Argo AS1S22MH, ASBS28MH, AS1S28MH, AS1S36MH, ASBS36MH Installation Instructions Manual

...
Page 1
AS1S
ASBS
AS2S
ASS
AWS
ACS
ADS
ADPS
AFS
AES
REM
85464359926000 2006
W
– MULTISET System Air Conditioner –
INSTALLATION INSTRUCTIONS
R410A Models
Indoor Units
Outdoor Units
Indoor Unit Type 22 28 36 56 73 106 140
AS1S 1-Way Air Discharge AS1S22MH AS1S28MH AS1S36MH
Semi-Concealed
ASBS 1-Way Air Discharge ASBS28MH ASBS36MH ASBS56MH ASBS73MH
Semi-Concealed Slim
AS2S 2-Way Air Discharge AS2S22MH AS2S28MH AS2S36MH AS2S56MH AS2S73MH
Semi-Concealed
ASS 4-Way Air Discharge ASS22MH ASS28MH ASS36MH ASS56MH ASS73MH ASS106MH ASS140MH
Semi-Concealed
AWS Wall-Mounted AWS22MH AWS28MH AWS36MH AWS56MH AWS73MH
ACS Ceiling-Mounted ACS36MH ACS56MH ACS73MH ACS106MH ACS140MH
ADS Concealed-Duct ADS22MH ADS28MH ADS36MH ADS56MH ADS73MH ADS106MH ADS140MH
ADPS Concealed-Duct ADPS73MH ADPS106MH ADPS140MH
High Static Pressure
AFS Floor-Standing AFS22MH AFS28MH AFS36MH AFS56MH AFS73MH
AFNS Concealed-Floor- AFNS22MH AFNS28MH AFNS36MH AFNS56MH AFNS73MH
Standing
* Refrigerant R410A is used in the outdoor units.
AES Heat Pump Unit ES04MMIH, AES05MMIH, AES06MMIH
Optional Controllers
Remote Controller REM HW
Wireless Remote Controller (For ASS type) REM HLASS
Wireless Remote Controller (For AS2S, ASBS type) REM HLAS2BS
Wireless Remote Controller (For ACS type) REM HLACS
REM Wireless Remote Controller REM HL
(For AS1S, ADS, ADPS, AFS, AFNS type)
Wireless Remote Controller (For AWS type) REM HLAWS
Simplified Remote Controller REM HWSM
Remote Sensor RSM
System Controller REM HW64S
Schedule Timer REM HWT
DC Inverter R410A
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page a
Page 2
2
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an impor­tant part of your job to install or service the system so it oper­ates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
This product is intended for professional use. Permission from the power supplier is required when installing an outdoor unit that is connected to a 16 A dis­tribution network.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including fail­ure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this sys­tem. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inad­equate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm after installation that no refrigerant gas is leak­ing. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
WARNING
WARNING
CAUTION
CAUTION
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 2
Page 3
3
2. The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adja-
cent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when mechanical ventilation is installed inter­locked with a gas leakage detector in the smallest room where the density limit is exceeded, the vol­ume of the next smallest room becomes the object.
3. The minimum indoor floor space compared with the amount of refrigerant is roughly as follows (when the ceiling is 2.7 m high):
Check of Density Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air condi­tioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to pro­tect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, how­ever, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant com­pared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant acci­dentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the density may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The density is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
<
Density limit (kg/m3)
The density limit of refrigerant which is used in multi air con­ditioners is 0.3 kg/m
3
(ISO 5149).
1. If there are 2 or more refrigerating systems in a sin­gle refrigerating device, the amount of refrigerant should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
NOTE
Outdoor unit
Refrigerant tubing
Indoor unit
e.g., charged amount (10 kg)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
e.g., charged amount (15 kg)
Refrigerant tubing
Outdoor unit
Very small room
Indoor unit
Small room
Medium room
Large room
Mechanical ventilation device – Gas leak detector
40
35
30
25
20
15
10
5
0
10 20 30
Total amount of refrigerant
Min. indoor floor space
m
2
kg
Range below the density limit of 0.3 kg/m
3
(countermeasures not needed)
Range above the density limit of 0.3 kg/m
3
(countermeasures needed)
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 3
Page 4
R407C tools
Item compatible Remarks
with R410A?
Manifold gauge Yes No Types of refrigerant, refrigerating machine oil, and
pressure gauge are different.
Charge hose Yes No To resist higher pressure, material must be changed.
Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped
with a check valve. If it has no check valve, purchase and attach a vacuum pump adapter.
Leak detector Yes No Leak detectors for CFC and HCFC that
react to chlorine do not function because R410A contains no chlorine. Leak detector for HFC134a can be used for R410A.
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso oil)
to the flare nuts on the tubing to prevent refrigerant leakage. For machines that use R407C or R410A, apply synthetic oil (ether oil) to the flare nuts.
4
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause
defects of the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
Unit: mm
Material O
Copper tube
Outer diameter 6.35 9.52 12.7 15.88 19.05
Wall thickness 0.8 0.8 0.8 1.0 1.0
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seam-
less Pipes and Tubes.”
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution
joints (optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
Manifold gauge
Vacuum pump
Outlet Inlet
CAUTION
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to prevent dirt, moisture, or other foreign substances from entering. These substances can result in system malfunction.
New tool?
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 4
Page 5
5
Valve
Liquid
3-2. Use R410A exclusive cylinder only.
