ASCO European Instruction Manual: Series G2 Control Net Quick Start Manual Manuals & Guides

T
G2-2 Series ControlNet Quick Start Manual
Getting Started
This is a brief document designed to quickly get you started setting up your valve manifold with an integrated
1) Initial Unpacking and Inspection
2) G2-2 Introduction
Numatics’ G2-2 series ControlNet communication node.
1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.
2) Remove wrapped manifold assembly from box. a) Remove manifold assembly from anti-static packaging b) Retain documentation for installation and configuration
3) Examine manifold assembly for any shipping damage such as: a) Bent pins or connectors b) Report any damage to shipping carrier immediately
4) Examine manifold assembly for proper ordered configuration. (Valves, I/O, Protocol, etc.)
Below is an example of a 2012 series valve manifold. This fieldbus manifold series is capable of addressing a total of 224 I/O. The manifold can be viewed as having two sections to it, the
. The
Side
Valve Side
supports a maximum of 32 solenoid coils and the
Valve Side
Discrete I/O Side
and the
Discrete I/O
supports a maximum of 6 modules totaling 192 Outputs, 96 Inputs, or various combinations. The communication module has two BNC communication connectors. The power module has a 4-pin power connector. Pin-outs for these, along with I/O connectors, are labeled on the side of the respective modules.
Valve Side
Chassis Ground
Connection
Valve
End Plates
Valve
Module/ Network
Status LED's
Aux. Power
LED's
(Maximum of 32 Solenoids)
Valve Side Sub-D Output Module
3835052
Communications Module
DG22CNQS4-0 1/07
Power Module
Manual Override
Solenoid LED Status Indicator
Page 1
www.numatics.com/fieldbus
T
G2-2 Series ControlNet Quick Start Manual
3) MCM - Manual Configuration Module (for Self-Test Mode Function Only)
Rotary Switch
(SW3)
Rotary Switch
(SW4)
All DIP switches shown in the "OFF" position
DIP Switch
(SW2)
4
5
3
1
2
ON
678
DIP Switch
(SW1)
4
325
1
ON
8
6
7
The MCM is the module that allows the user to manually test the Numatics manifold using Self-Test mode. The MCM consists of two DIP switch sets (SW1 and SW2) and two rotary switches (SW3 and SW4).
MCM Module Part Numbers
Description Part Number
Complete Module 239-1384
Replacement Board 256-684
3835052
DG22CNQS4-0 1/07
Page 2
www.numatics.com/fieldbus
T
T
G2-2 Series ControlNet Quick Start Manual
4) Self-Test Mode
An internal diagnostic tool can also be enabled using the optional MCM module. This tool allows the user to confirm that all of the Inputs and Outputs on the manifold are fully functional without needing a network connection or controller. There are two test modes that the user can choose using SW2-8. The “Output” test mode tests all the outputs by sequentially turning them ON one at a time. The “Input/Output” test mode tests the inputs by causing all of the outputs to toggle between even and odd values when any input is made.
To use the Self-Test Mode, the user must first set some initial conditions using the MCM module. Follow these steps to obtain the needed initial condition settings. Remember to remove power from the manifold before making changes to the MCM when setting these initial conditions.
1) Disconnect power and air from the manifold!
2) Record current MCM settings.
3) Set the rotary switches to 99 (SW3 and SW4).
4) Make sure that SW1-5, SW2-1, and SW2-7 are in the “ON” position.
5) Select the desired test mode with SW2-8 (see table below)
Switch
SW2-8
6) Make sure that all of the other switches are in the “OFF” position.
The initial conditions are now set. To enable the Self-Test Mode, apply power to the manifold and make the following changes within 5 to 10 seconds:
Self-Test Mode is terminated by removing power to the unit. Remember to return the MCM settings to their original settings to return the communication node to normal operation.
!
esting
Mode
Output Off Sequentially turns all the outputs ON and OFF.
