This bulletin should be used by experienced personnel as a guide to the installation of the
FLO-RITE-TEMP Instantaneous Water heater. Selection or installation of equipment should always
be accompanied by competent technical assistance. You are encouraged to contact Armstrong
International, Inc. or its local sales representative for additional information.
Page 2
FLO-RITE-TEMP
INSTANTANEOUS WATER HEATER
INSTALLATION AND ADJUSTMENT INSTRUCTIONS
NOTICE
No water heater will work satisfactorily if improperly installed and operated. These instructions contain
important information for the installation and adjustment of the FLO-RITE-TEMP Water Heaters. Read
these instructions carefully before installing this unit. FAILURE TO ADHERE TO THESEINSTRUCTIONS COULD RESULT IN SERIOUS BODILY INJURY OR PROPERTYDAMAGE.
STEAM PIPING INSTALLATION OF A SINGLE UNIT
Single and Double Wall
Steam
In
Armstrong Pressure
Reducing Valve (If Req'd)
Armstrong
I.B. Trap
Armstrong Thermostatic
GP-2000
Air Vent
2-15 psig Steam
in the Shell
Vacuum Breaker
Pressure
Gauge
Gate
Valve
Safety Relief
Valve
Armstrong
I.B. Trap
NOTE: FLO-RITE TEMP is provided with (1) one Armstrong Steam Trap and Thermostatic
Air Vent (shaded). All other items shown not included.
Fig. 2-1
NOTE: units may be piped in parallel for larger capacity requirements. See Fig. 15-1 for an example of
parallel unit installation.
The unit includes the mixing valve mounted to the heat exchanger, channel iron and U-bolts mounted,
thermostatic air vent installed on the heat exchanger, a water pressure pop off valve integral to the unit control
valve and a separate Armstrong Inverted Bucket Steam Trap.
STEAM SIDE INSTALLATION
(Refer to Fig. 2-1)
1.Install the FLO-RITE-TEMP with adequate room to allow for tube bundle removal when cleaning is
required. See Table 12-1 for specific dimensions.
2.If 2-15 psig of steam is available a pressure reducing valve is NOT required. If a pressure reducing valve is
required, an Armstrong Inverted Bucket Steam Trap is recommended to drain condensate at the inlet of the
pressure reducing valve.
October 31, 2002 @ 3:15 pm
2
Page 3
3.An Armstrong Y-strainer should be installed
before the pressure reducing valve to reduce the
chance of dirt fouling.
4.If an externally piloted pressure reducing valve is
used, the control pipe should be pitched away
from the PRV and installed at the pressure gauge
on the shell of the heat exchanger.
5.A steam safety relief valve should be used prior to
the heat exchanger if either or both of the
following conditions exist. (1) If the maximum
steam pressure could exceed the minimum water
pressure in the tubes, or (2) The maximum steam
pressure could exceed 150 psig (the maximum
steam pressure rating of the shell).
IMPORTANT -Steam supply pipe size
coming to the heat exchanger should NOT be
smaller than the steam connection supplied on
the heater, otherwise steam flow could be
restricted. If a pressure reducing valve is used,
installation should be as close as possible to the
Flo-Rite-Temp. Downstream piping from the
Pressure Reducing Valve should be expanded
immediately after the PRV to accomodate the
expanded volume of steam.
6.To vent start-up air, an Armstrong Thermostatic
Air Vent is included and installed on the top
connection, opposite the trap drain connection of
the heat exchanger. This discharge can be piped
to drain or the floor if preferred.
7.Install a vacuum breaker in the piping between the
heat exchanger drain connection and the steam
trap. This will prevent improper draining of the
heat exchanger caused by a possible vacuum
forming when the steam is shut off.
8.Install a suitable steam pressure gauge in the 1/4"
coupler located in the top mid section of the heat
exchanger shell. This gauge will help diagnose
pressure problems should they occur. This port
may also be used for a PRV external control pipe
if a PRV is required.
WATER PIPING INSTALLATION
(Follow same plumbing for DW units)
D
A
C
E
B
C
B
1.An 18 inch minimum thermal loop should be piped into the water inlet and outlet of the FLO-RITE-TEMP
and should be located as close to the mixing valve as possible (See Fig. 3-1A). These loops will act as a
thermal check valve or heat trap to prevent the conduction of heat through the water from the unit during
inactive times.
F
A
Fig. 3-1
2.Isolation valves and hose connections added to both the inlet and outlet water supplies will allow for
Clean-In-Place equipment to be utilized.
3.Use pipe unions on both the water inlet and outlet to allow ease of water heater mixing valve removal for
maintenance and removal of the tube bundle for cleaning (See Fig. 3-1A).
4.For adjusting the unit, an isolation valve and hot water by-pass to drain should be installed close to the unit
October 31, 2002 @ 3:15 pm
3
Page 4
down stream from the thermal loops and prior to
the recirculation loop (if one is used) (See Fig.
