7 INSTALLATION TIPS AND TRICKS ..................................................................................24
1
Gas Monitor 1AVC Two Channel Monitor
2
Gas Monitor 1AVC Two Channel Monitor
1WARRANTY
The AMC-1AVC two-channel monitor is warranted against defects in material and workmanship
for a period of two (2) years from date of shipment (except electrochemical sensor elements,
catalytic elements and portable monitors – one (1) year – refer to individual spec sheets for
additional exceptions). Calibration is not warranted. During the warranty period, Armstrong
will repair or replace components that prove to be defective in the opinion of Armstrong
Monitoring. The corporation is not liable for auxiliary interfaced equipment, nor consequential
damage.
NOTE: Any substitution or tampering with components without expressed, written permission of
ARMSTRONG MONITORING may result in intrinsic damage which will cancel the effectiveness
of the warranty. Extended warranties are available through the factory. Please contact factory.
Service agreements may supersede standard warranty terms.
1.1 LIABILITY
All Armstrong Monitoring systems shall be installed by a qualified technician and maintained
according to Armstrong Monitoring Installation and Maintenance Manual instructions.
Armstrong Monitoring shall not be responsible for any liability arising from auxiliary interfaced
equipment, consequential damage, the installation, or the operation of this equipment.
Armstrong’s total liability is contained in the warranty conditions stipulated above. No other
acceptance of liability is expressed or implied by Armstrong Monitoring. Except as set forth
herein, Armstrong Monitoring makes no warranty, expressed or implied, with respect to the
fitness for any particular purpose or use or otherwise of the products or services, or on any parts
or components or labour furnished as part of the sale. In no event shall Armstrong Monitoring,
its officers, directors, employees, agents or servants be liable to the buyer or any other party for
any loss of profit, loss of use, incidental, consequential or special damages arising out of the
sale, delivery, servicing, use, loss of use, of the products or of any part thereof, irrespective of
whether Armstrong Monitoring or any of its officers, directors, employees, agents or servants
has advanced notice of the possibility of such damages. In no event will the total liability to the
buyer exceed the sum paid to Armstrong Monitoring by buyer for the products and services.
1.2 PRODUCT RETURN
All products that must be returned for warranty service will be shipped by prepaid freight and will
only be accepted with a Returned Materials Authorization (RMA) number issued by
ARMSTRONG MONITORING. Goods returned to the client will be by freight collect.
1.3 MODIFICATIONS AND SUBSTITUTIONS
Due to an ongoing development program, Armstrong Monitoring reserves the right to modify the
design and substitute components in any of its products without prior notice. All changes are at
the sole discretion of Armstrong Monitoring, and the corporation shall not be liable for any cost
arising out of such modifications or substitutions that may be incurred by the user.
3
Gas Monitor 1AVC Two Channel Monitor
2PRODUCT INFORMATION
Monitor Part Number….…………………………………. AMC-1AVC
Monitor Serial Number. ………………..………………...
DSI Part Number…………………………………………. AMC-DSI-91AD-98AA-X
DSI Serial Number. ………………..……………….........
DSI Warranty Period……………………………………...2 year
Sensor Warranty Period………………………………….
CO Channel 1 __________________
Channel 2 _________________
NO
2
Power Supply Requirement. ………………….……..…. 120 VAC, 60 Hz, 30 VA
Operating Temperature.…….………………….……..… -20°C to +40°C (-4°F to +104°F)
All Armstrong Monitoring systems must be installed and maintained according to
instructions, to ensure proper operation. Only qualified technicians should install and
maintain the equipment.
4
Gas Monitor 1AVC Two Channel Monitor
3 PRODUCT DESCRIPTION
3.1 GENERAL DESCRIPTION
The Gas Monitor 1AVC is a two channel gas monitoring system incorporating state of the art
sensing technology using micro-controller based design to provide continuous, reliable
surveillance of surrounding air for traces of hazardous gases (listed in Section 2). The DSI (Dual
Sensor Interface) permits two on-board sensor inputs and two 4-20 mA signals out. The monitor
comes with the following features, see Figures 1 and 2.
