ASCO European Instruction Manual: Series G2 Modbus TCP Quick Start Manual Manuals & Guides

G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
Getting Started
This is a brief document designed to quickly get you started setting up your valve manifold with an integrated Numatics’ G2-2 series EtherNet/IP
1) Initial Unpacking and Inspection
1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.
2) Remove wrapped manifold assembly from box. a) Remove manifold assembly from anti-static packaging b) Retain documentation for installation and configuration
3) Examine manifold assembly for any shipping damage such as: a) Bent pins or connectors b) Report any damage to shipping carrier immediately
4) Examine manifold assembly for proper ordered configuration. (Valves, I/O, Protocol, etc.)
2) G2-2 Introduction
Below is an example of a 2012 series valve manifold. This fieldbus manifold series is capable of addressing a total of 224 I/O. The manifold can be viewed as having two sections to it, the
. The
Side
Valve Side
maximum of 6 modules totaling 192 Outputs, 96 Inputs, or various combinations. The communication module has a RJ45 communication connector. The power module has a 4-pin power connector. Pin-outs for these, along with I/O connectors, are labeled on the side of the respective modules.
supports a maximum of 32 solenoid coils and the
TM
or Modbus TCP communication node.
Discrete I/O Side
Module/ Network
Status LED's
Aux. Power
LED's
FUSE 1 +24V VLV/OUT FUSE 2 +24V NODE/IN
Communications Module
Valve Side
and the
supports a
(Maximum of 32 Solenoids)
Valve Side
Chassis Ground
Connection
Valve Side Sub-D Output Module
Power Module
Valve
End Plates
Valve
Discrete I/O
Manual Override
Solenoid LED Status Indicator
3835056
DG22ENQS2-0 1/07
Subject to change without notice
Page 1
www.numatics.com/fieldbus
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
3) EtherNet/IP
EtherNet/IP
Connector Type Description Part Number
TM
TM
and Modbus TCP Communication Replacement Part Numbers
IP20 RJ45
Connector
IP67 RJ45
Connector
and Modbus TCP Communication Module Part Numbers
TM
FUSE 1 +24V VLV/OUT FUSE 2 +24V NODE/IN
Complete Module 239-2037
Communication Board 256-846
Auxiliary Power Board 256-848
Valve Driver Board 256-680
4 Amp Fuse 140-933
10 Amp Fuse 140-934
Complete Module 239-2342
Communication Board 256-846
Auxiliary Power Board 256-848
Valve Driver Board 256-680
4 Amp Fuse 140-933
10 Amp Fuse 140-934
3835056
DG22ENQS2-0 1/07
Subject to change without notice
Page 2
www.numatics.com/fieldbus
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
4) MCM - Manual Configuration Module (Optional)
Rotary Switch
(SW4)
Rotary Switch
(SW3)
All DIP switches shown in the "OFF" position
The MCM is the module that allows the user to manually enable user definable options such as self test mode, bit mapping offset (Modbus TCP ONLY) and byte swapping (Modbus TCP ONLY), without the need for software configuration. If software configuration is preferred, this module is not necessary consists of two DIP switch sets (SW1 and SW2) and two rotary switches (SW3 and SW4).
MCM Module Part Numbers
Description Part Number
Complete Module 239-1384
Replacement Board 256-684
DIP Switch
(SW2)
4
325
1
ON
DIP Switch
(SW1)
4
5
ON
3
1
2
678
8
6
7
. The MCM
3835056
DG22ENQS2-0 1/07
Subject to change without notice
Page 3
www.numatics.com/fieldbus
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
MCM Settings (Modbus TCP ONLY)
DIP Switch Settings (SW1)
Offset:
Switch Setting Description
Enable Output offset of 400 hex or 1024 dec (Some software programs deal
SW1-7 Off*
SW1-7 On
Bit swap:
with a pre-determined offset for the Output data table. This setting allows the user to work with the offset.) Disable Output offset. (This setting allows the user to disregard the offset.)
