Asco 457 Installation & Operation Manual

Surge Protective Devices
Installation & Operation Manual
Model 457
Installation, Operation and Maintenance Manual IO-70063 RevD 03-182
V
Safety First – Hazardous Voltage & Shock Hazard
Only qualified licensed electricians should install or service SPDs
Hazardous voltages exist within SPDs
SPDs should never be installed or serviced when energized
Use appropriate safety precautions including Personal Protection Equipment
Failure to follow these instructions can result in death, serious injury, and/or
equipment damage
This manual shall be read in its entirety prior to installing
Bonding and Grounding Hazard
Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electric Code (NEC®), Canadian Electrical Code (CEC) and all applicable codes.
Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground in accordance with the NEC®, CEC and all applicable codes.
During installation into an electrical system, the SPD must not be energized until the electrical system is completely installed, inspected and tested. All conductors must be connected and functional including the neutral (if required). The voltage rating of the SPD and system must be verified before energizing the SPD.
Failure to follow these guidelines can lead to abnormally high voltages at the SPD. This may cause the SPD to fail. The warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC® or CEC.
Do Not Hi-Pot Test SPDs
Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high-potential testing and then reconnected after test completion.
Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void the warranty.
Installation, Operation and Maintenance Manual IO-70063 RevD 03-183
ASCO SURGE PROTECTIVE DEVICE
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
TABLE OF CONTENTS
INTRODUCTION
Major Industry Nomenclature Changes Eective 2008-2009 Figure 1: NEC® Article 285 & UL 1449-4
4
4 4
PRE-INSTALLATION & INSTALLATION PLANNING
Operating Environment Audible Noise Mounting, Dimensions, and Weight Service Clearance Maximizing SPD Performance Cascade Surge Protection Overcurrent Protection Circuit Breaker and Disconnect Switch Wire Size and Installation Torque
6
6 7
7 7
7 8 8 8 8
SPECIAL ENCLOSURE CONSIDERATIONS
Removing and Reconnecting the Ribbon Cables NEMA Type 4X Enclosure Figure 2: Flush Mount Front & Side View Flush Mount Option Terminals Shortest Leads Possible Voltage Rating System Grounding UL 1283 Required Language Concerning the Installation of EMI Filters
8
8 9 9 9
10 10 10
11 11
GENERAL INFORMATION
Simplified Explanation of Operation Precautionary Statement Regarding SPDs on Ungrounded Systems Cascade Surge Protection Parallel Connection Unpacking & Preliminary Inspection Storage Environment Table 1: Model Number Decoder
5
5 5 5 5 5 5 6
MAINTENANCE
Troubleshooting & Service Figure 16: Troubleshooting Flowchart Module Removal & Replacement Instructions Display/Diagnostic Board Removal and Replacement Preventive Maintenance (Inspection and Cleaning) Corrective Maintenance (Repair) Limited Warranty Table 2: Replacement Parts
18
18 18 19 19 19 19
20
21
INSTALLATION
Figure 3: Typical Panel Installation Figures 4-9: Electrical Connection Diagrams Figure 10: Display Panels Control and Diagnostic Panel Service LED and the Audible Alarm Figure 11: SPD Dimensions: NEMA Type 1, 4, And 4X Stainless Steel Figure 12: SPD Dimensions: NEMA Type 3R Figure 13: SPD Dimensions: NEMA Type 4X Plastic Surge Counter Options Figure 14: Module LEDs Supplemental LED Indicators on Modules Figure 15: Pinout Diagram For Dry Contacts Of SPD Dry Contact Option Remote Monitor Accessory Option
12
12 13 14 14 14 15 15 15 16 16 16 17 17 17
Installation, Operation and Maintenance Manual IO-70063 RevD 03-184
INTRODUCTION
Thank you for choosing an ASCO Surge Protective Device (SPD). This is a high quality, high energy surge suppressor designed to protect sensitive equipment from damaging transient overvoltages.
Proper installation is important to maximize performance. Please follow steps outlined herein.