3.1.1 MONITOR FEATURES
1. RUN/FAULT/OFF INDICATOR:A green LED for each channel.
RUN: LED on
FAULT: LED flashing
OFF: LED off
2. WARNING INDICATOR: Warning levels of gas are indicated by a yellow LED for
each channel. Warning concentrations are indicated in
Section 2
3. ALARM INDICATOR: Alarm levels of gas are indicated by a red LED for each
channel. Alarm concentrations are indicated in Section 2
4. POWER TERMINAL BLOCK: For line voltage connections of 120 VAC, 60 Hz
5. TRANSFORMER: A Class II, step down transformer powers the internal
circuitry and remote sensor at low voltages. Located
underneath the PCB
6. INTERNAL WIRING HEADER: Provides wiring connection points as follows:
7. AUDIO ALARM INDICATOR: The buzzer will activate for Alarm, Warning
(configurable) and Fault conditions, with a distinct tone
for each one
8. RELAY SETUP JUMPERS: Used to independently configure the Warning and Alarm
relays as Normally Energized or Non-Energized
9. TEST SWITCH: The test switch is provided to electronically simulate
alarms in order to test audio and relay functions
10. CHANNEL 1 ADJUSTMENT: Sets the Alarm and Warning for channel 1
5
Gas Monitor 1AVC Two Channel Monitor
11. CHANNEL 2 ADJUSTMENT: Sets the Alarm and Warning for channel 2
12. PROGRAMMING DIP
SWITCHES:
13. RELAYS: 2 alarm DPDT relays are provided
14. DSI (Dual Sensor Interface): Dual sensor interface: allows two on board sensors and
15. ON-BOARD SENSORS: Sensors allows local detection of gas
Allows user to configure the alarm delay and timer
circuits, audio alarm activation, sensor mode selection,
fault threshold, and acknowledge switch function
a 4-20mA signal out
16. SIGNAL INPUT/OUTPUT
TERMINAL BLOCK:
2. WARNING
INDICATOR
Allows connection to transmitter input and output
Channel 1: Pins 1-6
Channel 2: Pins 7-12
1, 7 - Negative
2, 8 - 4-20mA out
3, 9 - Power
4, 10 - 4-20mA in
5, 11 - Chassis ground
6, 12 - Signal ground
3. ALARM INDICATOR
1. RUN/FAULT/OFF
INDICATOR
FIGURE 1: Gas Monitor 1AVC, Front Cover.
6
Gas Monitor 1AVC Two Channel Monitor
FIGURE 2: Internal Features of the Gas Monitor 1AVC.
7
Gas Monitor 1AVC Two Channel Monitor
4INSTALLATION
Follow the guidelines in this section for proper locations and installation of the Gas Monitor
1AVC. In addition to these instructions, ensure installation is compliant with local building and
electrical codes. This section covers topics related to installation location, mounting, cable
selection, wiring instructions and monitor function programming for the Gas Monitor 1AVC.
4.1 MOUNTING INSTRUCTIONS
Securely fasten the Gas Monitor 1AVC unit on a solid, non-vibrating surface or structure. Install
the unit where it is not exposed to rain or water spray. Install in an area where the local
concentration of gas is unaffected by the presence of ventilation systems and away from
sources of interference gases. Mount the monitor where the unit can be observed periodically.
For most applications the monitor should be mounted 1.2 -1.8 m (4-6 ft) from the floor. See
Figure 3 for mounting hole locations.
CAUTION: All cable entry MUST BE through the BOTTOM of the monitor enclosure only.
Other entry locations will allow foreign materials to enter the enclosure, causing possible
damage to the internal components.
225 mm
(8.875")
140 mm
(5.500")
Ø9.5 mm
(Ø0.375")
4 HOLES
FIGURE 3: Locations of Mounting Holes.