Switch Setting Description
Disable I/O bit stream swapping (Some software programs reverse the
SW1-8 Off*
SW1-8 On Enable I/O bit stream swapping
DIP Switch Settings (SW2) – No Function
Rotary Switch Settings (SW3 and SW4) – No Function
way the I/O bits are presented to the node and thus the bit mapping may be reversed or swapped from the expected mapping scheme.)
*Factory Default Settings
3835056
Subject to change without notice
Page 4
www.numatics.com/fieldbus
DG22ENQS2-0 1/07
T
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
5) Self-Test Mode
An internal diagnostic tool can also be enabled using the optional MCM module. This tool allows the user to confirm that all of the Inputs and Outputs on the manifold are fully functional without needing a network connection or controller. There are two test modes that the user can choose using SW2-8. The “Output” test mode tests all the outputs by sequentially turning them ON one at a time. The “Input/Output” test mode tests the inputs by causing all of the outputs to toggle between even and odd values when any input is made.
To use the Self-Test Mode, the user must first set some initial conditions using the MCM module. Follow these steps to obtain the needed initial condition settings. Remember to remove power from the manifold before making changes to the MCM when setting these initial conditions.
1) Disconnect power and air from the manifold!
2) Record current MCM settings.
3) Set the rotary switches to 99 (SW3 and SW4).
4) Make sure that SW1-5, SW2-1, and SW2-7 are in the “ON” position.
5) Select the desired test mode with SW2-8 (see table below)
Switch
SW2-8
6) Make sure that all of the other switches are in the “OFF” position.
The initial conditions are now set. To enable the Self-Test Mode, apply power to the manifold and make the following changes within 5 to 10 seconds:
Self-Test Mode is terminated by removing power to the unit. Remember to return the MCM settings to their original settings to return the communication node to normal operation.
!
esting
Mode
Output Off Sequentially turns all the outputs ON and OFF.
Input/
Output
Setting Description
Causes all of the odd outputs to come on and stay on until an
On
1) Set SW2-6 to the “ON” position.
2) Set SW2-7 to the “OFF” position.
input is made. When an input is made, the outputs will toggle to the even outputs.
Air should be disconnected to the manifold when attempting to run the Self-Test Mode to prevent unwanted motion.
Communication lines should be disconnected before attempting to run the Self-Test Mode.
3835056
Subject to change without notice
Page 5
www.numatics.com/fieldbus
DG22ENQS2-0 1/07
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
6) I/O Mapping Example
Example:
Assumed Settings
- Single Z-Boards
valves
- Double Z-Boards
valves
Discrete I/O Configuration
Module Type Part No.
No.
1 MCM 239-1384 -- --
8O Sourcing
2
3
4
5
(PNP)
16O Sourcing
(PNP)
4I Sinking
(NPN)
8I Sinking
(NPN)
Manifold I/O Configuration
Outputs and Mapping Location
Valve Outputs = 12
Allocated Unused Valve Outputs = 20
Discrete Outputs = 24
Total Outputs = 56
Inputs and Mapping Location
Discrete Inputs = 12
Allocated and Reserved Inputs = 4 Total Inputs = 16
TM
used with single solenoid
TM
used with double solenoid
In OutPos
Bytes
239-1315 1 1
239-1319 1 2
239-1304 1 0
239-1308 1 0
Byte 0; Bits 0-7 Byte 1; Bits 0-3 Byte 1; Bits 4-7 Bytes 2 - 3; Bits 0-7 Bytes 4,5 and 6; Bits 0-7
Byte 6; Bits 0-3, Byte 7; Bits 0-7
Byte 6; Bits 4-7
+24V NODE/IN
+24V VLV/OUT
FUSE 2
FUSE 1
3835056
Subject to change without notice
Page 6
www.numatics.com/fieldbus
DG22ENQS2-0 1/07
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
I/O Mapping Table Example Continued
Output Table
BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
2
3
4
5
6
Valve Coil
No. 8
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 7
Discrete
Output No. 7
Discrete
Output No. 15
BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
2
3
4
5
6
7
Coil No. 8
Status
Coil No. 16
Status
Coil No. 24
Status
Coil No. 32
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 7
Valve Coil
No. 7
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 6
Discrete
Output No. 6
Discrete
Output No. 14
Coil No. 7
Status
Coil No. 15
Status
Coil No. 23
Status
Coil No. 31
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 6
Valve Coil
No. 6
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 5
Discrete
Output No. 5
Discrete
Output No. 13
Coil No. 6
Status
Coil No. 14
Status
