ASCO ARCS Manuals & Guides

IM-IND-536985-RevAA-sec1
Installation & Maintenance Instructions
Advanced Redundant Control System (ARCS) Direct Acting Platform
User Experience Prerequisites
To eectively use the Pneumatic ARCS, users should have some experience with pneumatic systems.
Warnings! READ THIS ENTIRE MANUAL AND ALL RELATED
PUBLICATIONS PERTAINING TO THE WORK TO BE PERFORMED BEFORE INSTALLING, OPERATING OR SERVICING THIS EQUIPMENT.
Follow all appropriate safety codes and standards.
Failure to follow instructions may result in personal injury and/or property damage.
Use extreme caution when working around power-input cables. ese cables may have potentially lethal or dangerous voltages.
Prior to energizing the equipment, have qualied personnel verify all wiring and connections against vendor drawings. Incorrect wiring and/or connections can result in equipment damage or serious system failure. If you have questions or need more information on installing and operating ASCO equipment, contact ASCO.
PRODUCT DESCRIPTION
The Advanced Redundant Control System as ARCS is solenoid operated valve system designed for use as a component in safety instrumented systems. It functions as a redundant pneumatic tripping device to control the pilot air signal to a process valve actuator. The ARCS uses 1oo2, 2oo2 or 2oo3 voting solenoids to enhance the reliability of the circuit. The ARCS consists of two or four electrically actuated solenoid valves (V1, V2, V3 & V4) and a pneumatically operated (Manually Controlled) bypass valve or isolation valve, and visual Indicators, Pressure switches. The pressure switches provide solenoid state feedback and are used during on-line testing of the ARCS unit. The bypass valve or isolation valve allows for maintenance of the solenoid valves without having to shut down the process valve. The use of the Maintenance Bypass/Isolation valve is not required for functional testing of the ARCS unit.
SERIES
141
Under normal operating conditions:
The ARCS allows for periodic testing of the solenoids by cycling one solenoid valve automatically therefore attaining the desired safety availability. This testing is performed online without the need for bypassing/Isolating of the safety action and without interruption of the process.
The ARCS supplies air to the process valve actuator through the “Process” port when energized.
When a trip occurs:
The ARCS blocks the incoming pneumatic signal and connects the “Process” port to the “Exhaust” port. This vents the air signal from the process valve actuator and allows the actuator return spring to move the process to its fail-safe position.
SPECIFICATIONS: Manifold Architecture: Normally Closed System Voltage: 12 VDC, 24 VDC, 48VDC, 120 VDC,
120/60-110/60 VAC or 230/50-240/50 VAC.
Operational Mode: De-Energized to trip. Optional Features: Visual Indicators/Pressure gauge,
Pressure switches. Dierential pressure: 0/1 - 10 bar [1 bar = 100kPa]
Maximum viscosity: 65 cSt (mm2/s) Response time: 75 - 100 ms Fluid: Dry & Non Lubricated Air
NOTE: Filtered (5 micron) instrument air recommended
Temperature Range (TS): -20°C to +60°C Seal Materials: FPM Pneumatic Valve:
3/2 solenoid operated valve. Bypass Valve: 5/2 manually operated valve Isolation Valve: 3/2 manually operated valve
Visual indicators:
Red – Air not available Green – Air available
ASCO Valves
®
E290699 - 01/2019 All Rights Reserved. IM-IND-536985-RevAA-sec1
Page 1 of 9
Pressure Switches:
SPDT switches, Steel, galvanised. Switching function-Selectable: Normally open, normally closed, change-over contact
Pneumatic Connections:
Inlet & Process: ¼” or ½” NPTF
Exhaust Port: ¼” NPTF
Approvals:
Exida Certied SIL 3 capable
Lifting:
1. Don’t use valve body or enclosure to lift the system.
2. Don’t use Pressure switches or indicators to lift the system
WARNING: Explosion Hazard! Do not remove or replace any component while circuit is live unless the area is known to be non hazardous.