3-1B). This allows for quick and easy setting of
the FLO-RITE-TEMP by one person. By isolating
the unit from the hot water system, flow can be
controlled to drain through the globe valve while
monitoring outlet water temperature during low
and high flow adjustments on the water heaters
mixing valve.
Minimum line sizes to drain should be as
follows: model 415 = 3/4", model 535 = 1",
model 665 = 1-1/4", model 8120 = 2". Line
sizes smaller than these will not allow sufficient
flow for making high flow settings on the mixing
valve.
5.A water temperature gauge should be installed
directly after the by-pass drain valve. This
thermometer is only used for inital temperature
adjustments of the Flo-Rite-Temp or
troubleshooting the unit. (See Fig. 3-1B)
6.If a recirculation system is used with a
FLO-RITE-TEMP, a small diverting valve must
be piped into the loop return downstream of the
recirculating pump (See Fig. 3-1C). This device is
used to divert recirculated water back to the
heater for reheating if the temperature of the
water drops too low due to no hot water demand
from the system plus piping radiation losses (See
page 9 for operation explanation). Be sure to pipe
in unions and isolation valves to facilitate diverting
valve removal required when element replacement
is needed. A throttling type valve should be
installed in a full return line size bypass around the
diverting valve in order to balance the flow to the
diverting valve. This is especially needed when
recirculating pumps are large or oversized.
7.For a recirculated system, a small constant running
pump should be piped in on the return side of the
loop (See Fig.3-1D). This pump should be sized to
move approximately 10% of the maximum rated
gpm of the FLO-RITE-TEMP in the system with
enough head to overcome the head encountered in
the loop.
NOTE: A thermometer should be installed in
the outgoing loop to monitor system temperature
(Fig. 3-1E). A thermometer may also be
installed on the loop return to monitor
temperature drop through the loop or to help
troubleshoot the diverting valve (Fig. 3-1D). The
thermometer referred to in point #4 and Fig. 3-1B
should only be used to set the FLO-RITE-TEMP
and never used to monitor system temperature.
NOTE: Expansion tanks should be used in on/
off demand applications where there is a short
duration of time from high flow to no flow of
water, i.e., a shut off time of 10 seconds or less.
(See Fig. 3-1F)
OPTIONAL SAFETY EQUIPMENT
See Fig. 3-1E for location of each option within the system. All options would be installed downstream of
the water heater in the outgoing recirculation loop, if one is present, or downstream of the hot water thermal
loop if recirculation is not used but always before the first hot water take off from the system.
Option #1 A temperature relief valve set at roughly 15-30 degrees above that of the FLO-RITE-TEMP
will help prevent any chance of overheated water reaching the faucets. (NOTE: Normally unit will fail closed
and either no water or only cold water will flow from the unit.)
Option #2 A 3-way blending valve with a set
point 10-30 degrees above that of the FLO-RITETEMP will help prevent the chance of overheated
water reaching the faucets in the event of unit failure.
Under normal operating conditions the hot water flows
straight through the blending valve from Port B to Port
A. But in the event of an overheated situation, the
blending valve will open Port C to add sufficient cold
water to maintain a constant temperature . (NOTE:
The blending valve should be sized to handle the
maximum flow of the system).
October 31, 2002 @ 3:15 pm
Temperature
Relief Valve
Option #1
4
Loop or System
Thermometer
Hot Water from
Flo-Rite-Temp
Page 5
3-Way
Thermostatic
Valve
Loop or System
Thermometer
To Flo-Rite-Temp
Cold Water Supply
Option 3A
Temperature
Switch
Hot Water from
Flo-Rite-Temp
Option 3B
Pressure Switch
Loop or System
Thermometer
To steam
shut-off valve
Option #3Option #2
Hot Water Supply From
Flo-Rite-Temp
To Steam
Shut-Off Valve
!
Cold Water Supply to
Flo-Rite-Temp
Option #3 A temperature switch installed well downstream of the Flo-Rite-Temp outlet on a non-recirculated
system or just into the outgoing recirculated system loop on a recirculated system, with a set point 15-30
degrees above that of the FLO-RITE-TEMP will help prevent the chance of overheated water reaching the
faucets in the event of system problems. This switch can be used to turn off the steam supply to the heater in
the event of overheating. The most economical way to accomplish this is with a solenoid on the PRV. A full
ported motorized valve on the steam supply line may also be used. Option 3B. Along these same lines, a
pressure switch installed in the inlet water line would shut down the supply steam on the heat exchanger in the
event of water pressure loss, preventing thermal shock and water hammer to the unit.
Option #4 (Available only when a pressure reducing station is installed on the Flo-Rite-Temp). Using the
Model GP-2000W1P system, when piped as shown in the Option 4 drawing, will provide a safe dependable
shut down of the main steam valve when the water pressure fails or drops rapidly on the Flo-Rite-Temp.
Unlike a solenoid application, which shuts the steam down when the water pressure drops below a pre-set
point, the GP-2000W1P offers another benefit that it allows the system to keep producing hot water even
when the water pressure is below the set pressure. The GP-2000W1P Combination valve essentially lets the
steam pressure modulate below the water pressure by 2 or 3 pounds, allowing a water heater to supply hot
water even when water pressure is low.