Coil No. 22
Status
Coil No. 30
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 5
Valve Coil
No. 5
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 4
Discrete
Output No. 4
Discrete
Output No. 12
Input Table
Coil No. 5
Status
Coil No. 13
Status
Coil No. 21
Status
Coil No. 29
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 4
Valve Coil
No. 4
Valve Coil
No. 12
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 3
Discrete
Output No. 3
Discrete
Output No. 11
Coil No. 4
Status
Coil No. 12
Status
Coil No. 20
Status
Coil No. 28
Status
Allocated &
Reserved
Status for
Discrete Outputs
No. 12-15
Discrete
Input No. 3
Discrete
Input No. 3
Valve Coil
No. 3
Valve Coil
No. 11
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 2
Discrete
Output No. 2
Discrete
Output No. 10
Coil No. 3
Status
Coil No. 11
Status
Coil No. 19
Status
Coil No. 27
Status
Allocated &
Reserved
Status for
Discrete Outputs No. 8-11
Discrete
Input No. 2
Discrete
Input No. 2
Valve Coil
No. 2
Valve Coil
No. 10
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 1
Discrete
Output No. 1
Discrete
Output No. 9
Coil No. 2
Status
Coil No. 10
Status
Coil No. 18
Status
Coil No. 26
Status
Status for
Discrete Outputs
No. 4-7
Status for
Discrete Outputs No. 4-7
Discrete
Input No. 1
Discrete
Input No. 1
Valve Coil
No. 1
Valve Coil
No. 9
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 0
Discrete
Output No. 0
Discrete
Output No. 8
Coil No. 1
Status
Coil No. 9
Status
Coil No. 17
Status
Coil No. 25
Status
Status for
Discrete Outputs
No. 0-3
Status for
Discrete Outputs
No. 0-3
Discrete
Input No. 0
Discrete
Input No. 0
This example supports Modbus TCP function codes: “Write Multiple
!
Registers” (FC 16) and “Read Multiple Registers” (FC 03).
3835056
DG22ENQS2-0 1/07
Subject to change without notice
Page 7
www.numatics.com/fieldbus
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
I/O Mapping Table Example (Modbus TCP ONLY-Bit Reversal) Continued
Output Table
BYTE Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
0
1
2
3
4
5
6
Valve Coil
No. 8
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 7
Discrete
Output No. 7
Discrete
Output No. 15
BYTE Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
0
1
2
3
4
5
6
7
Coil No. 8
Status
Coil No. 16
Status
Coil No. 24
Status
Coil No. 32
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 7
Valve Coil
No. 7
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 6
Discrete
Output No. 6
Discrete
Output No. 14
Coil No. 7
Status
Coil No. 15
Status
Coil No. 23
Status
Coil No. 31
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 6
Valve Coil
No. 6
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 5
Discrete
Output No. 5
Discrete
Output No. 13
Coil No. 6
Status
Coil No. 14
Status
Coil No. 22
Status
Coil No. 30
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 5
Valve Coil
No. 5
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 4
Discrete
Output No. 4
Discrete
Output No. 12
Input Table
Coil No. 5
Status
Coil No. 13
Status
Coil No. 21
Status
Coil No. 29
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 4
Valve Coil
No. 4
Valve Coil
No. 12
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 3
Discrete
Output No. 3
Discrete
Output No. 11
Coil No. 4
Status
Coil No. 12
Status
Coil No. 20
Status
Coil No. 28
Status
Allocated &
Reserved
Status for
Discrete Outputs
No. 12-15
Discrete
Input No. 3
Discrete
Input No. 3
Valve Coil
No. 3
Valve Coil
No. 11
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 2
Discrete
Output No. 2
Discrete
Output No. 10
Coil No. 3
Status
Coil No. 11
Status
Coil No. 19
Status
Coil No. 27
Status
Allocated &
Reserved
Status for
Discrete Outputs No. 8-11
Discrete
Input No. 2
Discrete
Input No. 2
Valve Coil
No. 2
Valve Coil
No. 10
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 1
Discrete
Output No. 1
Discrete
Output No. 9
Coil No. 2
Status
Coil No. 10
Status
Coil No. 18
Status
Coil No. 26
Status
Status for
Discrete Outputs
No. 4-7
Status for
Discrete Outputs No. 4-7
Discrete
Input No. 1
Discrete
Input No. 1
Valve Coil
No. 1
Valve Coil
No. 9
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 0
Discrete
Output No. 0
Discrete
Output No. 8
Coil No. 1
Status
Coil No. 9
Status
Coil No. 17
Status
Coil No. 25
Status
Status for
Discrete Outputs
No. 0-3
Status for
Discrete Outputs
No. 0-3
Discrete
Input No. 0
Discrete
Input No. 0
This example supports Modbus TCP function codes: “Write Coil” (FC 05) or “Force Multiple Coils” (FC 15) and “Read Coils” (FC 01) or “Read Input
!
