ASCO Installationsanleitung: Pneumatic Valves Proportional 603-IM-3834610 Manuals & Guides

Installation & Maintenance Instructions
U
I
GB
FR
DE
Instructions d'installation et de maintenance
Inbetriebnahme- und Wartungsanleitungen
AMPLIFIER PLUG CONNECTEUR AMPLIFICATEUR STECKERVERSTÄRKER Catalogue no.: E908A00X Code : 603 00 019 Artikel-Nr.: 833-15009X
The amplifier plug 603 00 019 (and/or E908A00X and/or 833-15009X) replaces an IP-65 spade plug connector to ISO 4400. It is equipped with an electronic amplifier to modify and amplify an input signal (setpoint) to a modulating output current to provide stepless control for ASCO Numatics proportional solenoid valves such as series 602.
IMPORTANT
This I&M sheet must be used in conjunction with the I&M sheet of the main proportional valve.
FUNCTION
- Input signal 0-10V DC, 0-20 mA or 4-20 mA to be selected by dip switches.
- Required flow rates adjustable to input signal by means of two potentiometers.
- Switch-off function at less than 2% of the maximum control signal.
- Ramp control function (up and down) can be activated by a dip switch and is adjustable by means of a potentiometer.
- Switch frequency adjustable by means of a potentiometer.
INSTALLATION / ADJUSTMENT
Check nameplate for correct catalogue number and voltage.
1. Install valve and apply line pressure.
2. Remove centre screw and cover with gasket from plug connec tor.
3. Position connector gasket between coil and connector and install plug connector.
Input signal setting
4. Set required input signal by adjus ting dip switches S1, S3 and S4. The factory default is 0-10V DC.
Supply voltage
5. Apply 24V DC ( ±10%) supply voltage to pin 1 (+) and common to pin 2 (0V). The circuit is protected against overvoltage and reverse voltage.
Input signal
6. Apply input signal to pin 3 (+).
Minimum flow
7. Increase input signal to value at which minimum flow is required and adjust potentiometer P1 until the required minimum flow is obtained.
Le connecteur amplificateur 603 00 019 (et/ ou E908A00X et/ou 833-15009X) s'adapte sur une bobine à broches normalisées ISO 4400 (protection IP65). Il est pourvu d’un amplificateur électronique pour modifier et amplifier un signal d’entrée (valeur de con­signe) afin d’obtenir un courant modulateur de sortie pour le contrôle progressif des élec­trovannes proportionnelles ASCO Numatics comme celles de la série 602.
AVIS IMPORTANT
Ces instructions d'installation et de main­tenance complètent celles fournies vanne proportionnelle correspondante.
avec la
FONCTION
- Signal d’entrée 0-10 V CC, 0-20 mA ou 4-20 mA, à sélectionner à l'aide des dips­witchs.
- Débit réglable en fonction du signal d’entrée au moyen de deux potentio­mètres.
- Fonction de fermeture à moins de 2 % du signal de contrôle maximal.
- Fonction de rampe (croissance et décrois­sance) à activer par dipswitch et ajustable au moyen d’un potentiomètre.
- Fréquence de commutation ajustable par potentiomètre.
INSTALLATION / MISE AU POINT
Vérifier que le code et la tension marqués sur l’étiquette signalétique soient corrects.
1. Installer la vanne et la mettre sous pres­sion.
2. Ôter la vis centrale, le couvercle et le joint d’étanchéité du connecteur amplificateur.
3. Placer le joint entre la bobine et le con­necteur et installer le connecteur.
Sélection du signal de consigne
4. Choisir le signal d’entrée en ajustant les dipswitchs S1, S3 et S4. Le réglage en usine est de 0-10 V CC.
Tension d’alimentation
5. Appliquer une tension d’alimentation de 24 V CC ± 10 % à la broche 1 (+) et la masse à la broche 2 (0V). Le circuit est protégé contre les surtensions et les inversions de polarité.
Signal de consigne
6. Appliquer le signal de consigne à la bro­che 3 (+).
Débit minimale
7. Augmenter la consigne à la valeur à laquelle le débit minimal est requis et ajuster le potentiomètre P1 jusqu’à obtenir le débit minimal.