Incoming cold water is piped into the hot water heater with a sample line piped to the W-1 Pilot of
GP-2000W1P. At the same time the cold water is supplying the water heater, its pressure it is also supplying
the W-1 Pilot. When the pressure of the incoming cold water decreases, the W-1 Pilot modulates down the
supply of steam to the pressure pilot controlling the main steam valve, acting as a non-electric self-controlled
shutdown device. Ultimately, this valve eliminates the use of any electricity and gives the customer safe
control of their hot water supply when water pressure loss or fluctuating water pressure conditions exist.
October 31, 2002 @ 3:15 pm
Option #4
5
Page 6
IMPORTANT UNIT START-UP AND
SHUTDOWN PROCEDURES
Its important to remember that water
pressure must ALWAYS be greater than steam
pressure on the unit to avoid boiling the water
in the tubes of the heat exchanger. When
starting up a FLO-RITE-TEMP it is very
important that the water supply is turned on to
the unit before any steam is turned on. Once the
unit is up and running, the inlet water valve
should never be closed unless the steam is
turned off first. When shutting down a unit you
should always first shut off the steam and then
allow water to run through the unit until it has
cooled and completely condensed all remaining
steam in the heat exchanger before closing off
the supply water to the unit.
ADJUSTING PROCEDURES
All models of FLO-RITE-TEMP’s have two
settings which need to be made on initial start-up.
One setting must be made at low flow while the other
is made at high flows. IMPORTANT: Once the
low and high flow adjustments have been made,
the unit generally need not be adjusted again
unless your operating conditions change or a
different set point is desired. A significant drop
in temperature output or capacity is an
indication of a bad diaphragm or that the tube
bundle needs to be cleaned. Do not readjust the
valve unless isolation of the unit from the
system and running water to drain produces
poor temperature control. If capacity is
minimal, check the diaphragm or clean the
bundle but do not readjust the control valve.
START-UP AND ADJUSTING
PROCEDURE FOR MODEL 415
1.Before turning on the steam to the FLO-RITE-
TEMP, begin by opening the water supply valve
to the unit and checking for water leaks at the
unit or any of the associated piping.
2.If the unit is connected to a system which has a
recirculation loop and pump, be sure the pump is
turned off and the isolation valve on the leg of
piping going from the diverting valve back to the
inlet of the FLO-RITE-TEMP is closed (this is
the isolation valve downstream of port “B” of the
thermostatic diverting valve). (See Fig. 3-1)
3.Close the isolation valve on the hot water outlet of
the unit and open full and close several times the
throttling bypass valve to drain to purge all the air
from the FLO-RITE-TEMP. (See Fig. 3-1B).
This process also primes the units lower
diaphragm area with water. Failure to do this
prior to initial adjustment can result in
inaccurate settings and poor results.
4.Throttle the bypass valve to drain so that a
constant 3 gpm of flow may pass to drain.
5.Slowly open steam valve or adjust the pressure
reducing valve to allow 2 - 15 psig of steam
pressure on the unit
(CAUTION: always make sure there is water
pressure on the unit before adding steam.
Failure to do this will cause severe
hammering of the unit and possible damage).
6.Make sure that the steam trap draining the unit is
functioning properly and allow the entire unit to
come up to temperature for at least three to five
minutes while passing the 3 gpm of water flow to
drain before beginning the adjustment of the unit.
7.Locate the low and high flow adjustments on top
of the mixing valve hidden under the hex bonnet
(see Fig. 7-1). Before beginning adjustments,
check to make sure the high flow adjustment is
fully open. To do this start by pressing down on
the high flow adjustment when water pressure is
present on the unit and there is no water flow
through the unit. This should only depress about
1/8". If it pushes in further, turn the adjustment
stem counter clockwise to open. Check every
turn until there is only 1/8" travel to the high flow
stem when pushed down (Note: with water
pressure on the unit the stem should pop back up
after depressing it). If the high flow adjustment
stem will not depress at all the valve is opened too
far and you must turn the adjustment clockwise
until there is 1/8" travel downward to the stem.
8.With the unit now isolated from the hot water
system and all flow of water being directed to
drain at 3 gpm, let the temperature stabilize.
9.Monitor the outlet temperature on the gauge
located in the bypass to drain (see Fig. 3-1B).
Place an adjustable wrench on the flats of the low
flow adjustment (see Fig. 7-1).
Turning clockwise raises the discharge
temperature and counter-clockwise lowers the
discharge temperature. Make the appropriate
adjustment to achieve the desired set point. For
October 31, 2002 @ 3:15 pm
6
Page 7
example if a set point of 140 °F is desired and the
temperature reading is 155 °F, you must turn the
low flow adjustment counter-clockwise to lower
the set point temperature from 155 °F down to
140 °F.
(IMPORTANT - When making the low flow
adjustment the high flow adjustment shaft
SHOULD rotate with the low flow adjustment.
If it does not do so, you will have to turn it by
hand while making the low flow adjustment).