Discrete” (FC 02).
3835056
Subject to change without notice
Page 8
www.numatics.com/fieldbus
DG22ENQS2-0 1/07
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
7) Output Short Circuit Protection (Status Input Bits)
Status Input Bits report the integrity of the load being driven by the output driver. They must be mapped to the scanner as part of the Input Size Value. Please refer to the table below for Status Input Bit action during fault condition:
Output Type Output State Fault Condition Status Bit
Valve Solenoid Coil Driver or
Sinking (NPN)
Discrete Outputs
Discrete Outputs
8) Ground Wiring
All Numatics Inc. communication nodes should be grounded during the installation process. These grounding guidelines can be found in National Electrical code IEC 60204-1 or EN 60204-1. There also is a, “ATTENTION: CONNECT TO EARTH GROUND FOR PROPER GROUNDING OF UNIT”, label attached to the chassis ground connection point on the G2-2 series communication node housing. This label also points out where the grounding guidelines can be found.
!
ON
OFF
ON
Proper grounding will alleviate and prevent many intermittent problems with network communication. When grounding to a machine frame, please ensure that the machine frame itself is already properly grounded. Better grounding can be achieved when larger diameter (lower gauge) wire is used.
No Fault Fault ­No Fault Fault ­No Fault 0 Sourcing (PNP) Fault -
Short Circuit, Over Temp/Over Current 1
Open Load 1
Short Circuit, Over Temp/Over Current 1
0
0
3835056
Subject to change without notice
Page 9
www.numatics.com/fieldbus
DG22ENQS2-0 1/07
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
9) Auxiliary Power Connector Pin-Out
Pin No. Function Description
1
2 Earth Ground Protective Earth (Case Ground) 3 0VDC Common 0VDC Common, for Valves, I/O, and Node Power
4
+24VDC
(Valves and Outputs)
+24VDC
(Node and Inputs)
Voltage Used to Power Outputs (Valve Coils and Discrete Outputs)
Voltage Used to Power Discrete Inputs and Node Electronics
Pin-Out
Aux. - MINI
4
!
1
Maximum current capacity on the 0VDC common pin of the auxiliary power connector is 8 Amps. The combined draw of the +24VDC Valves and Outputs and +24VDC Node and Inputs pins cannot exceed 8 Amps, at any given moment in time. The auxiliary power +24VDC Node and Inputs pin supplies power to the node electronics. This pin must be powered at all times for communication node to be functional.
3
2
3835056
Subject to change without notice
Page 10
www.numatics.com/fieldbus
DG22ENQS2-0 1/07
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
10) Power Consumption
Auxiliary Power Connection (Standard)
Aux. Power
Connector Pin No.
1 24 VDC Power for Valves & Discrete Outputs
4 24 VDC Power for Inputs & Node Electronics
Discrete I/O Module(s) Power Jumper
All of Numatics, Inc., G2-2 I/O modules have a selectable power source jumper. This jumper determines which Aux. Power connector pin will power these modules.
This option allows the user to select how each specific module will be powered during different conditions (i.e. E-Stop). Each I/O module can be set-up independently allowing individual Output and/or Input modules to remain active if needed.