Input/
Output
Setting Description
Causes all of the odd outputs to come on and stay on until an
On
1) Set SW2-6 to the “ON” position.
2) Set SW2-7 to the “OFF” position.
input is made. When an input is made, the outputs will toggle to the even outputs.
Air should be disconnected to the manifold when attempting to run the Self-Test Mode to prevent unwanted motion.
Communication lines should be disconnected before attempting to run the Self-Test Mode.
3835052
Page 3
www.numatics.com/fieldbus
DG22CNQS4-0 1/07
T
G2-2 Series ControlNet Quick Start Manual
5) Communication Module Rotary Switches
The Rotary switches allow the user to set the node address.
Rotary Switch Settings
Network Address:
Switch Description
NA 01 Sets the Ones Digits
NA 10 Sets the Tens Digits
Address is set to a default setting of 00 prior to shipment. Rotary switch settings do not take effect until power is cycled (turned
!
OFF and ON).
3835052
Page 4
www.numatics.com/fieldbus
DG22CNQS4-0 1/07
T
G2-2 Series ControlNet Quick Start Manual
6) I/O Mapping Example
Example:
Assumed Settings
- Single Z-Boards
- Double Z-Boards
valves
- Run Idle Header (Overhead) will always take up
the first two Input words of the Input Map.
TM
used with single solenoid valves
TM
used with double solenoid
Discrete I/O Configuration
No.
1 MCM 239-1384 -- --
2
3
4
5
Manifold I/O Configuration
Outputs and Mapping Location
Valve Outputs = 12 Word 0; Bits 0-11 Allocated Unused Valve Outputs = 20 Discrete Outputs = 24 Total Outputs = 56
Inputs and Mapping Location
Discrete Inputs = 12 Word 5; Bits 0-3, 8-15 Allocated and Reserved Inputs = 4 Total Inputs = 16
Module Type Part No.
8O Sourcing
(PNP)
16O Sourcing
(PNP)
4I Sinking
(NPN)
8I Sinking
(NPN)
239-1315 1 1
239-1319 1 2
239-1304 1 0
239-1308 1 0
Word 0; Bits 12-15 Word 1; Bits 0-15 Word 2; Bits 0-15
Word 3; Bits 0-7
Word 5; Bits 4-7
In OutPos
Bytes
3835052
Page 5
www.numatics.com/fieldbus
DG22CNQS4-0 1/07
T
G2-2 Series ControlNet Quick Start Manual
I/O Mapping Table Example Continued
WORD BYTE
0
0
1
2
1
3
4
2
5
3 6
WORD BYTE
0
0
1
2
1
3
4
2
5
6
3
7
8
4
9
10
5
11
Output Table
7 15 6 14 5 13 4 12 3 11 2 10 1 9 0 8
Valve Coil
No. 8
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 7
Discrete
Output No. 7
Discrete
Output No. 15
Valve Coil
No. 7
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 6
Discrete
Output No. 6
Discrete
Output No. 14
Valve Coil
No. 6
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 5
Discrete
Output No. 5
Discrete
Output No. 13
Valve Coil
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 4
Discrete
Output No. 4
Discrete
Output No. 12
Input Table
7 15 6 14 5 13 4 12 3 11 2 10 1 9 0 8
Run Idle
Header
Run Idle
Header
Run Idle
Header
Run Idle
Header
Coil No. 8
Status
Coil No. 16
Status
Coil No. 24
Status
Coil No. 32
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 7
Run Idle
Header
Run Idle
Header
Run Idle
Header
Run Idle
Header
Coil No. 7
Status
Coil No. 15
Status
Coil No. 23
Status
Coil No. 31
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 6
Run Idle
Header
Run Idle
Header
Run Idle
Header
Run Idle
Header
Coil No. 6
Status
Coil No. 14
Status
Coil No. 22
Status
Coil No. 30
Status
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 5
Run Idle
Header
Run Idle
Header
Run Idle
Header
Run Idle