Allow the unit to stabilize to be sure that the unit
will remain at the desired set point. The low flow
is now adjusted and should not be readjusted.
10.To make the high flow adjustment, SLOWLY
increase the flow of water through the unit to
drain while monitoring the outlet thermometer.
When the outlet temperature has dropped by
approximately 10 °F below set point for a
Model 415E, make your high flow adjustment
while maintaining that flow.
11.Place a small screw driver or center punch
through the hole in the high flow adjustment stem
(see Fig. 7-1) and turn it in a clockwise direction.
This will start to close the valve restricting the
cooling water and cause the outlet water
temperature of the unit to rise. Continue until the
outlet temperature is back up to your required set
point.
(IMPORTANT - When making the high flow
adjustment the low flow adjustment SHOULD
NOT rotate with the high flow adjustment. If it
does, you will have to hold it stationary while
making your high flow adjustment).
12.The unit is now adjusted.
(IMPORTANT - If for any reason you must
readjust the unit, you will first have to return
the high flow adjustment back to its full up
position as stated in point # 7).
START-UP AND ADJUSTING PROCEDURE
FOR MODEL 535EP, 665SEP and 8120
High Flow Adjustment (HFT)
"
Low Flow Adjustment (LFT)
"
Top Of Mixing Valve
Fig. 7-1
Follow all the steps 1-6 as stated in the adjustment
procedures of the model 415.
7.Locate the low flow temperature adjustment
(LFT) and the high flow temperature adjustment
(HFT) on top of the mixing valve hidden under
the hex bonnet (See Fig. 7-1). Before beginning
adjustments, check to make sure the LFT is
fully closed. To do this, turn the LFT clockwise
until it stops. Also make sure the HFT is fully
open. To do this start by pressing down on the
HFT when water pressure is present on the unit
and there is no water flow through the unit. The
HFT should only depress about 1/8". If it pushes
in further, turn the HFT stem counter clockwise
to open. Check every turn until there is only 1/
8" travel to the HFT when pushed down (Note:
with water pressure on the unit the stem should
pop back up after depressing it). If the HFT
stem will not depress at all the valve is opened
too far and you must turn the adjustment
clockwise until there is 1/8" travel downward to
the stem.
October 31, 2002 @ 3:15 pm
7
Page 8
8.With the unit now isolated from the hot water
system and all flow of water being directed to
drain, slowly increase the water demand to
approximately 3/4 of the maximum capacity
according to the capacity chart on page 13.
When starting a cold system, you should take
at least 2 to 3 minutes to slowly increase to
this demand. This will allow time for the
steam piping feeding the unit to come up to
temperature, pressure and purge itself of
excess condensate.
the unit has been cleaned. Never attempt to
re-adjust the unit with a dirty tube bundle always clean tube bundle first. The unit is now
adjusted.
(IMPORTANT: If, for any reason, you
must readjust the unit, you will first have
to return the LFT adjustment to the fully
closed position as stated in step 8).
9.Place a small screwdriver or center punch
through the hole in the HFT adjustment and
slowly turn the HFT to change the
temperature to the desired set point. Close
(clockwise) the HFT to raise the outlet water
temperature. Allow adequate time for the
water temperature to stabilize. This could
take several minutes if the piping is cold and
the measurement point is far from the unit.
(IMPORTANT: When making the HFT
adjustment, the LFT adjustment
SHOULD NOT rotate with the HFT
adjustment. If it does, you will have to
hold it stationary while making your HFT
adjustment).
10.Lower the water flow rate to 3 gpm. The
LFT adjustment is currently fully closed (see
step 8). Slowly open (counterclockwise) the
LFT to lower the outlet water temperature to
the desired set point. Allow adequate time for
the temperature to stabilize.This will take
longer since the flow rate is so small.
CAUTION
When putting a heavy load on the heat
exchanger, watch the steam pressure gauge. This
pressure should not be permitted to fall below 2
psig. If it does and severe water hammer
develops, reduce the load by closing some of the
faucets or shut the system down. When steam
pressure drops under heavy load and hammering
occurs, not enough steam is getting to the unit.
This can be a result of an undersized reducing
valve, lack of boiler capacity or restrictive steam
lines. Hammering can also be caused by a loss of
water pressure where the water pressure in the
unit falls below the pressure of steam. This
condition is usually caused by improper shutdown
of the unit or someone closing the inlet water
valve with the steam pressure still on the unit.
(IMPORTANT: When making the LFT
adjustment, the HFT adjustment shaft
SHOULD rotate with the LFT
adjustment. If it does not do so, you will
have to turn it by hand while making the
LFT adjustment).
11.Recheck the outlet water temperature at 3/4
of the maximum demand it will see. Adjust if
necessary. Opening the HFT
(counterclockwise) will lower the temperature
and closing the HFT (clockwise) will raise the
temperature. Note: You may want to fine
tune the HFT adjustments during normal
operation of the unit at heavy demand. If
outlet temperature is slightly low, turn HFT
clockwise to raise it. This should only be done
during the initial service of the unit or when
October 31, 2002 @ 3:15 pm
8
Page 9
FLO-RITE-TEMP
Recirculation System Piping and Operation
Because of its relatively small size and compactness, the FLO-RITE-TEMP can easily be installed
close to the point of water use eliminating the need for
a recirculation system.