Power Rating
Maximum system current capability is 8 amps. Care should be taken not to exceed 8 amp draw
through the 0VDC common pin (Current through all +24 VDC Pins combined).
Discrete I/O current draw is dependent on the device(s) connected. It is critical to know what these
values are in order to remain safely within the 8 amp limitation.
Loads should not draw more than 0.5 amps of current from any one individual discrete output point.
(Contact factory for higher current capabilities)
Auxiliary Power Connector Voltage Tolerance Current Power
+24VDC (Valves & Outputs) Solenoid Valve Coil 2005 (Each) 24VDC +10%/-15% 0.042 A 1.0 Watts Solenoid Valve Coil 2012 (Each) 24VDC +10%/-15% 0.105 A 2.5 Watts Solenoid Valve Coil 2035 (Each) 24VDC +10%/-15% 0.105 A 2.5 Watts Solenoid Valve Coil ISO - SPA (Each) 24VDC +10%/-15% 0.160 A 4.0 Watts Discrete Output 24VDC - 0.5 A max. * 12 Watts max. * Discrete I/O Status LEDs (Each) 24VDC - 0.015 A 0.36 Watts
+24VDC (Node & Inputs) Node 24VDC +/- 10% 0.040 A 0.96 Watts Discrete I/O Module (Each) 24VDC - 0.006 A 0.14 Watts Discrete I/O Status LEDs (Each) 24VDC - 0.015 A 0.36 Watts
Recommended External Fuses:
External fuses should be chosen based upon the physical manifold configuration. Please refer to the next page for the fuse sizing chart.
Power consumption for each Discrete I/O point is dependent on the specific current draw of input sensor devices and output loads. Please consult the factory for output current requirements greater than 0.5 amps.
Description
3835056
Subject to change without notice
Page 11
www.numatics.com/fieldbus
DG22ENQS2-0 1/07
G2-2 Series EtherNet/IPTM and Modbus TCP
Quick Start Manual
11) Power Consumption and External Sizing Guide Chart
Power Consumption - Aux. Power Connector Pin for Valves and Outputs
Description
Number of Solenoid Valve Coils Energized Simultaneously
___ X 0.105 A (2012 and 2035 Series)
___ X 0.042 A (2005 Series)
Total load current drawn by simultaneously energized Discrete Outputs
with Discrete Outputs Power Jumper in “SP” Position (Factory Default).
= __________Amps
= __________Amps
=
Current
+
__________Amps
+
Total load current drawn by Sensor Devices from Discrete Inputs source
with Discrete Input Power Jumper in “SP” Position.
Surge Compensation:
Suggested External +24 VDC (Valves and Outputs) Fuse Value: __________Amps
Power Consumption - Aux. Power Connector Pin for Node and Inputs
Description
Communication Node Power Consumption
Total load current drawn by simultaneously energized Discrete Outputs
with Discrete Outputs Power Jumper in “UP” Position.
Total load current drawn by Sensor Devices from Discrete Inputs source
with Discrete Inputs Power Jumper in “UP” Position (Factory Default).
Number of I/O modules installed ___ X 0.006 A
Number of Discrete I/O Status LEDs simultaneously on ___ X 0.015 A
Surge Compensation:
Suggested External Pin +24 VDC (Node and Inputs) Fuse Value: __________Amps
The standard power jumper configuration for all Output Modules is “SP”.
The standard power jumper configuration for all Input Modules is “UP”.
At any given moment in time, the combined current draw through +24VDC (Valves & Outputs) pin and cannot exceed 8 amps. Therefore, the combined value of the external fuses on the two +24VDC pins should not exceed 8 amps.
The internal fuses are installed to protect against fire damage due to catastrophic failure of internal components. External fuses are recommended for protection against power supply failure, over-current conditions, etc…
= __________Amps
Total:
Total:
__________Amps
X 1.25
=
+
=
=
=
=
X
Current
.040 Amps
__________Amps
+
__________Amps
+
__________Amps
+
__________Amps
__________Amps
1.25
+24VDC (Node & Inputs) pin
3835056
Subject to change without notice
Page 12
www.numatics.com/fieldbus
DG22ENQS2-0 1/07
Loading...
+ 28 hidden pages