This entire Operation & Maintenance Manual should be read prior to beginning installation. These instructions are not intended to replace national or local codes. Follow all applicable electrical codes to ensure compliance. Installation of this SPD should only be performed by qualified electrical personnel.
ASCO SPDs are extensively tested in accordance with industry standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62, C62.72, UL 1449, UL 1283, IEC 61643, etc.
This SPD is a single-port parallel-connected device intended for service entrance, panelboard or downstream installation for IEEE Category C, B or A applications.
Major Industry Nomenclature Changes Eective 2008-2009
Be aware that UL 1449 Fourth Edition and 2008 NEC® Article 285 generated substantial changes.
The term TVSS changed to SPD
Types 1, 2, 3 & 4 SPDs are created
UL 1449 clamping voltage performance testing changed from 500A to 3,000A
UL 1449 added new I nominal testing (In), which consists of more rigorous duty-cycle testing
This SPD complies with the latest regulatory actions and is UL Listed as such.
For further information, please review latest editions of NEC® Art. 285, UL 1449 or contact ASCO Tech Support at (800) 237-4567.
FIGURE1: NEC® ARTICLE 285 & UL 14494
SPD Types: Types 1, 2, & 3
Based on Location within electrical distribution system
(also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B & A)
Installation, Operation and Maintenance Manual IO-70063 RevD 03-185
GENERAL INFORMATION
This is a Type 2 SPD. It includes internal overcurrent protection. Type 2 SPDs are suitable for installation on the load side of the service disconnect overcurrent device.
This device features internal overcurrent and overtemperature protection that will disconnect eected surge suppression components at the end of their useful life, but will maintain power to the load – now unprotected. If this situation is undesirable for the application, follow these instructions for servicing or replacing the device.
Service of this unit consists of replacing internal modules and/or display assembly.
There are no user-serviceable parts inside the replaceable modules. Do not attempt to disassemble the module as it stores charge and is potted.
Simplified Explanation of Operation
SPDs sense overvoltage and create a momentary short circuit to redirect harmful surge energy to earth ground. Then they reset automatically and wait for the next surge. This is similar to the pressure relief valve on a water heater: pressure goes up, valve opens to relieve pressure and then resets. In an electrical system, an SPD senses overvoltage, shorts temporarily sending energy to ground and then resets. SPDs are capable of repeating this function thousands of times.
Parallel Connection
This is a Parallel connected SPD – not series connected. As outlined above, an SPD ‘drains o’ excessive voltage from an electrical system. Because of parallel connection, installation of the SPD near the equipment to be protected is satisfactory. This eect is similar to flushing any toilet in a house; pressure in the shower goes down. In an electrical system, a parallel connected SPD will remove excessive voltage o the entire system (assuming reasonable proximity).
Tip: It is critically important that wiring leads be configured as short & straight as possible. Avoid long leads. Avoid sharp bends. Route SPD conductors in the same conduit. Leads do not have to be sized for the entire load – this SPD is parallel connected, not series connected. As a generalization, 6 AWG works fine.
Precautionary Statement Regarding SPDs on Ungrounded Systems
Caution – Ungrounded systems are inherently unstable and can produce excessively high line-to-ground voltages during certain fault conditions. During these fault conditions, any electrical equipment including an SPD, may be subjected to voltages which exceed their designed ratings. This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an ungrounded power system.
Unpacking & Preliminary Inspection
Inspect the entire shipping container for damage or signs of mishandling. Remove the packing materials and further inspect the unit for any obvious shipping damages.
If any damage was found and is a result of shipping or handling, immediately file a claim with the shipping company and forward a copy to ASCO.
Storage Environment
This SPD should be stored in a clean, dry environment. Storage temperature range is -40°C (-40°F) to +60°C (+140°F). Avoid exposure to high condensation.
Installation, Operation and Maintenance Manual IO-70063 RevD 03-186
TABLE 1: MODEL NUMBER DECODER TABLE 1: MODEL NUMBER DECODER
PRE-INSTALLATION & INSTALLATION PLANNING
Operating Environment
The standard unit is in a Type 1 enclosure. Other enclosure types are available as options. Before installing, ensure that your enclosure type and application are appropriate per NEMA 250 with regard to moisture, dirt, excessive dust, flammable materials or atmospheres, corrosive vapors, etc.
