ASCO Accessories Series 610 Manuals & Guides

MOTORFLOW
D
Motorised Control Valve
Vanne Motorisée
Motorregelventil
Series - Série - Baureihe 610
Installation manual
Manuel d'installation
Installationshandbuch
IM14219-R03
GB
FR
ESD
!
SUMMARY - SOMMAIRE - INHALT
English version
1. Introduction .........................................................................................................................................................3
2. Cable connection................................................................................................................................................. 3
3. Electrical connection ........................................................................................................................................... 3
4. LED indicators ..................................................................................................................................................... 4
5. Manual position adjustment................................................................................................................................. 4
6. Auto adapt ........................................................................................................................................................... 4
8. Cascaded control ................................................................................................................................................ 4
8. Frequency imput ..................................................................................................................................................4
9. Technical characteristics ..................................................................................................................................... 5
10. Accessories ......................................................................................................................................................... 5
11. Dimensions and weight ....................................................................................................................................... 5
Version française ........................................................................................................................................... 6
Deutsche Version .................................................................................................................. 10
This product contains electronic components sensitive to electrostatic
CAUTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC SENSITIVE
DEVICES
CAUTION! Dangerous operating conditions may occur when using the programming interface on the valve as the valve may possibly not react to the analog setpoint any more. Provide for protection against uncontrolled movement of equipment when putting the valve into operation and before making any modifications to the valve settings.
We herewith declare that the version of the product described in this installation manual is intended to be incorporated into or assembled with other machinery and that it must not be put into service until the machinery into which it is to be incorporated has been declared in conformity with the provisions of Council Directive 2006/42/EC. Handling, assembly and putting into service and all settings and adjustments must be done by qualified, authorised personnel only.
This product complies with the essential requirements of the EMC Directive 2014/30/EU and its amendments. It is CE-approved. A separate Declaration of Conformity is available on request. Please provide ordering code and serial numbers of products concerned.
The information in this manual is subject to change without notice.
In no event shall ASCO NUMATICS be liable for technical or editorial errors or omissions. Neither is any liability assumed for accidental or consequential damages arising out of or in connection with the supply or use of the information contained herein. THIS MANUAL CONTAINS INFORMATION PROTECTED BY COPYRIGHT. NO PART OF THIS DOCUMENT MAY BE PHOTOCOPIED OR REPRODUCED IN ANY FORM OR MANNER WHATSOEVER WITHOUT PRIOR WRITTEN PERMISSION FROM ASCO NUMATICS.
COPYRIGHT © 2016 - ASCO NUMATICS - All rights reserved.
discharge. An electrostatic discharge generated by a person or object coming in contact with the electrical components can damage or destroy the product. To avoid the risk of electrostatic discharge, please observe the handling precautions and recommendations contained in standard EN 100015-1. Do not connect or disconnect the device while it is energised.
NOTICE
IM14219-2
INSTALLATION
MOTORFLOw
4
1
3
2
4
132
GB
1. INTRODUCTION
The A DC motor controls the opening width to regulate the flow. A potentiometer is integrated into the electrical actuator to
D
is a motorised control valve designed to control the flow of liquids.
capture the position. A microcontroller enables digital control. Two buttons are provided for manual control. The setpoint is displayed in % (0-100%). A PC software and the RS232 interface allows modification of settings and parameters and data recording. The position is maintained on loss of power. The actuator remains in its current position.
2. CABLE CONNECTIONS
LEDS
M12 male connector
(power supply:
setpoint/feedback)
Display
Cover
RS232 interface
Buttons
M12 female connector
(external sensor)
3. ELECTRICAL CONNECTION
Male connector pinning (power supply)
+ 24 V DC, supply 1
analog setpoint input 2
supply ground 3
analog ground
analog output (feedback) 4
digital output (pressure switch) 5
(1)
A 6-wire cable with separate analog ground is used for cable lengths over 2 m to set off the voltage drop for the setpoint.
(2)
The housing of the M12 male connector/M12 female connector is connected to the valve body.