8
Gas Monitor 1AVC Two Channel Monitor
4.2 WIRING
4.2.1 MONITOR WIRING
POWER SUPPLY: The monitor operates on 120 VAC, 60 Hz. A Class II step down
transformer runs the internal circuitry at low voltages. The power
supply connections are made at the power terminal block located
inside the monitor, see Figure 4.
RELAYS: The 2 “Ice Cube” DPDT relays are set for different alarm conditions;
one ALARM and one WARNING. The contacts are rated for
10Amps@250VAC resistive. For relay contact arrangement, see
Figure 5.
The Gas Monitor 1AVC is shipped with 2 relays factory configured to be de-energized in the
non-alarm state. If the user prefers to have relays in a normally energized (failsafe) state see
section 4.4 for jumper configuration.
All programmable settings are factory configured for use with sensor options provided on
original order. Certain user options however may be set according to preferences in the field. Be
certain to observe appropriate interconnection of sensors to specified monitor inputs (see
Section 2).
9
Gas Monitor 1AVC Two Channel Monitor
FIGURE 4: Location of Power Supply Connections.
FIGURE 5: Relay Contact Arrangement for 2 or 3 Relays.
4.2.2 GAS MONITOR INTERFACE CONFIGURATION
The AMC-1AVC is factory configured to the following setting.
The input interface is configured by strapping the jumpers shown in Figure 6; note V+ equals
18-22 volts.
Table 1: Signal input configuration jumper selection
SIGNAL INPUT
CONFIGURATION
DSI 4-20 mA V+ 4-20 mA V+
JB 8
TERMINATION
SENSOR 1 SENSOR 2
JB10
POWER SUPPLY
JB7
TERMINATION
POWER SUPPLY
JB9
Note:
The signal input configuration jumpers are under the DSI board. Turn off the main
power supply of the monitor before removing the DSI board to configure the jumpers.
10
Gas Monitor 1AVC Two Channel Monitor
NOTE: THE DSI BOARD IS REMOVED
JB8
MD-V
SS
JB10
JB7
JB9
JB8
SS =
MD-V =
4-20mA
+5V
V+
MD-V
SS
4-20mA
+5V
V+
EXAMPLE
SENSOR 1
SENSOR 2
JB10
V+ =
+5V =
4-20mA =
FIGURE 6: Gas Monitor signal input configuration jumpers.
4.2.2.1 On-Board Sensors Connection
Most sensors have a socket connection to the DSI board for easy sensor replacement in the
field while others are directly soldered. For removal, unplug the sensor from the DSI when the
main power supply is turned off. For installation hold the sensor in such a way that the sensing
area is not covered. Align the sensor pins with pin sockets on the DSI and lightly push the
sensor on to the DSI. Sensors need to be calibrated at regular intervals, see 5.6.2 AMC-DSI
CALIBRATION for procedure. Sensor replacement is needed when the sensor life has expired;
see 6.3 SENSOR REPLACEMENT for details.
CAUTION
TURN OFF THE MAIN POWER SUPPLY BEFORE REMOVING THE SENSORS AND HAVE THE
POWER OFF WHEN INSTALLING AS WELL.
11
Gas Monitor 1AVC Two Channel Monitor
4.2.2.2 Building Automation Wiring
On the DSI board, only the 4-20mA output portion of the signal input/output terminal block (see
Figure 2, item 16), is available if there are on board sensors. This output can be connected to
the building automation system. Figure 7 show a detailed depiction of the signal input/output
terminal block.
CHANNEL 1 CHANNEL 2
456789101112
123
TOP VIEW
CHANNEL 1
24681012
357911
1
FRONT VIEW
CHANNEL 2
PINS
CH 1 CH 2
1
7
8
2
3
9
4
10
11
5
12
6
SYMBOL
4-20mA
OUT
4-20mA
IN
CGND
DESCRIPTION
NEGATIVE
4-20mA SIGNAL OUTPUT
POSITIVE
4-20mA SIGNAL INPUT
CHASSIS GROUND
SIGNAL GROUND
FIGURE 7: Signal input/output terminal block.