In applications where water heaters are located
in basements or utility rooms and feed an entire
building or wing a recirculation system or loop must
be utilized to assure instantaneous hot water to all
usage points.
The recirculation system is made up of several
different components designed to work together to
maintain the temperature of the water in the loop at
times of low or no flow.
Recirculation pump - This is a constant GPM
pump that runs continuously regardless of the hot
waterdemand from the loop. Its function is to
continually recirculate the water in the loop in order
to maintain the temperature during low or no flow
conditions. As a rule of thumb, the capacity of the
pump should be approximately 10 to 15 percent of the
maximum capacity of the FLO-RITE-TEMP and be
able to overcome any head found in the loop. The
recirculation pump however, may be larger than 15
percent. But when a larger pump is used, a full line
size bypass with a globe valve must be piped to divert
most of the flow around the thermostatic capsule.
Three-way Thermostatic Capsule - This
device has a set point roughly 20 degrees below the
set point of the FLO-RITE-TEMP and will maintain
the temperature in the loop between the set point of
the capsule and the set point of the FLO-RITETEMP. The capsule senses the temperature of the
recirculated water and compares it with its pre-set
temperature. If the temperature in the loop drops
below the capsule's set point because of radiation loss
from the piping and no hot water demand from the
loop, then the capsule begins to divert some of the
loop's flow to the inlet of the FLO-RITE-TEMP
(ports A to B) for reheating. This diversion will bring
the temperature of the loop back up to its required
temperature. Once the temperature in the loop is over
the capsule’s set point all flow from the recirculation
pump now goes straight through the capsule (ports A
to C) and the return water is fed back to the hot water
supply line. To regulate flow to the capsule, a
balancing/bypass line with globe valve is required.
This diverting recirculating system eliminates
the need for aquastats and any electrical wiring. It is
a self contained, self regulating system that controls
the temperature of the water in the loop during low or
no hot water demand situations. When there is a
demand for hot water the temperature of the water
introduced into the system is instantly controlled by
the FLO-RITE-TEMP feed forward mode of operation.
Recirculation
Pump
Capsule Balance
Line
Globe Valve
Loop or System
Thermometer
Unit Setting Thermometer
October 31, 2002 @ 3:15 pm
A
B
C
Bypass to drain
3-Way Thermostatic Capsule
Fig. 9-1
9
Page 10
FLO-RITE-TEMP-Accumulation System
For peak load conditions or to avoid large intermittent steam demands
The FLO-RITE-TEMP water heater accumulation system is designed to provide a specified volume
of accumulated hot water for short duration peak
loads or when steam is in short supply and a recovery
time can be tolerated. During periods of low or no
demand, the water in the accumulator tank is heated
to the set point temperature by the FLO-RITE-TEMP
water heater.
An accumulator or large storage tank is installed
in series with the FLO-RITE-TEMP water heater.
Cold water is piped to the inlet of the water heater
and into the bottom of the accumulator tank. Hot
water flows from the FLO-RITE-TEMP directly to
the accumulator tank through a pump that is controlled by an aquastat. When the pump is off the flow
goes to the accumulator via a bypass around the
pump. This would occur when there is hot water
demand and the temperature in the tank is at set
point.
When the system is started the water in the
accumulator tank is cold which causes the aquastat to
turn the pump on. Water flows out of the bottom of
the tank to the inlet of the FLO-RITE-TEMP. The
water continues this cycle until the aquastat in the
tank senses the appropriate temperature. At that time
the pump shuts off and the water is ready for use.
The globe valve on the bottom of the accumulator
tank should be adjusted at full system demand so that
a pressure differential of approximately 8 psi is read
across the FLO-RITE-TEMP.
In operation, hot water is drawn off the top of the
tank at the same time as cold water enters from the
bottom and hot water from the FLO-RITE-TEMP
enters the tank from the side. When the peak load
stops andthe aquastat senses the cooler water in
the tank, the pump starts and the heating process
begins another cycle.
A bypass line from the heater to the hot water
demand is shown and is normally kept closed. When
the accumulator tank requires maintenance this
bypass allows the tank to be isolated, with hot water
beingsupplied by the FLO-RITE-TEMP only.
Advantages of the accumulation system are:
! Accumulation tank temperatures are restored over
a period of time avoiding large intermittent steam
demands.
! Providing the FLO-RITE-TEMP's safety features
to the entire system.
! Providing accurate hot water temperature control.
! Providing a back up alternative during tank
maintenance.
! To allow accumulator tanks to be relatively small
in size because hot water demand is supplemented
by the FLO-RITE-TEMP.
October 31, 2002 @ 3:15 pm
Fig. 10-1
10
Page 11
Flo-Rite-Temp Tempered Water Systems
For Safety Shower/Eye Wash Stations
The problem which faces many companies
today is how to safely warm water to be used
effectively in a drench shower or safety shower
situation.