Single-outlet valve
(with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 5
Page 6
IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Please Read Before Starting Check of Density Limit Precautions for Installation Using New Refrigerant
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Type of Copper Tube and Insulation Material 1-4. Additional Materials Required for Installation 1-5. Tubing Size 1-6. Straight Equivalent Length of Joints 1-7. Additional Refrigerant Charge 1-8. System Limitations 1-9. Tubing Length 1-10. Check of Limit Density 1-11. Installing Distribution Joint 1-12 Optional Distribution Joint Kit 1-13. Optional Ball Valve Kit 1-14. Recommended Location of Ball Valves 1-15. Example of Tubing Size Selection and
Refrigerant Charge Amount
2. SELECTING THE INSTALLATION SITE . . . . .21
2-1. Indoor Unit 2-2. Outdoor Unit 2-3. Air Discharge Chamber for Top Discharge 2-4. Installing the Unit in Heavy Snow Areas 2-5. Precautions for Installation in Heavy Snow
Areas 2-6. Dimensions of Air-Discharge Chamber 2-7. Dimensions of Outdoor Unit with
Air-Discharge Chamber (field supply) 2-8. Dimensions of Snow Ducting 2-9. Dimensions of Outdoor Unit with
Snow-Proof Vents (field supply)
3. HOW TO INSTALL THE INDOOR UNIT . . . . . .29
1-Way Air Discharge Semi-Concealed Type
(AS1S Type) . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3-1. Suspending the Indoor Unit 3-2. Placing the Unit Inside the Ceiling 3-3. Installing the Drain Piping 3-4. Checking the Drainage
1-Way Air Discharge Semi-Concealed Slim Type
(ASBS Type) . . . . . . . . . . . . . . . . . . . . . . . . . . .34
3-5. Suspending the Indoor Unit 3-6. Placing the Unit Inside the Ceiling 3-7. Installing the Drain Piping 3-8. Checking the Drainage
2-Way Air Discharge Semi-Concealed Type
(AS2S Type) . . . . . . . . . . . . . . . . . . . . . . . . . . .39
3-9. Suspending the Indoor Unit 3-10. Placing the Unit Inside the Ceiling
3-11. Installing the Drain Piping 3-12. Checking the Drainage
4-Way Air Discharge Semi-Concealed Type
(ASS Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
3-13. Preparation for Suspending 3-14. Suspending the Indoor Unit 3-15. Placing the Unit Inside the Ceiling 3-16. Installing the Drain Piping 3-17. Checking the Drainage
Wall-Mounted Type (AWS Type) . . . . . . . . . . . .47
3-18. Removing the Rear Panel from the Unit 3-19. Selecting and Making a Hole 3-20. Installing the Rear Panel onto the Wall 3-21. Removing the Grille to Install the Indoor Unit 3-22. Preparing the Tubing 3-23. Shaping the Tubing 3-24. Installing the Drain Hose
Ceiling-Mounted Type (ACS Type) . . . . . . . . . .51
3-25. Required Minimum Space for Installation and
Service 3-26. Suspending the Indoor Unit 3-27. Duct for Fresh Air 3-28. Shaping the Tubing 3-29. Installing the Drain Piping
Concealed-Duct Type (ADS Type) . . . . . . . . . .58
3-30. Required Minimum Space for Installation and
Service 3-31. Suspending the Indoor Unit 3-32. Installing the Drain Piping 3-33. Checking the Drainage 3-34. Increasing the Fan Speed
Concealed-Duct High Static Pressure Type
(ADPS Type) . . . . . . . . . . . . . . . . . . . . . . . . . . .63
3-35. Required Minimum Space for Installation and
Service (73, 106, 140 Type) 3-36. Suspending the Indoor Unit 3-37. Installing the Drain Piping 3-38. Caution for Ducting Work
Floor-Standing Type (AFS Type)
Concealed Floor-Standing Type (AFNS Type) . . .67 3-39. Required Minimum Space for Installation and
Service 3-40. Dimensions and Part Names 3-41. Removing and Attaching the Front Panel
(Floor-Standing Type) 3-42. Installing the Refrigerant Tubing 3-43. Installing the Drain Piping 3-44. Installing the Remote Controller
4. HOW TO INSTALL THE OUTDOOR UNIT . . . .72
4-1. Installing the Outdoor Unit 4-2. Drainage Work 4-3. Routing the Tubing and Wiring
CONTENTS
Page Page
6
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 6
Page 7
7
5. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . .73
5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Wire
Diameter for Power Supply System
5-3. Wiring System Diagrams
6. HOW TO INSTALL THE REMOTE CONTROLLER
(OPTIONAL PART) . . . . . . . . . . . . . . . . . . . . . .77
6-1. When Using a Wall Box for Flush Mounting 6-2. Basic Wiring Diagram 6-3. Wiring System Diagram for Group Control 6-4. Switching the Room Temperature Sensors 6-5. Connecting to a Ventilation Fan 6-6. Wiring the Remote Controller
7. HOW TO PROCESS TUBING . . . . . . . . . . . . .82
7-1. Connecting the Refrigerant Tubing 7-2. Connecting Tubing Between Indoor and
Outdoor Units 7-3. Insulating the Refrigerant Tubing 7-4. Taping the Tubes 7-5. Finishing the Installation
8. AIR PURGING . . . . . . . . . . . . . . . . . . . . . . . . .86
Air Purging with a Vacuum Pump (for Test Run)
Preparation
9. HOW TO INSTALL THE CEILING PANEL . . . .89
1-Way Air Discharge Semi-Concealed Type
(AS1S Type) . . . . . . . . . . . . . . . . . . . . . . . . . . .89
9-1. Installing the Ceiling Panel 9-2. How to Use the Stoppers
1-Way Air Discharge Semi-Concealed Slim Type