BESCHREIBUNG
Der Steckerverstärker 603 00 019 (und/oder E908A00X und/oder 833-15009X) ersetzt eine Leitungsdose gemäß ISO 4400 in Schutzart IP65. Er verfügt über einen elek­tronischen Verstärker zur Umwandlung bzw. Verstärkung des Eingangssignals (Sollwert) in einen Modu lations-Ausgangsstrom zur stufenlosen Steuerung von Proportionalven­tilen wie z.B. die der Baureihe 602.
WICHTIGER HINWEIS
Diese Anleitung gilt nur zusammen mit den Inbetriebnahme- und Wartungsanleitungen des entsprechend verwendeten Proportio­nalventils.
FUNKTION
- Das Eingangssignal 0-10 V DC, 0-20 mA bzw. 4-20 mA, wird mit dem entsprechen­den DIP-Schalter festgelegt.
- Der gewünschte Durchfluss entsprechend dem Eingangssignal wird mittels zweier Potentiometer eingestellt.
- Die Abschaltfunktion tritt bei weniger als 2 % des maximalen Steuersignals ein.
- Die Rampensteuerung (Anstieg und Ab­fall) kann mit dem DIP-Schalter aktiviert werden und ist über einen Potentiometer einstellbar.
- Die Schaltfrequenz ist mit Potentiometer einstellbar.
INBETRIEBNAHME / EINSTELLUNG
Typenschild auf korrekte Bestellnummer und Spannung überprüfen.
1. Ventil installieren und mit Druck beauf­schlagen.
2. Zentralschraube, Deckel und Dichtung vom Steckverbinder entfernen.
3. Dichtung zwischen Spule und Stecker einlegen und Steckverbinder installieren.
Wahl des Steuersignals
4. Erforderliches Eingangssignal durch Ein­stellung der DIP-Schalter S1, S3 und S4 auswählen. Werkseitige Einstellung: 0-10 VDC.
Versorgungsspannung
5. Eine Spannung von 24 V DC ± 10% an Pin 1 (+) und Masse an Pin 2 (0) anlegen. Der Schaltkreis ist gegen Überspannung und Verpolung gesichert.
Steuersignal
6. Das Steuersignal an Pin 3 (+) anlegen.
Minimaldurchfluss
7. Das Steuersignal bis zum gewünschten Minimaldurchfluss erhöhen und Poten­tiometer P1 drehen, bis der erforderliche Mindestdurchfluss erreicht wird.
(383 46 10) IM14054-R5
Installation & Maintenance Instructions
U
I
GB
FR
DE
Instructions d'installation et de maintenance
Inbetriebnahme- und Wartungsanleitungen
AMPLIFIER PLUG CONNECTEUR AMPLIFICATEUR STECKERVERSTÄRKER Catalogue no.: E908A00X Code : 603 00 019 Artikel-Nr.: 833-15009X
Maximum flow
8. Increase input signal to value at which maximum flow is required and adjust potentiometer P3 until the required maximum flow is obtained.
Notes:
a. Adjusting the maximum flow will slightly
influence the minimum flow. For accurate adjust ment, repeat steps 7 and 8 until the required flow is obtained.
b. Minimum and maximum flow at the chosen
settings are dependent on the pressure differential (P) over the valve.
If the valve has to operate at several
Ps, adjust minimum flow (step 7) to the highest P and the maximum flow (step
8) to the lowest P.
Switch-off
9. To ensure that the valve will close at
minimum control signal, the coil current will switch off at less than 2% of the maximum input signal.
Ramp function
10. To temporize the flow at fast input signal
changes, a ramp control function can be activated by dip switch S2. The factory default is “no ramp”. The ramptime can be adjusted between 0.1
means of potentiometer P2.
Switching frequency
11. The electronic amplifier is equipped with
a device switching the voltage rapidly "on” and “off”. The switching frequency (number of “on/off” times per second) has an influence on the flow regulation characteristics, such as hysteresis, sensitivity etc., as well as on the core vibration. The frequency is factory set to 300 Hz for optimal opera tion. Depending on operation requirements, can be adjusted between 40 and 700 Hz by means of potentiometer P4.
12. Under certain installation circumstances,
undesirable pressure variations might occur. In this case, increase frequency and/or ramp time.
13. Position the cover with gasket and tighten
the central screw to 0.6 N/m to ensure proper gasket compression and IP65.
and 3 seconds by
the frequency
Débit maximale
8. Augmenter la consigne à la valeur à laquelle le débit maximal est requis et ajuster le potentiomètre P3 jusqu’à ob­tenir le débit maximal.