Storage tank units can run out of warm water
causing people to go into possible shock due to cold
water exposure or to end the shower before proper
flushing has taken place. Also, because the water in
the tank is only heated to a temperature range of 65
to 95 degrees F. there is the potential and risk of
legionella bacteria forming inside of the tank. Lastly,
tank systems are feedback systems which can cause
severe overheating of the water when thermostatic
elements fail causing personal injury.
The solution is to use the Armstrong Flo-RiteTemp tankless instantaneous feedforward water
heater in series with a self-contained fail safe thermostatic mixing valve.
How The System Works
The system, when piped as shown in the
drawing, will provide a safe, continuous and dependable source of accurately controlled warm water.
Incoming cold water is heated between 120 to
130 degrees F by the Flo-Rite-Temp. (The unit is set
to provide a constant supply of hot water at an
adjusted set point within this temperature range,
O
usually the lowest set point of 120
degrees is used).
The 120°F water can be piped to the Rada Z358
thermostatic mixing valve which will blend cold water
with the 120°F water to make the tepid water for the
safety shower/eye wash station. The Rada Z358
valve is equipped to allow cold water to the
showerhead in the event of hot water failure.
The Rada Z358 Mixing Valve (see Bulletin
ALIB-Z358-20) properly proportions the hot and cold
incoming water to obtain a preset delivery temperature to the drench shower head. Demand induced
changes are sensed and automatically compensated
for by the valve so that shower output temperature
remains constant. A recirculation system may also
be incorporated in this system and is especially
recommended in applications where shower lines are
exposed to the cold air or shower heads are a distance from the heater.
Feedforward control in the water heater eliminates the danger of thermostatic element failure and
overheating typical in storage tank feedback systems.
Because there is no storage tank, there is no danger
of legionella forming in the stored warm water. All
water is heated instantaneously on the spot, there is
no shortage of heated water or shower time limits.
Option 1: Water recirculation when heater is servicing a long run to the shower head, more than one shower
head, or piping is exposed to cold ambient temperatures
October 31, 2002 @ 3:15 pm
Fig. 11-1
11
Page 12
Single Wall and Double Wall Profile
L
g
g
g
g
g
g
g
g
Model 415 and 535 Profile Shown (665 and 8120 valve shows that connections for water inlet and outlet are on
opposite sides of the valve body).
Fig. 12-1
Table 12-1. Dimensions & Weights
DimensionsConnections
415
535
665
8120
415DW
535DW
665DW
8120DW
ABC D EFGHJ K
in mm54
in mm67- 1/2
in mm82
in mm85
in mm76- 1/8
in mm77- 3/8
in mm90- 5/8
in mm79- 7/8
1372
1715
2083
2159
1934
1965
2302
2029
4-1/2
114
5-1/4
133
5-3/4
146
5-3/4
146
4-1/2
114
5-1/4
133
5-3/4
146
5-3/4
146
7-1/2
190
8-5/8
219
10-3/8
264
11-3/4
299
7-1/2
190
8-5/8
219
10-3/8
264
11-3/4
298
7
178
9
229
10-3/8
264
12
305
7
178
9
229
10-3/8
264
12
305
4-1/2
3-1/2 893-1/2 897
114
5-9/16
4
141
102
6-5/8
4-3/4
168
121
8-5/8
6-1/8
219
156
4-1/2
3-3/8 863-3/4 9510-1/2
114
5-9/16
4
141
102
6-5/8
4-3/4
168
121
8-5/8
6
219
152
4-1/2
114
5-1/2
140
8-7/8
225
4-1/4
108
5
127
8-3/4
222
178
7-7/8
200
9-1/4
235
9-1/2
241
267
11-1/2
292
11-3/4
298
12-5/8
321
127
152
7-1/2
203
127
152
7-1/2
203
5
6
190
8
5
6
191
8
6-1/4
159
7-1/2
191
8-3/4
222
9-1/2
241
6-7/8
175
8-1/8
206
9-3/4
248
11-5/8
295
M1 23
50
7-1/2
1270
62
1575
74
1880
74
1880
75
1905
75
1905
87
2210
75
1905
12-3/8
12-3/8
1" NPT 253/4" N PT 202" NPT 50lb
190
9
1-1/2" NPT 401" NPT 252-1/2" NPT 65lb
229
11
2" NPT 501-1/4" NPT 323" NPT 80lb
280
3" NPT 802" NPT 504" 150# AN SI
314
7-1/2
1" NPT 253/4" N PT 202" NPT 50lb
190
9
1-1/2" NPT 401" NPT 252-1/2" NPT 65lb
229
11
2" NPT 501-1/4" NPT 323" NPT 80lb
280
3" NPT 802" NPT 504" 150# AN SI
314
100
100
k
k
k
lb
k
k
k
k
lb
k
Wt.Model
133
60
235
107
358
162
585
265
199
90
270
122
444
201
665
302
Table 12-2 Materials
BodyValveValve SeatsDiaphragm
(415) 303 Stainless Steel
Single WallDouble Wall
Bronze
with Teflon Inserts
(535/665/8120) Brass(665/8120) Brass
(415DW) 303 SS with
(415DW/535DW)
Teflon Inse rts
535DW/665DW/8120DW
(665DW/8120DW)
Brass
Note: ** There is an open vent to atmosphere between the tube sheets to detect tube failure.