Note:
Use Copper Conductors Only.
The building automation system is wired to the Gas Monitor through the signal input/output
terminal block on the DSI board. The wiring for channel 1 and 2 are conveyed in the following
table.
Gas Monitor Building Automation System
Negative - → Not applicable
4-20mA signal output
Positive + → Not applicable
4-20mA signal input
Chassis ground
Signal ground -
4-20mA
out
4-20mA
in
CGND
→ 4-20mA signal input
→ Not applicable
→ Connect to shield of cable
→ Negative -
12
Gas Monitor 1AVC Two Channel Monitor
CHANNEL 1CHANNEL 2
CHANNEL 1CHANNEL 2
4-20mA
OUTIN
SENSE RESISTOR
SENSE RESISTOR + LOOP
<= 500 Ohms
CGND
4-20mA
OUTIN
4-20mA4-20mA
CGND
23456789101112
1
EXAMPLE OF CHANNEL
1 CONNECTION
EXAMPLE OF CHANNEL
2 CONNECTION
FIGURE 8: Building Automation Wiring.
4.3 DIP SWITCH PROGRAMMING
The circuit board has two blocks of DlP-switches for configuring the various functions; see
Figure 2, item 12. Each DIP-switch can be set to OFF (left position) or ON (right position)
depending on functions required.
Table 2: DIP-switch programming chart
Switch Feature Position Description
SW1-1 Activate
Alarms until
Acknowledge
(Latching
Relays)
OFF
ON Once activated, warning and alarm relays remain
Warning and alarm relays are automatically de-activated
once activating condition has been removed and
minimum run timer has expired.
activated (latched) until activation condition has been
removed, minimum run timer has expired and the
Acknowledge button has been pressed.
13
Gas Monitor 1AVC Two Channel Monitor
Switch Feature Position Description
SW1-2,
SW2-2
Minimum Run
Timer
SW1-3,
SW1-4
Sensor Type
(Mode
Select)
SW1-6 Number of
Sensors
See
Description
See
Description
OFF
ON Only channel 1 enabled.
Warning and alarm relays are maintained in alarm state
for a minimum time interval following alarm activation, as
follows:
SW1-2 SW2-2 Minimum Run Time
OFF OFF 0 minutes
ON OFF 5 minutes
OFF ON 10 minutes
ON ON 30 minutes
Note that a sensor level falling below the alarm threshold
and then re-occurring during this time resets the alarm
timer for the associated alarm.
Sensor type (threshold mode) is selected as follows:
SW1-3 SW1-4 Sensor Type (Mode)
OFF OFF Both channels Increasing
ON OFF Both channels Decreasing
OFF ON Channel 1 Decreasing
Channel 2 Increasing
ON ON Reserved
Channel 1 and 2 are enabled.
SW1-7 Two Zone
Enabled
SW1-8
Enable One
group of
Relays
AMC 1AVC only functions with this switch OFF.
OFF
One zone.
ON Two zones.
ON
AMC 1AVC only functions with this switch ON.
Only the first group of relays Warning/J2-2 and Alarm/J2-
3. See SW2-1 for double duty Alarm and Fault.
Signals exceeding thresholds on either channel will
result in relays being activated
14
Gas Monitor 1AVC Two Channel Monitor
Switch Feature Position Description
SW2-1 Alarm Relay
Activated
when Fault is
Detected
SW2-3 Audio Enable
for Warning
SW2-4 Sensor Fault
Threshold
SW2-5 Activation
Delay,
Warning or
Sensor 1
OFF
ON When fault is detected, the Alarm relay is activated.