Notes:
a. Le réglage du débit maximal
légèrement le débit minimal. glage précis, répéter les réglages 7 et 8 jusqu’à obtenir les valeurs souhaitées.
b. Les débits minimal et maximal en fonction
des valeurs de réglage choisies dépen­dent de la pression différentielle (P) sur la vanne. Si la vanne doit opérer à plusieurs P, ajuster le débit minimal (réglage 7) au ∆P le plus élevé et le débit maximal (réglage 8) au P le plus bas.
Mise hors circuit
9. Pour s'assurer que la vanne est fermée au signal de consigne minimal, le courant de la bobine est mis hors circuit à moins de 2 % du signal d’entrée maximal.
Fonction de rampe
10. Pour temporiser le débit de sortie lors de changements rapides de la consigne, activer la fonction "rampe" au moyen du switch S2. Le réglage en usine est "sans rampe". La rampe est réglable entre 0,1 et 3 secondes au moyen du poten­tiomètre P2.
Fréquence de commutation
11. Le connecteur amplificateur est équipé d’un dispositif "modulation de fréquence" (commutation rapide ON - OFF). La fréquence de commutation (nombre de mises en/hors circuit par seconde) a une influence sur les caractéristiques de régulation du débit, comme l'hystérésis, la sensibilité etc., ainsi que sur la vibra­tion du noyau. Pour un fonctionnement optimal, la fréquence est réglée en usine à 300 Hz. La fréquence peut être réglée entre 40 et 700 Hz (au moyen du poten­tiomètre P4) en fonction des exigences opératoires.
12. D a ns c er ta in es c o nf ig ur a ti on s d'installation, on peut constater des variations de pression indésirables. Aug­menter alors la fréquence et/ou la durée de rampe.
13. Positionner le couvercle avec son joint d’étanchéité et serrer la vis centrale à 0,6 N/m pour assurer la compression du joint et IP65.
influence
Pour un ré-
Maximaldurchfluss
8. Das Steuersignal bis zum gewünschten Maximaldurchfluss erhöhen, und Poten­tiometer P3 drehen, bis sich der erforder­liche maximale Durchfluss einstellt.
Anmerkungen:
a. Die Einstellung des Maximaldurchflusses
beeinflusst geringfügig den Minimal­durchfluss. Zur präzisen Einstellung sind die Schritte 7 und 8 solange zu wiederho­len, bis die gewünschten Werte erreicht werden.
b. Der eingestellte Minimal- und Maximal-
durchfluss hängt vom Differenzdruck (P) des Ventils ab. Wenn das Ventil bei mehreren P funktionieren soll, ist der Mindestdurchfluss (Schritt 7) beim höchsten P und der maximale Durch­fluss (Schritt 8) beim niedrigsten P einzustellen.
Abschaltung
9. Um sicherzustellen, dass das Ventil bei einem Mindeststeuersignal schließt, schaltet der Spulenstrom bei weniger als 2 % des maximalen Eingangssignals ab.
Rampenfunktion
10. Zur Verzögerung des Durchflusses bei schnellen Änderungen der Steuersi­gnale kann mit dem DIP-Schalter S2 eine Rampenfunktion gewählt werden. Die werksseitige Einstellung ist „keine Rampe“. Die Rampenzeit kann mit dem Potentiometer P2 zwischen 0,1 und 3 Sekunden eingestellt werden.
Schaltfrequenz
11. Der elektronische Steckerverstärker ist mit einer Vorrichtung ausgestattet, die die Spannung schnell ein- bzw. ausschaltet. Die Schaltfrequenz (Anzahl der Ein- und Ausschaltungen pro Sekunde) hat einen Einfluss auf die Durchflusseigenschaften wie Hysterese, Empfindlichkeit etc. Sie wirkt sich auch auf die Ankervibration aus. Für einen optimalen Betrieb ist die Frequenz werkseitig auf 300 Hz einge­stellt. Je nach Betriebsanforderungen kann die Frequenz mit dem Potentiome­ter P4 zwischen 40 und 700 Hz einge­stellt werden.
12. Manche Einbaubedingungen können zu unerwünschten Vibrationen führen. In diesem Fall sind die Frequenz und/oder Rampenzeit zu erhöhen.
13. Dichtung und Deckel aufsetzen und Zentralschraube mit 0,6 N/m anziehen, um sicherzustellen, dass die Dichtung ausreichend zusammengepresst wird.
IM14054-2