Page 2 of 9
Page 2 of 4 IM-IND-536985-RevAA-sec1
No. 57, Kundrathur Main Rd., Gerugambakkam, Chennai -6000128, India www.asco.com
ASCO components are intended to be used only within the technical characteristics as specied on the nameplate. Changes to the equipment are only allowed after consulting the manufacturer or it’s representative. The solenoid valves of Advanced Redundant Control System with ATEX/IEE Ex certication is intended for installation in potentially explosive atmospheres, ATEX category 2G, gas Group IIC. The surface temperature classication depends on the voltage, wattage and ambient temperature which are stated on the nameplate. The ARCS should be mounted as closely to the process valve as possible. In order to insure proper operation of the process valve, tubing runs should be as straight and short as possible
Wiring Guidelines
The following general guidelines apply to all wiring discussed in this document.
WARNING: Circuit power must be removed from the device prior to disconnecting the wiring on either
the eld or internal side of the terminal strip.
Wire size: stranded 16 and 18 AWG.
Bypass valve in Normal mode.
Pressure Gauge(3x)
Adaptor (3x)
The terminal clamps are designed for one wire only; DO NOT attempt to terminate multiple wires into one terminal.
Use care when running signal wiring near to or crossing conduit or wiring that supplies power to motors, solenoids, lighting, horns, bells, etc.
AC power wiring should be run in a separate conduit from DC power. All power wiring to and from the ARCS should be in grounded conduit.
The ARCS should be connected to a high quality instrument grade ground with #14 AWG or heavier wire.
Electrical Connection (Customer Responsibility):
In all cases follow local and national electrical codes and conrm compliance with Zone 1 ATEX requirements.
It is recommended that standard industry practices are followed to prevent condensation from entering the enclosure and, in some cases of Class I, Div. 2 or ATEX Zone 1 conditions, to prevent hazardous gasses and vapors from migrating through the conduit to the control room or open ignition source.
REDUNDANT FUNCTIONS
1oo2 Manifold Assembly, without Online Maintenance & without Diagnostic
1oo2 Manifold Assembly, with Common By-pass & without Diagnostic
2oo2 Manifold Assembly, without Online Maintenance & Diagnostic
2oo2 Manifold Assembly, without Online Maintenance, with Diagnostic
2oo2 Manifold Assembly, with Common By-pass with Diagnostic
2oo2 Manifold Assembly, with Individual Isolation with Diagnostic
2oo3 Manifold Assembly, without Online Maintenance, without Diagnostic
2oo3 Manifold Assembly, without Online Maintenance, with Diagnostic
2oo3 Manifold Assembly, with Individual Isolation & with Diagnostic
1oo2 REDUNDANT VALVE SYSTEM
1oo2 is for safe exhausting. It is enough to close one of the two solenoid valves to exhaust the outlet. Each valve V1 & V2 are channel 1&2.
1oo2 Manifold Assembly, without Online Maintenance & without Diagnostic
1oo2 redundant valve system has two solenoid valves which are connected in series (Normally closed valve). Valve 1 outlet is connected to valve 2 inlet. Both valves are energized then outlet will supply air to actuator. Any one valve gets fail/de-energized system goes to vent position. Refer Fig-1 circuit and logic table.
CAUTION: De-energizing one or two valves will
initiate a shutdown.
Valve
Assembly (2x)
Manifold
Assembly
Mounting
Bracket
Fig: 1A
Exhaust Silencer(2x)
1oo2 Manifold Assembly, with Common By-pass & without Diagnostic: Bypass Mode
The manually operated maintenance bypass valve is used to isolate and depressurize the solenoid valves. This function allows to do maintenance of solenoid valve system without disturbing the outlet air supply. Refer Fig-2 circuit and logic table.
Fig: 2
Valve
Assembly(2x)
Bypass valve
Exhaust
Silencer (2x),
Bypass valve
Manifold
Assembly
Lockout
Mounting
Bracket
Eyeball Indicator (3x)
Exhaust Silencer(2x), main
Fig: 2A shows 1oo2 Manifold ass embly with common bypass, with visual indicator option
Fig: 2A
In “Normal” mode Bypass valve indicator will show red. When switching to “Bypass” mode Bypass valve indicator will show green.
Fig: 1
Page 3 of 9
Page 3 of 4 IM-IND-536985-RevAA-sec1
No. 57, Kundrathur Main Rd., Gerugambakkam, Chennai -6000128, India www.asco.com
Loading...
+ 6 hidden pages