(ASBS Type) . . . . . . . . . . . . . . . . . . . . . . . . . . .90
9-3. Installing the Ceiling Panel
2-Way Air Discharge Semi-Concealed Type
(AS2S Type) . . . . . . . . . . . . . . . . . . . . . . . . . . .92
9-4. Before Installing the Ceiling Panel 9-5. Installing the Ceiling Panel 9-6. When Removing the Ceiling Panel for Servicing
4-Way Air Discharge Semi-Concealed Type
(ASS Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
9-7. Before Installing the Ceiling Panel 9-8. Installing the Ceiling Panel 9-9. Wiring the Ceiling Panel 9-10. How to Attach the Corner & Air Intake Grille 9-11. Checking After Installation 9-12. When Removing the Ceiling Panel for Servicing 9-13. Adjusting the Auto Flap
10. TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
10-1. Preparing for Test Run 10-2. Test Run Procedure 10-3. Outdoor Unit PCB Setting
10-4. Auto Address Setting 10-5. Caution for Pump Down 10-6. Meaning of Alarm Messages
11. HOW TO INSTALL THE WIRELESS REMOTE
CONTROLLER RECEIVER . . . . . . . . . . . . . .111
REM HLASS for 4-Way Cassette (ASS Type)
. . .111 11-1. Installing the Receiver Unit 11-2. Accessories 11-3. Wiring the Receiver Unit 11-4. Precautions on Simultaneous Installation of
Wired Remote Controller and Wireless Remote Controller
11-5. How to use the Test Run Setting
REM HLACS for Ceiling Mounted (ACS Type)
. . .114 11-6. Installing the Receiver Unit 11-7. Accessories Supplied with Unit 11-8. Wiring the Receiver Unit 11-9. Precautions on Simultaneous Installation of
Wired Remote Controller and Wireless Remote Controller
11-10. Ho w to Use the Test Run Setting
REM HLAS2BS for 2-Way and High Ceiling
1-Way Type (AS2S, ASBS Type) . . . . . . . . . . .117
11-11. Installing the Display 11-12. Installing the Control Unit 11-13. Installing the Display 11-14. Installing the Control Unit 11-15. Accessories 11-16. Wiring the Receiver Unit 11-17. Precautions on Simultaneous Installation of
Wired Remote Controller and Wireless Remote Controller
11-18. How to Use the Test Run Setting
REM HL for AS1S, ADS, ADPS, AFS, AFNS Type
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
11-19. Accessories Supplied with Separate
Receiver Unit
11-20. Important Information for Installation of
1 Separate Receiver Unit 11-21. How to Install the Separate Receiver Unit 11-22. Wiring the Separate Receiver Unit
11-23. . . .Important Information for Installation of
2 Separate Receiver Units 11-24. Test Run Setting
12. SPECIAL REMARKS . . . . . . . . . . . . . . . . . . .128
DC Fan Tap Change Procedure for 4-Way
Cassete (ASS Type)
13. MARKINGS FOR DIRECTIVE
97/23/EC(PED) . . . . . . . . . . . . . . . . . . . . . . . 129
Page
Page
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 7
Page 8
8
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
See Tables 1-1 to 1-10.
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to
5. Electrical Wiring for details.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
Table Type
1-1 1-Way Air Discharge Semi-Concealed
1-2 1-Way Air Discharge Semi-Concealed Slim
1-3 2-Way Air Discharge Semi-Concealed
1-4 4-Way Air Discharge Semi-Concealed
1-5 Wall-Mounted
1-6 Ceiling-Mounted
1-7 Concealed-Duct
1-8 Concealed-Duct High Static Pressure
1-9 Floor-Standing & Concealed Floor-Standing
1-10 Outdoor Unit
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 8
Page 9
9
Table 1-1 (1-Way Air Discharge Semi-Concealed)
Table 1-2 (1-Way Air Discharge Semi-Concealed Slim)
Part Name Figure
Q’ty
Remarks
Flare insulator
2
Insulating tape
3
2
Vinyl clamp
8
Hose band
1
Packing
1
Drain insulator
1
Drain hose
1
Installation gauge
8
For gas and liquid tubes
For gas and liquid tubes
For gas and liquid tube flare nuts
For flare insulator
For securing drain hose
For drain joint
For drain joint
For measuring clearance between the unit and ceiling
Special washer
For suspension bolts
1 For securing drain hose
(Black)
(White)
(White)
Part Name Figure
Q’ty
Remarks
Full-scale installation diagram
1
Special washer
8
Flare insulator
2
Insulating tape
2
2
Vinyl clamp
8
Hose band
1
Packing
1
Drain insulator
1
Sealing putty
1
Cable
1
For determining suspension bolt pitch
For temporarily suspending indoor unit from ceiling
For gas and liquid tubes
For gas and liquid tubes
For gas and liquid tube flare nuts
For flare insulator
For secur ing drain hose
For drain joint
For drain joint
For sealing recessed por tion of po
wer supply
Drain hose
1
(Black)
For securing drain hose
Connection cable for fan motor
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 9
Page 10
10
Table 1-3 (2-Way Air Discharge Semi-Concealed)
Part Name Figure
Q’ty
Remarks
Flare insulator
2
Insulating tape
2
Vinyl clamp
8
Hose band
1
Packing
1
Drain insulator
1
For gas and liquid tubes
For gas and liquid tube flare nuts
For flare insulator and drain insulator
For securing drain hose
For drain joint
F
or drain joint
(White)
Drain hose (L = 25cm)
Special washer
For suspension bolts
For securing drain hose
1
1
4
8
1
1
For sealing recessed portion of power supply
Putty
Installation gauge (Use the packaging side pad.)