Table 12-3. Specifications
ApplicationSteam Supply Pr essureWater Supply PressureMaximum Water Pr essure Dr op
*Units may be piped in parallel when desired capacities exceed that of a single unit.
Notes: Minimum water temperature increase is 60°F (33°C). Consult factory if less than 60°F (33°C) increase in required or a set temperature
of below 120°F (49°C) is required. See Armstrongs All Products Catalog 326 for proper pressure reducing valve selection.
The steam is not turned on to the unit.Open steam valve to the unit.
Only cold water
comes out of the
unit.
O nl y warm water
comes out of the
unit.
Extreme hot water
comes out of the
unit.
No water comes
out of the unit.
The unit hammers
an d bang s during
operation.
The water tubes in the heat exchanger are
plugged.
The differential pressure sensing diaphragm
is ruptured.
The mixing valve is not properly adjusted.Adjust the unit according to the instructions.
The steam pressure is too low.Increase s team pressure (2 - 15 psig).
Air has accumulated in the shell of the heat
exchanger.
The flow is above the rated capacity of the
unit.
The tubes in the heat exchanger are scaled.Remove the tube bundle and clean.
The mixing valve is not properly adjusted.Adjust the unit according to the instructions.
The steam pressure is too high.Decrease steam pressure (2 - 15 psig).
Recirculated water is continually diverting
through the Flo-Rite-Temp.
The steam is superheated.Pipe to saturated steam.
The mixing valve is not properly adjusted.Adjust the unit according to the instructions.
The inlet valve on the water supply is
closed.
There is no demand for hot water.Wait till demand is present then re-check.
The shell of the heat exchanger is not
properly drained.
The steam pressure has dropped or a
vacuum has formed.
The water pressure had dropped below that
of the steam pressure and steam is forming
inside of the water tubes.
TROUBLESHOOTING GUIDE
See Clean-In-Place operating instructions or remove
tube bundle and clean.
Replace the diaphragm.
Install a thermostatic air vent on the s hell.
Make sure unit is sized properly.
Check diverting valve for a stuck or failed thermal
capsule.
Open valve.
Make sure steam trap is working and properly installed.
Make sure shell is sloped to drain. Do not elevate
condensate if pressure is low.
Increase pressure and install vacuum breaker at shell
drain (Figure 1-1).
In s t all a pres s u re s witc h on wat e r in le t to s hut off
steam on a drop in water pressure.
Control Valve - All maintenance on the valve should be done by a factory trained product specialist
with the exception of replacing the pressure sensing diaphragm. To replace the diaphragm remove all nuts and
bolts from the bottom cover. After removing the bottom cover, remove the split nut from the bottom of the
valve shaft. You will need to hold the platter to prevent the assembly from spinning, or hold the stem with
large a slotted screw driver in the slot at the bottom of the stem. After removing the nuts, slide the platter off,
then the old diaphragm, being careful not to lose the brass washer above the diaphragm. To reassemble follow
the reverse order. Make sure when tightening the cover bolts that you use a criss-cross pattern.
October 31, 2002 @ 3:15 pm
DISASSEMBLY
14
Page 15
Single Wall Heat Exchanger - To remove the tube bundle for cleaning. Simply unbolt the mixing valve
from the shell and move it out of the way. The tube bundle can be pulled out from the valve end (see Table
12-1 for clearance dimensions). Once the tube bundle is out of the shell, unbolt the end cap on the floating
head end and remove to provide straight through cleaning. Reassemble in the reverse order (On the Model
665 dual stem unit when reassembling the tube bundle, make sure that the "TOP" indicator stamped on the
cover and both ends of the tube bundle line up and bundle is reinstalled in the shell with both "TOP" indicators
facing up). New gaskets will be required for this procedure. (Order heat exchanger gasket kit for model
number)
Armstrong
Pressure Reducing Valve
System Isolation
Valve
Steam In
I.B.
(If Req'd.)
GP-2000
Steam Pressure
Gauge
Safety Relief
Valve
Bypass to
Drain for
Setting
Setting
Thermometer
Heated
Water
Supply Water
NOTE: NOTE:
NOTE: Depending on capacity requirements a parallel water heater installation may also require (2) two PRVs in
Single wall installation shown - Double wall would be similar. See your Armstrong Representative forSingle wall installation shown - Double wall would be similar. See your Armstrong Representative for
Single wall installation shown - Double wall would be similar. See your Armstrong Representative for
Single wall installation shown - Double wall would be similar. See your Armstrong Representative forSingle wall installation shown - Double wall would be similar. See your Armstrong Representative for
System
Isolation
Valve
Bypass
to Drain
for Setting
Setting
Thermometer
Thermal
Loops
Thermal
Loops
Vacuum
Breaker
2-15 Psig Steam
in The Shell
Armstrong
Trap
I.B.