This SPD is designed in an ambient temperature range of -40°C (-40°F) to +60°C (+140°F) with a relative humidity of 0% to 95% (non-condensing). Excessive temperature may inadvertently operate internal thermal overtemperature protectors.
Audible Noise
SPD background noise is negligible or non-existent, and does not restrict the location of installation.
Mounting, Dimensions, and Weight
This SPD is designed to be wall mounted. The standard enclosure is: 12” x 12” x 7.5” (L/W/D), and the weight is 25 lbs.
Example: 457120SP16ACAE20 - Model 457, 240/120V Split Phase, 160kA, Standard Modes, Compression Lugs or Terminals, LEDs/Audible Alarm/Relay, NEMA 1/12/3R/4, Type 2, No Accessories or Options

Voltage Codes
P
Per Phase kA Rating
System
Modes of
Protection

kA Rating Per Phase
A = All Standard
Modes for that Product Line & Voltage Code
Series/
Product Line
457
Common North American Systems
120S = 240/120V Split Phase - 1Ø, 3W+Grnd, (Fig 1) 120Y = 208Y/120V Wye - 3Ø 4W+Grnd, (Fig 2)
240H = 240/120V High Leg Delta (B High), (Fig 3)
277Y = 480Y/277V Wye - 3Ø 4W+Grnd, (Fig 2) 347Y = 600Y/347V Wye - 3Ø 4W+Grnd, (Fig2) 480D = 480V Delta - 3Ø 3W+Grnd, (Fig4) & HRG Wye
Other Available Systems - Confirmation Encouraged
120N = 120V Single Phase, 1Ø 2W+G (Fig 5) 240N = 240V Single Phase, 1Ø 2W+G (Fig 5) 220Y = 380Y/220V Wye - 3Ø 4W+Grnd (Fig 2) 240C = 240V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 240D = 240V Delta - 3Ø 3W+Grnd (Fig 4) 480C = 480V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 600C = 600V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 600D = 600V Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye
16 = 160kA
24 = 240kA
09 = 90kA (SAD)
13 = 130kA (SAD) 17 = 170kA (SAD)
(SAD available in 120S & 120Y)
Installation, Operation and Maintenance Manual IO-70063 RevD 03-187
Figure 1
SPLIT 2 Phase, 1 Neutral, 1 Ground
Phase B (Black)
Phase A (Black)
Neutral (White)
V
V
}
}
Ground (Green)
Figure 2
WYE 3 Phase, 1 Neutral, 1 Ground
}
Phase A (Black)
Phase B (Black)
Neutral (White)
Phase C (Black)
Ground (Green)
A
C
N
V
B
Figure 3
HI-LEG DELTA (B High) 3 Phase, (B HIGH), 1 Neutral, 1 Ground
Phase A (Black)
Phase B (Orange)
Neutral (White)
Phase C (Black)
Ground (Green)
}
V
Figure 5
SINGLE POLE 1 Phase, 1 Neutral, 1 Ground
V
}
Neutral (White)
Phase A (Black)
Ground (Green)
Figure 4
DELTA & HRG WYE 3 Phase, 1 Ground
Phase A (Black)
Phase C (Black)
Phase B (Black)
Ground (Green)
}
V
Figure 6
CORNER GROUND DELTA (B grounded) 2 Phase, 1 Ground
Phase A (Black)
Phase C (Black)
Ground (Green)
V
}
Connection
Typ e
C = Compression
Lugs or Terminals
(No Wires Included)
Monitoring
Options
Enclosure
UL 1449
Type1/Type 2
Accessory/
Option(s)
2 = Type 2
(Includes UL1283 Filter)
0 = No Accessory/Option X = Yes Accessory/Option
Service Clearance
Service clearance is needed at the front of the Model 457 unit only, 36 inches minimum is the required distance for clearance pursuant to the NEC®.