Header
Coil No. 5
Coil No. 13
Coil No. 21
Coil No. 29
Allocated &
Reserved
Allocated &
Reserved
Allocated &
Reserved
Discrete
Input No. 4
No. 5
Status
Status
Status
Status
BIT
BIT
Valve Coil
No. 4
Valve Coil
No. 12
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 3
Discrete
Output No. 3
Discrete
Output No. 11
Run Idle
Header
Run Idle
Header
Run Idle
Header
Run Idle
Header
Coil No. 4
Status
Coil No. 12
Status
Coil No. 20
Status
Coil No. 28
Status
Allocated &
Reserved
Status for
Discrete Outputs
No.12-15
Discrete
Input No. 3
Discrete
Input No. 3
Valve Coil
No. 3
Valve Coil
No. 11
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 2
Discrete
Output No. 2
Discrete
Output No. 10
Run Idle
Header
Run Idle
Header
Run Idle
Header
Run Idle
Header
Coil No. 3
Status
Coil No. 11
Status
Coil No. 19
Status
Coil No. 27
Status
Allocated &
Reserved
Status for
Discrete Outputs No. 8-11
Discrete
Input No. 2
Discrete
Input No. 2
Valve Coil
No. 2
Valve Coil
No. 10
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 1
Discrete
Output No. 1
Discrete
Output No. 9
Run Idle
Header
Run Idle
Header
Run Idle
Header
Run Idle
Header
Coil No. 2
Status
Coil No. 10
Status
Coil No. 18
Status
Coil No. 26
Status
Status for
Discrete Outputs No. 4-7
Status for
Discrete Outputs No. 4-7
Discrete
Input No. 1
Discrete
Input No. 1
Valve Coil
No. 1
Valve Coil
No. 9
Allocated &
Reserved
Allocated &
Reserved
Discrete
Output No. 0
Discrete
Output No. 0
Discrete
Output No. 8
Run Idle
Header
Run Idle
Header
Run Idle
Header
Run Idle
Header
Coil No. 1
Status
Coil No. 9
Status
Coil No. 17
Status
Coil No. 25
Status
Status for
Discrete Outputs
No. 0-3
Status for
Discrete Outputs
No. 0-3
Discrete
Input No. 0
Discrete
Input No. 0
1 Byte = 8 Bits
1 Word = 2 Bytes or 16 Bits
3835052
Page 6
DG22CNQS4-0 1/07
www.numatics.com/fieldbus
T
G2-2 Series ControlNet Quick Start Manual
7) Output Short Circuit Protection (Status Input Bits)
Status Input Bits report the integrity of the load being driven by the output driver. They must be mapped to the scanner as part of the Input Size Value. Please refer to the table below for Status Input Bit action during fault condition:
Output Type Output State Fault Condition Status Bit
Valve Solenoid Coil Driver or
Sinking (NPN)
Discrete Outputs
Discrete Outputs
8) Ground Wiring
All Numatics Inc. communication nodes should be grounded during the installation process. These grounding guidelines can be found in National Electrical code IEC 60204-1 or EN 60204-1. There also is a, “ATTENTION: CONNECT TO EARTH GROUND FOR PROPER GROUNDING OF UNIT”, label attached to the chassis ground connection point on the G2-2 series communication node housing. This label also points out where the grounding guidelines can be found.
!
ON
OFF
ON
Proper grounding will alleviate and prevent many intermittent problems with network communication. When grounding to a machine frame, please ensure that the machine frame itself is already properly grounded. Better grounding can be achieved when larger diameter (lower gauge) wire is used.
No Fault Fault ­No Fault Fault ­No Fault 0 Sourcing (PNP) Fault -
Short Circuit, Over Temp/Over Current 1
Open Load 1
Short Circuit, Over Temp/Over Current 1
0
0
3835052
Page 7
www.numatics.com/fieldbus
DG22CNQS4-0 1/07
Loading...
+ 15 hidden pages