Arrow Hart - Cooper Wiring Devices Isolated Ground Devices Catalog

Hospital Grade Receptacles L-1
Hospital Grade and Commercial Specification Grade TVSS Receptacles L-2
Hospital Grade TVSS Receptacles L-3
Industrial Specification Grade Straight Blade Receptacles L-4
Hart-Lock®Locking Devices L-5 – L-7
Commercial Specification Grade TVSS Receptacles L-8
Pre-Marked Special Use Wallplates L-9
Isolated Ground Devices
Isolating the grounding circuit from harmonic distortion is an efficient and economical way to protect sensitive electronics from operational degradation, disruption, or damage. Cooper Wiring Devices has responded to the growing reliance on clean power systems with a sophisticated selection of isolated ground devices. Our line includes products that cover a wide range of applications – hospital grade, industrial and commercial specification grade straight blade and locking receptacles, transient voltage surge suppressors, and compatible plugs and pre-marked wallplates. All are built for heavy duty, designed for easy installation, and manufactured to provide users with years of dependable electrical and electronic performance.
L
Selecting the right grounding system and wiring devices – ones that completely isolate the grounding circuit from the transient signals that can be created by other ‘‘noise’’ producing sources – will provide protection for your equipment and information needs.
Install Isolated Grounding Circuits!
L-Intro
-
1
ISOLATED GROUND DEVICES
INDUSTRIAL COMMERCIAL
Isolated Ground Devices
As the use of electronics has grown, Cooper Wiring Devices isolated ground wiring devices have grown with it . . . from specification and hospital-grade straight blade receptacles and extra secure Hart-Lock® receptacles . . . to transient voltage surge suppressors . . . to compatible plugs and wallplates.
Cooper isolated ground products provide users with the security of dependable electrical and electronic performance, without the expense of often unnecessary power conditioners.
L-Intro
-
2
ISOLATED GROUND DEVICES
INDUSTRIAL COMMERCIAL
Isolated Ground Receptacle
Grounding contacts are bonded directly to the service entrance grounding system. In the illustration the insulating barrier (A) isolates the grounding contacts (B) from the mounting strap (C). The insulated grounding conductor (D) is bonded to the service entrance grounding system
How Isolated Ground is Different
A conventional receptacle is grounded to the building grounding system at the receptacle. When mounted in the box, grounding contacts are connected to the box, fittings, conduit and all other building ground system components which can act as a large antenna for EMI and RFI.
Conventional Receptacle
(D) Insulated Grounding Conductor
(C) Mounting Strap
(B) Grounding circuit and
grounding screw
(D) Insulated Grounding Conductor
(C) Mounting Strap
Outlet Box
Outlet Box
(B) Grounding circuit and
grounding screw
(A) Insulating
barrier
L-1
ISOLATED GROUND DEVICES
INDUSTRIAL COMMERCIAL
TESTING & CODE COMPLIANCE
• UL Listed to 498, (file no. E3663)
• CSA Certified to C22.2 no.42 (file no. LR7087)
MATERIAL CHARACTERISTICS
Environmental: Flammability per UL 94 requirements, V2 rated. Temperature Rating:
-40ºC to 60ºC except as noted.
Hospital Grade Receptacles
Hospital Grade Receptacles – Isolated Ground
2 Pole, 3 Wire Grounding 15A 125V, 20A 125V 15A 250V, 20A 250V
Hospital Grade – Isolated Ground Side and Back Wire
Rating Catalog No. A V/AC NEMA Colors Duplex Single*
15 125 5-15R Gray IG8200GY
Orange IG8200RN IG8210RN Red IG8200RD Ivory IG8200V IG8210V White IG8200W
20 125 5-20R Gray IG8300GY
Orange IG8300RN IG8310RN Red IG8300RD Ivory IG8300V White IG8300W
15 250 6-15R Orange IG8600RN IG8610RN
20 250 6-20R Orange IG8400RN IG8410RN
Hospital Decorator Duplex Receptacles – Isolated Ground
Rating A V/AC NEMA Colors Catalog No.
15 125 5-15R Ivory IG8262V
Orange IG8262RN
20 250 5-20R Ivory IG8362V
Orange IG8362RN
*Single receptacles meets all UL, CSA & Federal Specifications, but differ in design and
construction from duplex receptacles.
IG8200
IG8262
IG8210
All terminal (H-N-G) and mounting
screws nickel-plated, triple combination (slot/Phillips/Robertson) head for superior corrosion resistance and maximum installer flexibility.
Long, broad mounting strap helps reach
large panel cutouts for Code compliance.
Automatic grounding system eliminates
need for bonding jumper in grounded metal enclosure, provides redundant measure of ground continuity where jumper used.
Screw-Catch™ feature on duplex
devices speeds mounting of wallplates.
FEATURES
Exclusive 5-leaf brass line contacts ensure
lowest heat rise, smooth plug blade insertion and long-term retention.
Rigid, glass reinforced nylon base lends ultimate
strength and superior high heat resistance in contact carrier.
Unique screw terminal guards provide fast,
easy insulation from conductive surfaces.
Exclusive 0.030" (0.76mm) solid brass, non-
riveted, integral one-piece isolated grounding shunt system assures ground integrity under heaviest use – isolated from common building ground.
High impact and chemical-resistant nylon face.
Tapered lead-in slots on back wiring holes assist
in gathering stranded wires for faster, more secure connections.
(69.9mm)
(83.3mm)
4.19"
(106.4mm)
1.37"
(34.8mm)
2.37"
(60.2mm)
3.81"
(96.8mm)
2.75"
3.28"
(32.8mm)
1.29"
1.75"
(44.5mm)
1.40"
(35.6mm)
1.32"
(33.5mm)
1.30"
(33.0mm)
(17.0mm)
0.88" (22.4mm)
0.67"
1.72" (43.7mm)
2.75" (69.9mm)
3.28" (83.3mm)
3.28" (83.3mm)
0.88" (22.4mm)
5-15R
G
G
W
W
5-20R
G
6-15R
G
6-20R
Loading...