Thermostatic
Air Vent
2-15 Psig Steam
in The Shell
I.B.
Armstrong
Trap
Steam
Pressure
Gauge
I.B.
Armstrong
Trap
October 31, 2002 @ 3:15 pm
Fig. 15-1
15
Page 16
Clean-In-Place Operating Instructions
)
D
Temp’s — hot water capacity, temperature, or an increased
When there is a noticeable drop in the Flo-Rite-
water pressure drop across the unit — tube bundle scale
removal should be considered using the commercially
available product called RITE-Qwik*.
Tube bundle scale removal can be accomplished as
follows:
Step 1 - Shut off steam supply valve #1 to the Flo-RiteTemp.
Step 2 - While the water pressure is still ON and the steam is
OFF, run the Flo-Rite-Temp for (10) ten minutes or until the
outside of the unit is cool to the touch.
Step 3 - Shut the water inlet valve #4 OFF and water outlet
valve #5 OFF; open cleaning connection outlet #7. Connect
air hose with regulator to valve #9. Turn air on slowly to
approximately 5 psi. Increase to maximum of 25 psi. Leave
air pressure on until water stops coming out of connection
#7. Turn air (valve #9) off. Open cleaning connection inlet #8
and remove the pop-off valve or inlet pipe plug #6 from the
lower diaphragm cover of the control valve . Let the
remaining water drain by gravity from the Flo-Rite-Temp.
Step 4 - After all the water has been drained, reinstall the
pop-off valve or pipe plug #6 into the lower diaphragm cover
of the control valve.
Step 5 - With hose valve closed connect return hose A of the
Clean-in-Place to the outlet cleaning connection #7 of the
Flo-Rite-Temp.
Step 6 - With hose valve closed connect discharge hose B of
the Clean-in-Place to the inlet cleaning connection #8 of the
Flo-Rite-Temp.
Step 7 - Start pump. Open ball valve of discharge hose B of
the Clean-in-Place.
Step 8 - Slowly open the ball valve on return hose A and
watch for foaming in the tank.
Step 9 - Clean-in-Place is now circulating cleaning solution
through the Flo-Rite-Temp. Periodically check the solution
to see if it has changed color or quit fizzing. If the cleaning
solution has stopped fizzing and has not changed color, the
Flo-Rite-Temp is clean. You may save the remaining unspent
solution for your next job. If the solution quits fizzing and the
color has changed, add new cleaning solution. Continue
circulating in the same manner as above. Do not exceed a
maximum circulation time of (3) three hours.
Step 10 - Shut-off pump. Close discharge hose valve B on
Clean-in-Place. Open air (valve #9). Turn air on slowly to
approximately 5 psi. Increase as Clean-in-Place fluid returns
to tank. (Maximum air pressure 25 psi.)Step 11 - Leave air blow for approximately 3-5 minutes. This
should return most of the fluid to the tank. Close both hose
valves.
Step 12 - Disconnect return hose A from the Flo-Rite-Temp
outlet cleaning connection #7 and discharge hose B from the
inlet cleaning connection #8. Also remove the pop-off valve
or pipe plug #6 from the lower diaphragm cover of the
control valve. Let the cleaning solution drain by gravity from
the Flo-Rite-Temp.
Step 13 - Close valve #2 going into the system and open
valve #3 going to the drain.
Step 14 - Open the water outlet valve #5 then open SLOWLY
inlet water valve #4. Let the water run for (1) one minute
before installing the pop-off valve or pipe plug #6 into the
lower diaphragm cover of the control valve.
Step 15 - After the pop-off valve or pipe plug #6 is installed,
run water into the drain for (5) five minutes to flush out all of
the cleaning solution. Throttle the outlet valve #3 open and
closed to purge the air from under the diaphragm.
Step 16 - After flushing the unit, close valve #3 and open the
steam supply valve #1 SLOWLY and let the Flo-Rite-Temp
heat up.
Step 17 - Set the Flo-Rite-Temp as needed. (This step may
not be necessary).
Step 18 - Open valve #2 to the system and monitor the
system until the temperature is back to normal.
Step 19 - After use, flush the pump with water to remove the
chemical to prevent seal deterioration.
Flo-Rite-TempClean-In-Place
35"
(889 mm)
Air Vent
Return
Hose
Air
ischarge
Hose
Drain
* RITE-QWIK is a non hazardous chemical cleaner which has
been proven effective for removing deposits without
harming the FLO-RITE-TEMP internally.
Armstrong-Yoshitake, Inc.
221 Armstrong Blvd., P.O. Box 408, Three Rivers, Michigan 49093 - USA Ph: (616) 279-3600 Fax: (616) 273-8656
Bulletin No. AY-780-K 8/01 Printed in U.S.A.
Steam Traps \ Humidifiers \ Steam Coils \ Valves \ Air Vents \ Pumping Traps \ Water Heaters
www.armstrong-intl.com
47"
(1194 mm
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.