple of 10%
(no supply via diode bridge). Overvoltage or a ripple rate exceeding these tolerances can damage the electronics.
2) The max. current at the digital output is 500 mA (PNP output). The output is protected against short circuit and overload.
3) If a relay (inductive load) is connected to the digital output, a freewheel diode or a varistor must be used.
4) A shielded cable must be used for protection against interference and EMC.
5) The valve body must be grounded with the earthing terminal (pin 3).
DP-IM14152-6
INSTALLATION
GB
Control
Open loop control
ControlD offers 3 control modes
Setpoint
Setpoint
PWM* Signal
Proportional
Solenoid Valve
Process
PWM*
Signal
Open loop control
Closed loop control
ControlD offers 3 control modes
Setpoint
Setpoint
Setpoint
PWM* Signal
Proportional
Solenoid Valve
Proportional
Solenoid Valve
Process
Process
PWM*
Signal
PWM*
Signal
3. FACTORY SETTINGS
The AscoDigiCom files for the Current Controller configuration (standard), a simple Process Controller configuration and a
D
is supplied in a Current Controller configuration as standard.
Cascaded Process Controller configuration are included on the supplied CD-ROM.
The following configurations and pinnings apply for the supplied AscoDigiCom files:
Open-loop control
Voltage supply +24V or +12V Pin 1
Voltage supply GND Pin 2
PE Pin 3
ControlD offers 3 control modes
Setpoint
PWM* Signal
Setpoint 0 - 10 V Pin 11
Setpoint GND Pin 12
Coil + Pin 15
Open loop control
Setpoint
PWM*
Signal
Proportional
Solenoid Valve
Process
Coil 0V Pin 16
Closed-loop control
Voltage supply +24V or +12V Pin 1
Voltage suply GND Pin 2
PE Pin 3
Closed loop control
Setpoint
PWM*
Signal
Proportional
Solenoid Valve
Process
Sensor supply +24V or +12V Pin 5
Sensor input 0 - 10 V Pin 6
Sensor supply GND Pin 7
Setpoint 0 - 10 V Pin 11
Setpoint GND Pin 12
Solenoid valve coil + Pin 15
Solenoid valve coil 0V Pin 16
Cascade or double-loop process control
Voltage supply +24V or +12V Pin 1
Voltage supply GND Pin 2
PE Pin 3
Sensor supply +24V/+12V Pin 5
Sensor input 1* 0 - 10 V Pin 6
Sensor supply 1* GND Pin 7
Sensor supply (1-2) +24V or +12V Pin 8
Sensor input 2** 0 - 10 V Pin 9
Sensor supply 2** GND Pin 10
Setpoint 0 - 10 V Pin 11
Setpoint GND Pin 12
Solenoid valve coil Pin 15
Solenoid valve coil Pin 16 * Slave loop sensor (1) ** Master loop sensor (2)
If you have any questions on the configuration or parameter settings of this product, please contact our Product Support by email at product.support@emerson.com or phone (+49) 7237-996-676.
Double loop control
Set­point
Master Slave
Comparator
*PWM: pulse-width modulated
PWM*
Signal
Proportional
Solenoid Valve
Process
DP-IM14152-7
INSTALLATION
GB
CONTROL
CONTROL
4. FIELD-PROGRAMMABLE SETTINGS
DISPLAY
The solenoid coil's actual current is displayed in Ampere units during regular operation.
Other displays: Hnd indicates that the Manual mode has been selected. Err Internal overflow. AEr Autozero overflow. AdA Auto-adapt is active.
PUSHBUTTONS
To enter the Manual mode, press and hold both pushbuttons simultaneously during power up. "Hnd" appears in the display. Use the UP button to increase the coil current and the DOWN button to decrease it. The actual coil current is displayed. Quick presses on the buttons allow you to make slight changes in the current setting. Longer presses allow you to make quick changes to the current setting. Press both pushbuttons simultaneously to exit the manual mode.
5. TECHNICAL CHARACTERISTICS
5.1 GENERAL Ambient temperature -20 °C to +50 °C
5.2 CONSTRUCTION Body PA (Polyamid) Protection IP20 Electrical connection pluggable terminal block (0,08 - 1,5 mm²) Mounting DIN-EN 50022 rail
5.3 ELECTRICAL CHARACTERISTICS Supply voltage (U
or 12 V DC +15 % -5 %, max. ripple 10 %
Max. current of proportional solenoid valve 2 A Setpoint input 0 - 10 V DC, 0 - 20 mA, 4 - 20 mA Sensor input 0 - 10 V DC, 0 - 20 mA, 4 - 20 mA Feedback output 0 - 10 V, 0 / 4 - 20 mA Ramp ON/OFF, adjustable between 0,1 and 20 seconds Adjustable switching frequency 20 to 2000 Hz
) 24 V DC ±10 %, max. ripple 10 %
N
6. ACCESSORIES
Description catalogue no.
"ASCO-DigiCom" USB cable for
D
software on CD-ROM (supplied with the controller)
D
to PC connection (to be ordered separately)
88100893 88100894
DP-IM14152-8
INSTALLATION
GB
112,154
57,841
USB
7. MAINTENANCE AND CARE
No special maintenance or care required.
8. DIMENSIONS AND WEIGHT
Weight: 153 g
Pins 20-11
Pins 10-1
75
51,75
Pin 11
Pin 1
RS 232
Display
DIN rail
DP-IM14152-9