M5 × L40
(Black screw, with washer)
Gauge A (Install on tubing side.)
Gauge B (Install on opposite side of tubing.)
For fastening
installation gauges
Table 1-4 (4-Way Air Discharge Semi-Concealed)
Part Name Figure
Q’ty
Remarks
Full-scale installation diagram
1
Flare insulator
2
Insulating tape
2
Hose band
1
Packing
1
Drain insulator
1
Drain hose
1
4
For gas and liquid tubes
For securing drain hose
For drain joint
For dr
ain joint
(White)
Washer
8
For suspension bolts
Screw
Printed on container box
For gas and liquid tube flare nuts
For full-scale installation diagram
For securing drain hose
Table 1-5 (Wall-Mounted)
Part Name
Figure
Q’ty
Remarks
Plastic cover
1
Tapping screw
10
For improved tubing appearance
For fixing the rear panel
Truss-head Phillips 4 × 30 mm
Insulator
1
For insulating flare nut (73 type only)
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 10
Page 11
11
Table 1-6 (Ceiling-Mounted)
Part Name Figure
Q’ty
Remarks
Special washer
4
Drain insulator
1
Flare insulator
2 sets
Insulating tape
2
Vinyl clamp
8
Eyelet
1
Full-scale installation
diagram
1
Drain hose
1
For temporarily suspending indoor unit from ceiling
For drain hose joint
For gas and liquid tube joints
For gas and liquid flare joints
For flare and drain insulator
For pow
er supply inlet
T10
T5
T3
White (heat-resisting)
For drain hose connection
2
Hose band
L140
For main unit + PVC pipe joints
Printed on container box
Table 1-7 (Concealed-Duct)
Part Name Figure
Q’ty
Remarks
8
Flare insulator
2
Insulating tape
2
Drain insulator
1
Hose band
1
Packing
1
Drain hose
1
Sealing putty
1
Vinyl clamp
8
Booster cable*
1
For suspending indoor unit from ceiling
For gas and liquid tubes
For gas and liquid tube flare nuts
For drain hose joint
For securing drain hose
For drain joint
For sealing recessed por tion of power supply
F
or flare and drain insulators
* Booster cable is housed inside the electrical component box.
Washer
Connector for changeover to HT tap.
Use 3/8" for suspending bolts.Field supply for suspending bolts and nuts.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 11
Page 12
12
Table 1-8 (Concealed-Duct High Static Pressure)
Part Name Figure
Q’ty
Remarks
Special washer 8
Flare insulator 2
Drain socket 1
Tube connector 1
For suspending indoor unit from ceiling
For gas and liquid tubes
For drain pipe connection
For increasing size of liquid tube from ø6.35 to ø9.52 mm (only for 73 type)
Table 1-9 (Floor-Standing & Concealed Floor-Standing)
Part Name Figure
Q’ty
Remarks
Connection pipe 1
Flare insulator 2
Insulating tape 2
Insulating tape 2
Vinyl clamp
7
Insulating tape (black and long)
1
Drain insulator
1
For connecting gas tubes
For gas and liquid tubes
For gas and liquid tube flare nuts
For gas and liquid tubes
For ends of flare insulator
For drain pipe
For drai
n hose joint
(White)
(Black)
Table 1-10 (Outdoor Unit)
Figure
Q’ty
Tube Discharge Assy
1
Part name
0
1
0
1
1
Instruction manual
paper
hp = horsepower
04 Model
(4 hp)
05 Model
(5 hp)
06 Model
(6 hp)
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 12
Page 13
13
Table 1-13 Indoor Unit Tubing Connection (1, 2...
n–1
)
(mm)
ø15.88
ø9.52
Unit: mm
ø6.35
ø12.7
Gas tubing
(mm)
Liquid tubing
Indoor unit type 22 28 36 56 73 106 140
ø9.52
ø15.88
ø9.52
ø12.7
(mm)
(mm)
7.1
(2.5 hp)
7.1
(
2.5
hp)
15.5
(6 hp)
Below kW
Over kW
Total capacity after distribution
Tubing size
Gas tubing
Liquid tubing
hp = horsepower
Unit: mm
1-5. Tubing Size
Table 1-11 Main Tubing Size (LA)
ø19.05
6
Unit: mm
15.5
14.0
5
ø9.52
ø15.88
4
11.2
kW
System horsepower
Gas tubing (mm)
Liquid tubing (mm)
Table 1-12 Main Tubing Size After Distribution (LB, LC...)
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main
tubing size for the total capacity of the outdoor units.
Note: When only one indoor unit is connected to a 6-hp outdoor unit, connect ø19.05 gas tubing up to just before the indoor
unit, then use a socket or similar device (field supply) to change the tube diameter to ø15.88 and connect the gas tube to the indoor unit.
Material O
Copper tubing
Outer diameter 6.35 9.52 12.7 15.88
Wall thickness 0.8 0.8 0.8 1.0
1.0
19.05
Table 1-15 Required Copper Tubing Dimensions Unit: mm
Gas tubing size (mm)
90°
elbow
45°
elbow
U-shape tube bend (R60 100
mm)
Trap bend
12.7
0.30
0.23
0.90
2.30
15.88
0.35
0.26
1.05
2.80
19.05
0.42
0.32
1.26
3.20
Y-branch distribution joint Equivalent length conversion not needed.
Ball valve for service Equivalent length conv
ersion not needed.
