Arzel Zoning ModuPASS User Guide

Page 1
Arzel R Zoning Technology, Inc.
Modulating Bypass Control
Adjustable from .05” to .5” wc Static Pressure
Locate Pressure Transmitter within 24” of Bypass Damper.
Mount in Verticle position
Static Press Transmitter
Pitot Tube (3/16”OD)
“Low” port
Fixed Restrictor (.012”)
Bypass Duct
3/8” OD Static Press Sensing Tube (clear)
1/4” Bulkhead Port
Supply Duct
Return Duct
Spring Open Bypass Damper
1/4” OD PVC Air Tube (black w/color stripe)
Operating Sequence of the Arzel
Modulating Bypass Control;
Bypass
Arzel Zoning Panel- 200 mps/AirBoss
Bypass Pressure line
Zone # 1
Press/Vac Lines
Pressure Line
Vacuum Line
When static pressure in the duct is within the normal range (.05 to .10), the static pressure transmitter allows pressure to increase in the Bypass actuator and closes the Bypass damper.
When the static pressure increases above the the preset level, the Static Pressure Transmitter reduces the pressure allowing the actuators internal spring to open the bypass damper until the maximum allowable static is reached.
The Modulating Bypass control can maintain a desired maximum static pressure by holding the bypass damper position anywhere between 0 and 100%.
Page # 1 - Modulating Bypass Operation Page # 2 - Field Retro-fit Installation instructions Page # 3 - Field Up-grade from Press Switch Control Page # 4 - Installation of Factory Installed Modulating
Bypass control.
C
Copyright 2002 Arzel Zoning Technology, Inc.
Arzel® Zoning Technology, Inc.
Page 2
R
Arzel Zoning Technology, Inc.
Modulating Bypass Control
Field Retro-Fit Installation Instructions
Locate Pressure Transmitter within 18” of Bypass Damper.
Mount in Verticle position
Static Press Transmitter
Pitot Tube (3/16”OD)
Supply Duct
Bypass Duct
Return Duct
Fixed Restrictor (.012”)
zone #1
Add Tee
Zone #1 Press
Zone #3 Vac
Zone #3 Press
Pressure Line
“Low” port
Bypass Press line
Zone #2 Vac
Zone #2 Press
Vacuum Line
Spring Open Bypass Damper
1/4” OD PVC Air Tube (black w/color stripe)
3/8” OD Static Press Sensing Tube (clear)
1/4” Bulkhead Port
Retro-Fit Installation Process
1 Install the bypass duct and “Spring Open” Bypass damper. Bypass duct should enter return duct as far from equipment as possible, prior to first reducer or take off. Bypass damper should be located on the supply end of the bypass duct.
2 Mount the Pressure Transmitter on the supply duct within 24” of the Bypass damper.
3 In the panel, insert bulkhaed fitting into blank opening (see illustration), cut a tee into the pressure line (left side of pump) and connect with tube. Connect an air line from the bulkead (top) to the Restrictor on the Pressure Transmitter tee. (black w/ red cap).
4 Insert the Pressure sensing tube into the supply duct (5/16” hole) between the equipment and the bypass duct.
Nut
Pump
Arzel Zoning Panel- 200 mps/AirBoss
Arzel® Zoning Technology, Inc.
5 Connect the damper tubing to the Pressure Transmitter Tee, opposite of the restrictor (remove red cap).
6 With only the smallest zone calling for cooling, adjust the
C
Copyright 2002 Arzel Zoning Technology, Inc.
Page 3
R
Arzel Zoning Technology, Inc.
Modulating Bypass Control
Field Upgrade from the “Pressure Switch” Bypass Control
Locate Pressure Transmitter within 24” of Bypass Damper.
Mount in Verticle position
Static Press Transmitter
Pitot Tube (3/16”OD)
Supply Duct
Bypass Duct
Return Duct
Fixed Restrictor (.012”)
Arzel Zoning Panel
Bypass Pressure line
Zone #1 Vac
Zone #1 Press
Zone #3 Vac
Zone #3 Press
Pressure Line
“Low” port
Zone #2 Vac
Zone #2 Press
Vacuum Line
Bypass
sol
Spring Open Bypass Damper
1/4” OD PVC Air Tube (black w/color stripe)
3/8” OD Static Press Sensing Tube (clear)
Up-grade Installation Process
1 Remove existing Bypass damper and replace with the “Spring
Open” damper.
2 Disconnect the wires connected to the “A” & “B” Bypass Terminals on the PC board in the panel (upper right corner).
3 Remove the Bypass Pressure Switch Control and 18-2 wire from “A” & “B” “Bypass Damper” terminals in the panel.
4 Mount the Pressure Transmitter on the supply duct in the vicinity of the Bypass damper (within 24”).
5 Connect the Bypass air tube (from panel) to the Restrictor (Black) on the Pressure Transmitter tee. (remove red cap).
6 Remove and discard the Red orfice (coupling) in the Bypass Solenoid Pressure line. (in the panel) Reconnect tube to solenoid.
7 Insert the Pressure sensing tube into the existing opening in the supply duct or drill a new 5/16” hole.
8 Connect the damper tubing to the Pressure Transmitter Tee, opposite of the restrictor (remove red cap).
9 With only the smallest zone calling for cooling, adjust the Pressure transmitter for maximum branch run velocity without air noise at the registers.
C
Copyright 2002 Arzel Zoning Technology, Inc.
Arzel® Zoning Technology, Inc.
Page 4
R
Arzel Zoning Technology, Inc.
Modulating Bypass Control
Installation and Set-Up Instructions
Locate Pressure Transmitter within 24” of Bypass Damper.
Mount in Verticle position
Static Press Transmitter
Pitot Tube (3/16”OD)
Supply Duct
Bypass Duct
Return Duct
Fixed Restrictor (.012”)
Zone 1
Zone 2
Bypass
Arzel Zoning Panel 200 mps/AirBoss
“Low” port
1/4” Bulkhead Port
Spring Open Bypass Damper
1/4” OD PVC Air Tube (black w/color stripe)
3/8” OD Static Press Sensing Tube (clear)
Installation Process
1 Install the bypass duct and “Spring Open” Bypass damper.
Bypass duct should re-enter return duct as far from equipment as possible prior to first reducer or take off. Bypass damper should be located on the supply end of the bypass duct.
2 Mount the Pressure Transmitter on the Supply Duct within 24” of the Bypass Damper.
3 Connect the Bypass air tube (pressure line from panel) to the Restrictor (Black) on the Pressure Transmitter tee. (remove red caps).
4 Insert the Pressure Sensing Tube into the supply duct (5/16” hole) on the equipment side of the bypass duct.
5 Connect the damper tubing to the Pressure Transmitter Tee, opposite of the restrictor (remove red cap).
6 With only the smallest zone calling for cooling, adjust the Pressure Transmitter (adj screw at the top, CW decreases static press, CCW increases static press) for maximum branch run velocity, with minimal air noise at the registers.
C
Copyright 2002 Arzel Zoning Technology, Inc.
Arzel® Zoning Technology, Inc.
Page 5
R
Arzel Zoning Technology, Inc.
Modulating Bypass Control
Tubing Diagram
Static Sensing Tube
Inserts into supply duct
Clear Vinyl Pressure Tube
Pitot Tube To Supply Duct
To Bypass Port at top of Panel
To “Spring Open” Bypass Damper
Arzel® Zoning Technology, Inc.
Patent pending, Copyright Arzel R Zoning Technology, Inc.
All Rights Reserved.
Loading...