Maximizing SPD Performance
SPD’s must be located as close to the circuit as possible to minimize parasitic losses. Surges are high current, high frequency events that cause substantial voltage drops across conductors. This hurts SPD performance. Use the shortest & straightest possible leads. Pre-Plan installations and ensure that nearest breaker positions are used. If new construction, adjust breaker locations as appropriate.
Tip: Voltage drops for normal 120V or 277V lines might be 2-3V per hundred feet. In surge applications, voltage drops might be 100-150V per foot. These voltage drops add to clamping voltage, thus hurting performance. Make every eort to keep leads short and straight.
As distribution gear becomes larger, shorter leads are more diicult to accomplish. When longer leads are unavoidable, gently twist leads together (one to two twists per foot), or tie-wrap leads together.
E = NEMA 1/12/3R/4 (metal combo)
Size - 12” x 12” x 7.5”
J = NEMA 4X (polycarbonate, display inside door)
Size - 14” x 12” x 6”
H = NEMA 4X (stainless, display inside door)
Size - 12” x 12” x 6”
Q = Flush Mount, Wall Cavity Size - 12” x 12” x 6”
X = Smaller Enclosure, Size - 10” x 10” x 6”
N = No Enclosure (includes aluminum backplane)
U = LED(s)/Aud. Alarm A = LED(s)/Aud. Alarm/Relay C = LED(s)/Aud. Alrm/Relay/
Surge Counter
Installation, Operation and Maintenance Manual IO-70063 RevD 03-188
Tip: surges create magnetic fields per the ‘right-hand rule’. When current goes in direction of thumb, magnetic field is in direction of curl of fingers. As surge current goes to SPD, fields are created in one direction. When the SPD sends those currents to neutral and/or ground, current goes in the opposite direction. If ‘coming & going’ are on the same axis, the magnetic fields can be cancelled, thus avoiding performance decrease. Gentle twists, bundling & tie-wraps accomplish this.
Cascade Surge Protection
For optimum surge protection, cascade or staged surge suppression should be implemented at the service entrance and downstream locations as appropriate. Known or expected surge sources, as well as sensitive loads, should also have localized surge suppression. For interconnected electronic loads (data cabling), SPDs should also be utilized to protect the devices on either end of the interconnecting data cables.
Overcurrent Protection
SPDs draw very little current under normal conditions and conduct for a brief duration upon encountering a transient surge current. This SPD contain internal overcurrent and overtemperature protection to protect against abnormal voltage conditions.
Supplemental overcurrent protection is not required to protect this SPD. However, connecting conductors require protection in Type 2 or 4 applications. Follow applicable codes.
Circuit Breaker and Disconnect Switch
This Model 457 family SPD is tested and qualified as a Type 2 SPD per UL 1449 Fourth Edition and 2008 NEC®. This SPD can be installed on the load side of the service overcurrent device per 2008 NEC® Article
285.
When connected on load side of main disconnect, we suggest connecting via a 60A circuit breaker. The circuit breaker is the intended disconnect switch and provides short circuit protection to the connecting conductors. Model 457 has internal overload protection elements within the product. A breaker or disconnect is not required for the SPD’s overcurrent protection. Model 457 SPDs have demonstrated 200kA Short Circuit Current Ratings (SCCR). Confer to label on unit.
Wire Size and Installation Torque
This is a parallel-connected SPD; it is not series-connected. The size of the SPD wiring is independent of the ampere rating of the protected circuit. Recommended wire is 6 AWG for phase, neutral and ground connections. Torque connections to 18 inch-pounds. Conductor length should be as short as possible.
If other wire sizes are used, we recommend that all conductors be the same gauge. Note that larger conductor might appear to be beneficial; however, it tends to have the same inductance as smaller conductor and is more diicult to work with.
Terminals accept 14 - 2 AWG conductor with 6 AWG being preferred. Coordinate conductor size and overcurrent
SPECIAL ENCLOSURE CONSIDERATIONS
Removing and Reconnecting the Ribbon Cables
The ribbon cables are marked with matching phase connections. If any of the cables are removed, reconnect the cables as marked.
Loading...
+ 16 hidden pages