OFF Audio alarm is disabled for Warning conditions
ON
OFF Sensor Fault thresholds set at 0.4 mA into 250R or 100
ON
OFF
ON Five minute delay on activation of Warning (2-threshold)
The Alarm relay is not activated when fault is detected.
When only one group of relays is selected (see SW1-8),
if fail is detected on a channel which is enabled (see
SW1-6) then the Alarm relay is activated
When two groups of relays are selected (see SW1-8), if
fail is detected on a channel which is enabled (see
SW1-6) then the Alarm relay associated with the
channel is activated.
(2-threshold sensor modes only).
Audio alarm is activated in conjunction with Warning
(2-threshold sensor modes only).
mV.
Sensor Fault thresholds set at 1.4 mA into 250R or
350mV.
No activation delay of Warning / S1 alarm conditions.
or Sensor 1 (1-threshold) alarm conditions following
sensor exceeding alarm threshold.
SW2-6 Activation
Delay, Alarm
or Sensor 2
Enable
OFF
ON Delay on activation of Alarm (2-threshold) or Sensor 2
OFF Audio alarm (buzzer) disabled. SW2-7 Audio Alarm
ON
No activation delay of Alarm / S2 alarm conditions.
(1-threshold) alarm conditions following sensor exceeding
alarm threshold.
Audio alarm (buzzer) enabled.
4.4 ALARM RELAY PROGRAMMING
The WARNING and ALARM relays may be configured as normally energized or normally deenergized with the jumper straps identified in
State and shown in Figure 2, item 8
employed, activating the relay when an alarm condition is detected.
The “normally energized” position is selected when failsafe operation is required. For example,
the requirement is that when power to the Gas Monitor is lost, the load connects to a power
source via contacts of this, normally energized relay.
Table 3 WARNING and ALARM Relay Active
. Typically the “normally de-energized” position is
An audio alarm output is provided, which produces various alarm sounds, as shown in the chart
below. The audio alarm can be disabled by turning OFF the DIP-switch SW2-7.
Table 4: Audio alarm operation
Sensor Status Output
Normal off
Warning (SW2-3 OFF, 2-threshold modes only) off
Warning (SW2-3 ON, 2-threshold modes only) two long, slow beeps.
followed by short pause
Any Sensor (1-threshold modes),
or Alarm (2-threshold modes)
Any Sensor Fault
(with no unacknowledged alarms on opposite sensor)
Notes:
1) Micro-controller operation ensures that Warning, Alarm and
Fault conditions will not occur simultaneously on the same sensor.
2) An Alarm or Warning condition on either sensor overrides a Fault condition
on the opposite sensor.
four fast beeps, followed
by short pause
short, slow beeps
16
Gas Monitor 1AVC Two Channel Monitor
5OPERATION AND CALIBRATION
This section covers the operation and calibration procedures pertaining to the Gas Monitor
1AVC.
5.1 POWER-ON DELAY
Following successful completion of all self-tests, detection of sensor WARNING, ALARM and
FAULT conditions is disabled for 30 seconds. This delay is provided to allow the sensors to
stabilize. During this delay, the status LEDs shows the “sensor normal” condition (only the green
LED on). The audio alarm is silent, and the alarm relay outputs are held in the non-alarm
condition.
5.2 TEST SWITCH FUNCTION
While pressed, the on-board test switch will cause continuous activation of the alarm relay
outputs (energized or de-energized, depending on configuration), continuous activation of the
audio alarm, and all status LEDs will be illuminated. Sensor processing and updating of internal
status and timers continues. When released, the outputs and LEDs return to normal operation.
5.3 ACKNOWLEDGE FUNCTION
An option exists for an Acknowledge pushbutton switch. When pressed, any present
WARNING, ALARM or FAULT condition, including those previously acknowledged, will be
silenced (audio alarm off) for 30 minutes. If any WARNING, ALARM or FAULT condition
remains after 30 minutes, the audio alarm will again be activated. Any WARNING, ALARM or
FAULT condition returning to normal and then reactivating, or any new WARNING, ALARM or
FAULT condition will cause an immediate audio alarm.
