NEC® compliance
Wet locations for 15A and 20A receptacles
NEC® 406.9
The NEC defines wet locations as installations underground or in concrete slabs or masonry in
direct contact with the earth; in locations subject to saturation with water or other liquids, such
as vehicle washing areas; and in unprotected locations exposed to weather.
NEC® article 406.9 (B) (1) requires all 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet
location to have an enclosure that is weatherproof whether or not the plug is inserted. These receptacles
must use a while-in-use cover.
Applicable Arrow Hart products:
WIU-1 WIU-1D WIU-2 WIUMV-1 WIUMH-1
Wet locations for other receptacles
NEC® 406.9 (B) (2)
All other receptacles installed in a wet location shall comply with (B)(2)(a) or (B)(2)(b).
(a) A receptacle installed in a wet location, where the product intended to be plugged into it is
not attended while in use, shall have an enclosure that is weatherproof with the attachment plug
inserted or removed.
(b) A receptacle installed in a wet location where the product intended to be plugged into it will be attended
while in use (e.g. portable tools) shall have an enclosure that is weatherproof when the attachment plug is
removed.
Applicable Arrow Hart products:
WLRS1 7420CR 7770 20416D S1952 S2966 S989
WLRS2 7420A 7788 WP1 S1954 S3966 S966
AH7879 5741NS 20446N WP2 S2962 S992 S1966
7420 7420C 20416N S1951 S3962 S994 S993
L
SECTION
Damp locations for receptacles
NEC® 406.9 (A)
A damp location is defined as a location protected from weather and not subject to saturation with
water or other liquids but subject to moderate degrees of moisture. Examples of such locations
include partially protected locations under canopies, marquees, roofed pen porches, and like locations, and
interior locations subject to moderated degrees of moisture, such as basements, barns, and cold storage
buildings.
NEC® article 406.9 (A) requires receptacles installed in damp locations to have an enclosure for the
receptacle that is weatherproof when the receptacle is covered (attachment plug is not inserted and
receptacle cover is closed).
An installation suitable for wet locations shall also be considered suitable for damp locations.
Therefore, all catalog numbers noted for compliance to 406.9 (B)(1) and 406.9 (B)(2) are also suitable
for use in damp locations.
Applicable Arrow Hart products:
S1961 S1962
Wet or damp locations for switches
NEC® 404.4
A surface-mounted switch or circuit breaker in a damp or wet location shall be enclosed in a weatherproof
enclosure, and flush-mounted switches and circuit breakers in damp or wet locations shall be equipped with
a weatherproof cover.
Applicable Arrow Hart products:
S983 S984 S2983 S3999