1-6. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 1-14 Straight Equivalent Length of Joints
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 13
Page 14
14
1-7. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 1-16 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size Amount of refrigerant
charge/m (g/m)
ø6.35 26
ø9.52 56
Required amount of charge = (Amount of refrigerant charge per meter of each size of liquid tube × its tube length) + (...) + (...)
*Always charge accurately using a scale for weighing.
Table 1-17 Refrigerant Charge Amount at Shipment (for outdoor unit)
1-8. System Limitations
Table 1-18 System Limitations
Number of max. connectable indoor units
Outdoor units (Type)
04 05 06
6 8 9
Max. allowable indoor/outdoor capacity ratio
50 – 130%
Heat pump unit
AES04MMIH
3.5
AES05MMIH
3.5
AES06MMIH
3.5
(kg)
1-9. Tubing Length
Table 1-19 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
R410A distribution joint DDVI16 (for indoor unit)
Note: Do not use commercially available T-joints for the liquid tubing.
H2
LD
L1 L2
LCLB
LA
* Be sure to use special R410A distribution joints (DDVI: purchased separately)
for outdoor unit connections and tubing branches.
Main tube of unit
1st branch
Unit distribution tube
1
2 3
n-1
n
L3
H1
Items Marks Contents Length (m)
L1 Max. tubing length
Actual length
150
Equivalent length
175
L (L2 – L3)
Difference between max. length and min.
40
length from the No.1 distribution joint
1, 2~ n
Max. length of each distribution tube 30
1
+2+~
n–1
Total max. tubing length including length of
200
each distribution tube (only liquid tubing)
H1
When outdoor unit is installed higher than indoor unit
50
When outdoor unit is installed lower than indoor unit 40
H2 Max. difference between indoor units
15
L = Len
g
th, H = Height
Allowable tubing length
>
>
Allowable elevation differenc
e
>
>
>
>
>
>
+L1
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 14
Page 15
15
WARNING
Always check the gas den­sity limit for the room in which the unit is installed.
1-10. Check of Limit Density
When installing an air conditioner in a room, it is neces­sary to ensure that even if the refrigerant gas acciden­tally leaks out, its density does not exceed the limit level for that room.
If the density could exceed the limit level, it is neces­sary to provide an opening between the unit and the adjacent room, or to install mechanical ventilation which is interlocked with the leak detector.
(Total refrigerant charged amount: kg)
(Min. indoor volume where the indoor unit is installed: m3)
<
Limit density 0.3 (kg/m3)
The limit density of refrigerant which is used in this unit is 0.3 kg/m3(ISO 5149).
The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type, so add it to the amount that is charged in the field. (For the refriger­ant charge amount at shipment, refer to the unit’s nameplate.)
1-11. Installing Distribution Joint
(1) Refer to “HOW TO ATTACH DISTRIBUTION
JOINT” enclosed with the optional distribution joint kit (DDVI16).
(2) In order to prevent accumulation of refrigerant oil in
stopped units, if the main tubing is horizontal then each branch tubing length should be at an angle that is greater than horizontal. If the main tubing is verti­cal, provide a raised starting portion for each branch.
(3) If there are height differences between indoor units
or if branch tubing that follows a distribution joint is connected to only 1 unit, a trap or ball valve must be added to that distribution joint. (When adding the ball valve, locate it within 40 cm of the distribution joint.) (Consult with ARGO separately concerning the ball valve.)
If a trap or ball valve is not added, do not operate the system before repairs to a malfunctioning unit are completed. (The refrigerant oil sent through the tubing to the malfunctioning unit will accumulate and may damage the compressor.)
Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the follow­ing table.
40.5
54.0
20 30 40 50 60 70 80 kg
67.5
81.0
94.5
108.0
121.5
135.0
148.5
162.0
175.5
189.0
202.5
216.0
229.5
243.0
256.5
270.0
m
2
m
3
Total amount of refrigerant
Min. indoor floor area
(when the ceiling is 2.7 m high)
Min. indoor volume
Range below the density limit of
0.3 kg/m
3
(Countermeasures not needed)
Range above the density limit of
0.3 kg/m
3
(Countermeasures needed)
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
15 to 30°
B
A
B
A
Tube branching methods (horizontal use)
Arrow view
Horizontal line
View as seen from arrow
Ball valve
(BV: purchased
separately)
Main tubing
Types of vertical trap specifications
(If only 1 unit is connected, a ball valve is also needed on this side.)
Indoor unit (1)
(When not using ball valve)
(When using ball valve)
Branch tubing is directed upward.
(Each unit is connected to tubing that is either level or is directed downward.)
Main tubing
Indoor unit
More than 20 cm
Indoor unit (more than 2 units)
Horizontal
Indoor unit is directed downward
CAUTION
Pay special attention to any location, such as a basement, etc., where leaking refrigerant can accumulate, since refrig­erant gas is heavier than air.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 15
Page 16
16
DDVI16 Use: For indoor unit (Capacity after distribution joint is 22.4 kW or less.)
Table 1-21 Dimension for Connections of Each Part
Unit: mm
210 55
145
135
185
83
103
F
HG
F
F
G H
GH
J
J
J
F
F
Insulator
Insulator
Gas tube Liquid tube
Example: (F below indicates inner diameter. below indicates outer diameter.)
F
F
H
H
H
50
I
I
I
• When creating a tube of diameter G, use a tube cutter and cut between F and H. Cut at a point as close to H as possible.
Position A B C D E F G H I J
Dimension ø19.05 ø15.88 ø12.7 ø9.52 ø6.35
1-12. Optional Distribution Joint Kit
See the installation instructions packaged with the distribution joint kit for the installation procedure.