If the Activate Alarms Until Acknowledge (latching relays) (SW1-1 ON) feature is enabled, the
alarm outputs will not automatically return to normal, but will remain in alarm until the
acknowledge button has been pressed. While a relay remains latched, the audio alarm remains
active.
5.4 ALARM/WARNING RELAY ACTIVATION DELAYS
The Gas Monitor 1AVC comes standard with 5 min activation time delays for the WARNING and
ALARM relay contacts. The activation time delays can help prevent short cycling
WARNING/ALARM in some applications. The delays can be enabled by turning ON switches
SW2-5 and SW2-6, for WARNING/ALARM respectively.
5.5 RELAY OUTPUTS
The Gas Monitor 1AVC is factory configured as single relay group and single zone. In this
setup, a WARNING condition on either sensor will result in activation of the WARNING relay
17
Gas Monitor 1AVC Two Channel Monitor
output. An ALARM condition on either sensor will result in activation of both the WARNING and
ALARM relay outputs.
Each alarm relay (WARNING, ALARM) may be selected as either energized when alarm active,
or de-energized when alarm active, using on-board jumpers JB11 and JB12 respectively. This
option is provided to allow configuration flexibility. If configured to energize the relay when alarm
becomes active (jumpers set to “normally de-energized”), a controller failure or controller power
failure will prevent an alarm condition from being produced. The opposite setting of jumpers
(relay “normally energized”) will result in an alarm condition produced on reaching the gas
threshold level, controller failure or controller power failure.
5.6 CALIBRATION/SERVICE
Gas sensors need to be calibrated and periodically checked to ensure sensor accuracy and
system integrity.
The Gas Monitor 1AVC system comes factory calibrated and does not need to be adjusted as
part of installation. Periodic calibration is required on the Gas Monitor 1AVC system; please
contact the factory for recommended calibration intervals for your application. Direct service
enquiries to The Armstrong Monitoring Corp at (800)465-5777 or
service@armstrongmonitoring.com
installed and powered up, but a test for correct operation is recommended after a stabilization
period.
. The monitor should not need re-calibration when first
5.6.1 TRIP THRESHOLD ADJUSTMENT
The DSI supply a linear 4 to 20 mA signal to the monitor. This translates to a 0.4 to 2.0 volt DC
signal at TP4 (Sensor 1) and TP1 (Sensor 2) see Figure 9. The alarms are set to correspond to
some fraction of the transmitters full scale calibration, see section 2 PRODUCT INFORMATION.
Table 5 and Figure 9 below are provided to identify key components used in trip threshold
adjustment.
• TP4 (sensor 1) and TP1 (sensor 2) are used to monitor the signal from the sensors.
• RV5 (sensor 1) and RV2 (sensor 2) are used to set a threshold at which the
WARNING is triggered. TP5 (sensor 1) and TP2 (sensor 2) are used to monitor these
WARNING levels.
• RV6 (sensor 1) and RV3 (sensor 2) are used to set a threshold at which the ALARM is
triggered. TP6 (sensor 1) and TP3 (sensor 2) are used to monitor these ALARM
levels.
FIGURE 9: Gas Monitor 1AVC Test Points and Trimpots.
5.6.1.1 Equipment Required
• Digital multimeter with a minimum display range of 0 to 10.0 VDC.
• Miniature screwdriver or trimmer adjustment tool.
TP6
TP5
TP4
TP3
TP2
TP1
RV6
RV5
RV3
RV2
5.6.1.2 Trip Threshold Adjustment
Ensure that the interface is configured for 4-20 mA transmitters.
The formula below is used to determine the voltages the thresholds are adjusted to with the
trimpots.
V
alarm
= ((C
alarm
/ C
full scale
* I
Range
) + I
base
) * R
termination
* K
Gas Monitor 1A
Where
• V
– The voltage measured at the alarm test point while adjusting the alarm
alarm
trimpot.