EMC shield Housing
(1)
M12
5
(2)
5-wire cable
(2 m)
brown brown
white white
blue green
black pink
grey grey
shield shield
6-wire cable
(5 m, 10 m)
yellow
Female connector pinning (sensor)
+ 24 V DC, supply 1
external feedback input 2
supply ground 3
frequency input 4
unused 5
EMC shield Housing
M12
5
(2)
All leaflets are available on: www.asconumatics.eu
IM14219-3
INSTALLATION
MOTORFLOw
MOTORFLOw
MOTORFLOw
MOTORFLOw
GB
4. LED INDICATORS
Red LED Low or overvoltage (flashing) Green LED Pressure switch Yellow LED Manual operation
5. MANUAL POSITION ADJUSTMENT (manual operation)
During power up after an interruption in the power supply, press both arrow buttons located beneath the display to switch to the manual mode. The operating mode is indicated by the letters "H n d" in the display. This display disappears after having pressed the arrow buttons to show the current setpoint. Use the arrow buttons to change the setpoint which changes the opening width. Exit this operating mode by pressing both arrow buttons simultaneously or by turning off the power supply for a short time.
6. AUTO ADAPT (automatic setting of stop positions)
To enter the Auto-Adapt mode, simultaneously press and hold both buttons located underneath the display for at least 3 seconds. The Auto-Adapt operating mode is indicated by the letters "AdA" in the display.
Then release and push both buttons again for at least 3 seconds to start the auto-adapt procedure. “OPn” is displayed to indicate the opening process. The module moves into the “open” position until a current increase of the motor occurs at the open position stop. The module then moves into the “closed position“. “CLO” is displayed to indicate the closing process. In this case too, the closed position stop is established by the current increase in the motor. Successful setting of both stop positions is indicated by the letters “END” in the display. Press the left button to complete the procedure and return the
Errors are immediately displayed. E 1 Timeout error (> 2 sec) for open stop position E 2 Plausibility check for open stop position failed E 3 Timeout error (> 2 sec) for closed stop position E 4 Plausibility check for closed stop position failed Push both buttons for at least 3 sec. to delete the error display and return the mode.
In the event of an error, the previous stop position settings are restored.
D
into its normal operating mode.
D
into its normal operating
7. CASCADED CONTROL
A closed control loop for flow, pressure, temperature etc. can be set up with the The setpoint is compared to the feedback signal received from the external sensor and the valve opens or closes to reach the desired value. Maintaining the mechanical position control allows to stabilise the control loop.
D
and an external sensor.
8. FREQUENCY INPUT
Flow rate sensors with turbine technology for liquid monitoring can be directly connected to the frequency input of the
max. 5000 Hz frequency. To adapt the frequency input (npn or pnp polarity and frequency range) to your needs, please contact our Product Sup­port.
All leaflets are available on: www.asconumatics.eu IM14219-4
D
. Turbine flow rate sensors with either npn or pnp outputs can be used. The frequency input can process
INSTALLATION
108
138
GB
9. TECHNICAL CHARACTERISTICS
Electrical characteristics
Setpoint 0-10V; 0/4-20mA Feedback 0-10V; 0/4-20mA Supply voltage 24VDC ±10% Power rating max. 10W Actuating time 2 sec.
Operating conditions
Ambient temperature 0...+50 °C Storage temperature -20...+70°C
10. ACCESSORIES
description catalogue number
Straight M12 female connector, 5 pins, with screw terminals Right-angle M12 female connector, 5 pins, with screw terminals
88100256 88100725
Supply cable 2 m, 5x0,25 mm², straight connector 88100726 Supply cable 2 m, 5x0,25 mm², right-angle connector Supply cable 5 m, 6x0,56 mm², straight connector Supply cable 5 m, 6x0,56 mm², right-angle connector Supply cable 10 m, 6x0,56 mm², straight connector Supply cable 10 m, 6x0,56 mm², right-angle connector RS-232 cable for PC connection Software tool for PC “Asco-MotorCom” available for download from our website at
www.asconumatics.eu
88100727 88100728 88100729 88100730 88100731 88100732
-
11. DIMENSIONS (mm), WEIGHT (kg)
M12 (2x)
126.1
56.1
16.5
80
140
85
3/4
30
55.1
1 2
3
20
29
54.5
4
5
80
weight
1,1
A Display of setpoint (0-100%) Z Operating buttons (manual operation) E Power supply R Sensor input T Programming port
Availability, design and specifications are subject to change without notice. All rights reserved.
All leaflets are available on: www.asconumatics.eu
IM14219-5
Loading...