Table 1-20
Model name Cooling capacity after distribution Remarks
DDVI16 22.4 kW or less For indoor unit
1-13. Optional Ball Valve Kit
Table 1-22
1. Because the diameter of this ball valve is approximately the same as the inner diameter of the connecting cop­per tube, correction for pressure loss is not necessary.
2. Airtightness must be 3.6 MPa or more.
It is recommended that the ball valve is installed at each outdoor unit (gas tube and liquid tube), in order to prevent refrigerant from being released into the atmosphere if the outdoor unit is eventually replaced.
NOTE
Model No.
Gas tube Liquid tube
BV-RXP160AG 15.88
BV-RXP56AG 12.7
9.52
6.35
Valve connecting tube size (mm) Indoor unit where used
16.0 kW or less
5.6 kW or less
Total capacity of indoor units after the valve
A
E
D
C
Service port
30˚
Insulator
(divided in 2)
ø6.35 (1/4") ø9.52 (3/8") ø12.7 (1/2") ø15.88 (5/8")
A
BCD
E
72 76 89
108
42 42 42 51
54 54 58 68
16 16 20 22
44 44 51 56
Type with flare nut at each end
Dimensions
Size
Figure
Dimensions
Unit: mm
Note: Install the service port so that it faces the extension side.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 16
Page 17
17
Ball Valve Installation (for refrigerant R410A only)
Check the size of the ball valve set you separately purchased.
1. Installing the ball valve
(1) If the ball valve is to be installed for indoor unit
extension, or near an indoor unit, install it so that the service port faces the indoor unit side. (This facilitates indoor unit leak testing and vacu­um procedures.) Install the ball valve as close as possible to the distribution joint.
CAUTION
This ball valve is for use only in systems that utilize refrigerant R410A. The ser­vice port connection size is ø7.94. The face-to-face dis­tance between the ø12.7 or ø15.88 flare nuts is 26 mm or 29 mm, respectively. Be sure to use only the supplied flare nuts. Be careful to use the correct tools and materials.
2. Flare nut tightening
The flare nut on the service port side is fully tight­ened. Recommended tightening torque is (8~10 N·m).
If the valve is used for extension, it can be used as-is. In all other cases, use 2 monkey wrenches in combination to loosen the flare nut.
Outdoor unit
Indoor
Indoor unit
Service port
Ball valve
Outdoor
Indoor unit extension
Model name Size
BV-RXP56AG ø6.35 • ø12.7
BV-RXP160AG ø9.52 • ø15.88
Service port
Fully tightened (this side only)
Plug (this side only)
Cool with damp shopcloth or other means when heating brazed plug with torch.
Service port Tightening torque (8~10 N
m)
Valve cap Tightening torque (19~21 N
m)
These valves are flare-nut type.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 17
Page 18
18
1-14. Recommended Location of Ball Valves
Select a valve location that allows service to be easily provided for each unit or each refrigerant system.
(1) When adding ball valve for indoor unit
Outdoor unit
Distribution tube
Distribution joint
Main tube
Ball valve (for extension)
Less than 40 cm
Indoor unit for extension
Distribution tube
Main tube
Ball valve (for extension)
Indoor unit for extension
3. Opening and closing the valve
This valve is open at the time of shipment from the factory. If the valve is used for extension, be sure to close it.
4. Installing thermal insulation
The thermal insulation used for a flare-nut type valve is in the form of a bag. When the valve is used for extension, it can be used as-is. If the valve is used for any other purpose, use a box cut­ter or similar tool to cut away the part shown in the figure at right. The insulation is divided into 2 parts. After per­forming the leak test, use vinyl tape or other means to temporarily fasten the 2 parts together. Then carry out final finishing.
Valve opened
Spindle
Valve closed
Spindle
Notch
Insulator
1. Location: Install the ball valve at the distribution tube (not main tube).
2. Installation requirements
• Be sure to install the ball valve up-grade to prevent the inadvertent flow of oil.
• Install the ball valve at the shortest distance (within 40 cm) from the main tube. If the diameter of the ball valve is smaller than that of the main tube, use a reducer or the like to reduce the size of the tubing at that location.
• Select a place where it is easy to operate, using careful consideration of the location in advance.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 18
Page 19
19
1-15. Example of Tubing Size Selection and Refrigerant Charge Amount
Additional refrigerant charging
Based on the values in Tables 1-11, 1-12, 1-13 and 1-16, use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using the formula below.
= [56 × (a) + 26 × (b)] × 10
–3
(a): Liquid tubing Total length of ø9.52 (m) (b): Liquid tubing Total length of ø6.35 (m)
Charging procedure
Be sure to charge with R410A refrigerant in liquid form.
1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be in the “fully closed” position.
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.) Charge with R410A refrigerant in liquid form. With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from backing up.
After charging is completed, turn all valves to the “fully open” position.
Replace the tubing covers as they were before.
Required additional refrigerant charge (kg)
CAUTION
1. R410A additional charging absolutely must be done through liquid charging.
2. The R410A refrigerant cylinder has a gray base color, and the top part is pink.
3. The R410A refrigerant cylinder includes a siphon tube. Check that the siphon tube is present. (This is indicated on the label at the top of the cylinder.)
4. Due to differences in the refrigerant, pressure, and refrigerant oil involved in installation, it is not possible in some cases to use the same tools for R22 and for R410A.