• C
• C
• I
• I
• R
• K
- The target gas concentration for the alarm
alarm
- The gas concentration corresponding to full scale (20 mA)
full scale
– Calibrated at transmitter, typically 16 mA for full range.
Range
o I
– fixed at 4.0 mA
base
termination
Gas Monitor 1A
Range
+ I
typically add to 20 mA.
base
– fixed internally on Gas Monitor at 250 ohms
– constant which describes the scaling used within the Gas Monitor,
fixed at 0.4
19
Gas Monitor 1AVC Two Channel Monitor
EXAMPLE 1: To set an ALARM threshold of 100 PPM for a 4-20 mA transmitter calibrated for
20 mA for a concentration of 100 PPM;
• C
• C
• I
• V
• For sensor 1, RV6 would be adjusted so that 2.0V is measured at TP6.
EXAMPLE 2: Using the same transmitter as example 1, set a WARNING threshold of 25 PPM;
• C
• C
• I
• V
• For sensor 1, RV5 would be adjusted so that 0.8V is measured at TP5.
Every AMC-DSI sensor/transmitter is factory calibrated, so each unit should be ready for
operation after installation and a 30 minute stabilization time.
Periodic calibration is required as a part of regular maintenance. Calibration is needed every 3
to 6 months depending on the application. When the sensor life has expired, sensor
replacement is needed, see 6.3 SENSOR REPLACEMENT.
Caution:
- Only qualified personnel should perform the actual calibration.
- Users new to gas calibration are advised to consult with Armstrong Monitoring
The Armstrong Monitoring Corporation offers the following plans:
1. On site installation and calibration by Armstrong Monitoring
2. On site calibration by Armstrong Monitoring
3. Training by Armstrong Monitoring
4. Extended warranty calibration program
5.6.2.1 On Site Calibration Equipment Required
• Digital multi-meter with a minimum display range of 0 to 10.0 VDC.
• Miniature screwdriver or trimmer adjustment tool.
• Calibration adapter, available from AMC
• Zero and Span gases (Contact AMC for information)
5.6.2.2 Calibration Procedure
Calibration of the gas sensor involves two steps. First the “zero” must be set and then the
“span” must be calibrated.
20
Gas Monitor 1AVC Two Channel Monitor
Note:
The calibration procedure may cause false alarm and or fail signal. Appropriate
precautions may be required.
Refer to the Figure 10 below to perform the following calibration procedure:
1. Open the front cover on the Gas Monitor 1AVC enclosure.
2. Attach the multi-meter as shown in Figure 10.
• Connect negative (black) lead to TP22 (main board)
• Connect positive (red) lead to TP4 (Ch.1) / TP1 (Ch.2) (main board)
3. Apply a Zero gas sample, with a calibration adapter cup firmly and completely
over the sensor on the AMC-DSI for 2 minutes with a flow rate of .5 liters per
minute.
4. At 2 minutes adjust the Zero trimmer VR1 (Ch.1) / VR2 (Ch.2) (DSI board) for a
reading of 0.4 V +/- 5mV.
5. Apply the Span gas sample, with a calibration adapter cup firmly and completely
over the sensor on the AMC-DSI for 2 minutes with a flow rate of .5 liters per
minute. Since the output range is 0.4 to 2.0 V, a full-scale concentration should
register 2.0 V after a 2 minute exposure. Proportionately, a half-scale
concentration of gas should register 1.2 V, and so on.
V span adjust = ((Gas used / Full scale) x 1.6VDC) + 0.4 VDC.
6. At 2 minutes adjust the Span trimmer VR3 (Ch.1) / VR4 (Ch.2) (DSI board) for the
appropriate the Span voltage reading.
7. Make sure alarm indicators (see Figure 1, item 1) turn on when meter reading
passes the WARNING and/or ALARM thresholds.