1
3
4
2
Tightening torque for valve stem cap: 19~21 N·m
Tightening torque for valve stem cap: 28~32 N·m
Tightening torque: 34~42 N·m
Tightening torque: 68~82 N·m
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 19
Page 20
20
Checking of limit density
Density limit is determined on the basis of the size of a room using an indoor unit of minimum capacity. For instance, when an indoor unit is used in a room (floor area 7.43 m
2
× ceiling height 2.7 m = room volume
20.06 m3), the graph at right shows that the minimum room volume should be 14.1 m3(floor area 5.2 m2) for refrigerant of 4.238 kg. Accordingly, openings such as louvers are required for this room.
<Determination by calculation>
Overall refrigerant charge amount for the air conditioner: kg
(Minimum room volume for indoor unit: m3)
=
4.238 (kg) + 3.5 (kg) = 0.39 (kg/m
3
) 0.3 (kg/m3)
20.06 (m
3
)
Therefore, openings such as louvers are required for this room.
Obtain charge amount for each tubing size
Note that the charge amounts per 1 meter are different for each liquid tubing size. ø9.52 LA + LB + LC + LD : 65 m × 0.056 kg/m = 3.64 kg ø6.35 1 + 2 + 3 + 4 + 5 : 23 m × 0.026 kg/m = 0.598 kg
Total 4.238 kg
Additional refrigerant charge amount is 4.238 kg.
Be sure to check the limit density for the room in which the indoor unit is installed.
CAUTION
Example of each tubing length
Main tubing Distribution joint tubing
LA = 40 m Indoor side LB = 5 m 1 = 5 m 4 = 6 m LC = 5 m 2 = 5 m 5 = 5 m LD = 15 m 3 = 2 m
LD
L1 L2
LCLB
LA
Main tube of unit
1st branch
model 22 model 28 model 36 model 56
model 73
Unit distribution tube
1
2 3 4
5
Example:
40
35
30
25
20
15
10
5
0
108.0
94.5
81.0
67.5
54.0
40.5
27.0
13.5
0
10 20 30
Total amount of refrigerant
Min. indoor floor area
(when the ceiling is 2.7 m high)
m
2
kg
Range below the density limit of 0.3 kg/m
3
(countermeasures not needed)
Range above the density limit of 0.3 kg/m
3
(countermeasures needed)
m
3
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 20
Page 21
21
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
areas where leakage of flammable gas may be
expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room
directly. This may cause “sweating” on the air dis­charge ports, causing them to spray or drip.
locations where the remote controller will be splashed
with water or affected by dampness or humidity.
installing the remote controller behind curtains or fur-
niture.
locations where high-frequency emissions are gener-
ated.
DO:
select an appropriate position from which every cor-
ner of the room can be uniformly cooled.
select a location where the ceiling is strong enough
to support the weight of the unit.
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation differ-
ence above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 1-19.
allow room for mounting the remote controller about
1m off the floor, in an area that is not in direct sun­light nor in the flow of cool air from the indoor unit.
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 3 m (for ASBS type, greater than 3.5 m).
NOTE
Concealed-Duct Type
4-Way Semi-Concealed Type
1 m
1 m
1 m
1 m
1 m
2-Way,
Wall-Mounted Type
min.15 cm
Front View
min. 15 cm
min. 15 cm
Floor-Standing, Concealed Floor-Standing Type
min.
10 cm
min. 100 cm
min. 10 cm
min. 100 cm
Horizontal view Vertical view
Ceiling-Mounted Type
Side view
min. 25 cm
The rear of the indoor unit can be installed flush against the wall.
min. 50 cm
Air intake
Air discharge
min. 25 cm
Ceiling
Wall
NOTE
Front view
Max. 25 cm
Obstacle
Fig. 2-1
Fig. 2-2
20
cm
20
cm
100
cm
20
cm
100
cm
min. 5 cm
min. 5 cm
min. 1 m
Air intake
Air discharge
Obstacle
Ceiling
Wall
Wall
Side view
Semi-Concealed Type Semi-Concealed Slim Type
1-Way Semi-Concealed & Slim Type
Fig. 2-3
Fig. 2-5
Fig. 2-4
NOTE
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 21
Page 22
22
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 2-6)
damp, humid or uneven locations
DO:
choose a place as cool as possible.
choose a place that is well ventilated and outside
air temperature does not exceed maximum 45°C constantly.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 2-7)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
Installation space
Distance between obstructions and the unit air inlet and outlet must be as shown below.
Fig. 2-6
Fig. 2-8
Fig. 2-9
Out­door unit
Heat source
Hot air
Exhaust fan
Anchor bolts (4 pieces)
In case of multiple installations
provide a solid base (concrete block, 10 × 40 cm
beams or equal), a minimum of 15 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased ser­vice life. (Fig. 2-9)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
*4
*1
*2
*3
*1
More than 1 cm
More than 100 cm
More than 1 cm
Inlet side C
Inlet side More than 20 cm
Outlet side
(field supply)
A
B
(Ground)
Air direction chamber
(Obstruction above unit)
(Obstruction on inlet side)
CAUTION
Concerning inlet-side distance “C” (Fig. 2-7)
The minimum for distance “C” is 15 cm if there are no obstructions on the outlet side (wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance “C” is 20 cm.
If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
tions on 2 of the remaining 3 sides: *2, *3, *4.
If wall *1 is on the outlet side (Fig. 2-7), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 2-7), then the minimum distance for “A” and “B” is 2 m (Fig. 2-9). Even if there is no wall on the outlet side, a minimum of 100 cm is required.
Fig. 2-7
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 22
Page 23
23
Fig. 2-10
Fig. 2-11
Fig. 2-12
2-3. Air Discharge Chamber for Top Discharge
Be sure to install an air discharge chamber in the field when:
it is difficult to keep a space of min. 50 cm between
the air discharge outlet and an obstacle.
the air discharge outlet is facing a sidewalk and
discharged hot air may annoy passers-by. Refer to Fig. 2-10.