8. Let sensor recover is air.
21
Gas Monitor 1AVC Two Channel Monitor
DIGITAL
MULTIMETER
BLACK (-) LEAD
MAIN BOARD
GND
TP22
SENSOR 1SENSOR 2
DSI BOARD
CH1
VR1
VR3
TP3
ZERO
SPAN
1234567891011
4-20mA
4-20mA4-20mA
4-20mA
OUT IN
IN
OUT
CGND
CH1CH2
FIGURE 10: AMC-DSI Test Points and Trimpots.
12
CGND
CH2
VR2
VR4
TP4
Sensor 1
TP1
Sensor 2
COM
VDC
RED (+) LEAD
5.6.2.3 Recalibration
Every 3 to 6 months
22
Gas Monitor 1AVC Two Channel Monitor
6PREVENTIVE MAINTENANCE
This section covers all aspects of the Gas Monitor 1AVC. First, a description of general
maintenance is given followed by a verification of operation and sensor replacements.
6.1 GENERAL
The monitor unit should be brushed or wiped clean, once a year or more, of any dust or dirt that
settles on it, depending on the accumulation.
The unit SHOULD NOT be submerged in water or other liquids. Also, hosing and other
conditions that could cause a liquid to enter the enclosure should be avoided.
6.2 VERIFICATION OF OPERATION
To verify the operation of the system, make sure that the green power LED indicator is on
steady state. Push and hold the test button to verify the audio and WARNING and ALARM
relays are operational.
6.3 SENSOR REPLACEMENT
The sensor should be replaced when the sensor no longer adequately responds to test gas.
Refer to the calibration section and follow the calibration steps to apply the test gas to the
sensor.
CAUTION
TURN OFF THE MAIN POWER SUPPLY BEFORE ATTEMPTING THE FOLLOWING PROCEDURE.
Refer to the corresponding installation section; 4.2.2.1 On-Board Sensor(s) Connection for
proper removal and installation of the sensor. New sensor elements may require calibration; see
the calibration section 5.6.2 AMC-DSI CALIBRATION for details.
23
Gas Monitor 1AVC Two Channel Monitor
7 INSTALLATION TIPS AND TRICKS
CABLING
• Cabling – use 2 conductor cable with 2 wire transmitter and 3 conductor cable with
everything else. Generally, 18 gauge conductors are used (not true in all cases).
Shielded wires are used to connect all gas sensors.
• Route cabling in conduit to avoid damage to cabling.
• Sensor cable sheath must be grounded at the monitor end only; the cable sheath at the
sensor must be clipped short and wrapped with electrical tape to avoid electrical contact
with any components in the housing.
• Route cabling away from AC power cabling and any source of electro-magnetic
interference (EMI) or radio frequency interference (RFI) such as power transformers,
electric motors, etc.
• All cabling must enter the sensors and monitors from the bottom to ensure protection
against water damage due to water inside the conduit from condensation or leaks.
• Ensure that there are no short or open circuits in the sensor cabling.
• Verify that there is no AC or DC voltage present on the sensor cabling prior to
connecting the cabling to either the sensor or the monitor.
EQUIPMENT LOCATION
• Mount all equipment away from any source of electro-magnetic interference (EMI) or
radio frequency interference (RFI) such as power transformers, electric motors, etc.
• Mount sensors in accordance with the installation guidelines for the specific species of
gas to be detected; i.e. CO sensors should be mounted at breathing height etc.
• Equipment must be positioned such that the chance of water damage is minimized; i.e.
away from fire suppression sprinkler heads, away from wet or damp locations where
there would be a risk of water damage.
• Ensure a balanced layout of sensors to cover the intended area.
• Ensure that sensors are not in close proximity to clean air sources.
POWER AND GROUNDING
• All power and grounding connections to equipment must be made in accordance with
applicable electrical and building codes.
• A separate, dedicated, noise free, 15 amp power circuit, with an appropriately labeled
circuit breaker.
24
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.