2-4. Installing the Unit in Heavy Snow Areas
In locations with strong wind, snow-proof ducting should be fitted and direct exposure to the wind should be avoided as much as possible.
Countermeasures against snow and wind
In regions with snow and strong wind, the following problems may occur when the outdoor unit is not pro­vided with a platform and snow-proof ducting:
a) The outdoor fan may not run and damage to the
unit may occur. b) There may be no air flow. c) The tubing may freeze and burst. d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
2-5. Precautions for Installation in Heavy Snow
Areas
(1) The platform should be higher than the max. snow
depth. (Fig. 2-11)
(2) The 2 anchoring feet of the outdoor unit should be
used for the platform, and the platform should be installed beneath the air intake side of outdoor unit.
(3) The platform foundation must be firm and the unit
must be secured with anchor bolts.
(4) In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent the unit from being blown over.
Air discharge
In regions with significant snowfall, the outdoor unit should be provided with a platform and snow-proof duct.
Without snow­proof ducting (Low platform)
With snow­proof ducting (High platform)
Outdoor
Duct
Air
Unit
Intake
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 23
Page 24
24
2-6. Dimensions of Air-Discharge Chamber Reference diagram for air-discharge chamber (field supply) For AES04/05/06MMIH
24029.5
29.5
35537317 70
Rectangular hole
Rectangular hole
Rectangular hole
Rectangular hole
300
2
1
4
3
240
35317537 70
54425 25
569
1090
997
250
250
310250
Unit: mm
1 Unit front, air discharge chamber
2 Unit left side, air discharge chamber
3 Unit light side, air discharge chamber
4 Reinforcement brackets, 4 locations
110660170
13
13
340
405
380
1015
2020
13
68
544
300
Wind
direction
Wind direction
940
18
1230
Wind direction
Wind direction
Wind direction
Wind direction
300
108997
Wind direction
Wind direction
Unit: mm
2-7. Dimensions of Outdoor Unit with Air-Discharge Chamber (field supply) For AES04/05/06MMIH
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 24
Page 25
25
More than 2000
More than 400
More than 1500
Installation with intakes facing outletsInstallation with intakes facing
intakes or outlets facing outlets
More than 400
More than 300
More than 300
More than 200
Min. 1000
Min. 200
The front and both sides must remain open.
Installation in front-rear rows
The front and top must remain open. The obstacles must be no taller than the height of the outdoor unit.
Installation in lateral rows
(2) Multiple-unit installation
The top and both sides must remain open. If there are obstacles to the front and rear of the outdoor unit, the obstacle at either the front or rear must be no taller than the height of the outdoor unit.
(1) Single-unit installation
If an air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
Required space around outdoor unit
CAUTION
CAUTION
CAUTION
Unit: mm
Unit: mm
Unit: mm
Reference for air-discharge chamber (field supply) Required space around outdoor unit For AES04/05/06MMIH
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 25
Page 26
26
444
645
233
732
388
1209
2
3
302
101
233
732
46
1209
764
1
4
150
450
500
20
338
500
41
730
778
16
95
500
Fastened by screws at 13 locations
Fastened by screws at 3 locations (also on reverse side)
Fastened by screw at 1 location (also on reverse side)
Unit anchor hole
(7 – ø 7 hole)
2-8. Dimensions of Snow Ducting Reference diagram for snow-proof vents (field supply) For AES04/05/06MMIH
Unit: mm
1 Unit top, snow-proof vent
2 Unit left side
3 Unit right side
4 Unit reverse side
5 Unit reverse side
6 Unit sides, reinforcement brackets for snow-proof vent
302
732
Wind direction
Wind direction
Wind direction
Wind direction
Wind direction
Wind direction
1230
1209
940
632
405
380 1015
2020
764
645
179
2-9. Dimensions of Outdoor Unit with Snow-Proof Vents (field supply) For AES04/05/06MMIH
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 26
Page 27
27
Unit: mm
Reference diagram for snow-proof vents – 1
Space requirements for setting – (1) AES04/05/06MMIH
Outdoor unit
MN
AES04/05/06MMIH
1000 1000
Outdoor unit
AES04/05/06MMIH
HI J
500 300 1000
Min. I Min. I
Min. M
Min. N
Min. H
Min. J
(1) Single-unit installation
(2) Multiple-unit installation (2 or more units)
Top is open:
Top is blocked by an obstacle:
[Obstacle to the front of unit]
Outdoor unit
AES04/05/06MMIH
AB DCEFG
150
150
Outdoor unit
K
L
AES04/05/06MMIH
500 150
200300 300 150 200
Min. C
Min. E
Min. F
Min. E Min. E
Min. L
Min. B
Min. A
Min. D
Min. K
Min. G
[Obstacle to the rear of unit]
(1) Single-unit installation
(3) Multiple-unit installation (2 or more units)
Top is open:
Note: In cases 2 and 3 the height of the obstacle
must be no taller than the height of the outdoor unit.
Top is blocked by an obstacle:
(2) Obstacles on both sides
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 27
Page 28
28
Reference diagram for snow-proof vents – 2
Space requirements for setting – (2) AES04/05/06MMIH
Outdoor unit
AES04/05/06MMIH
OP
1000 150
Min. 300
Min. 300
Min. 1000 Min. 200
Min. 1500 Min. 2000
0
Min. 300
Min. 1000
Min. 200
Q
Q
Min. P
Min. O
(1) Single-unit installation
(2) Obstacles on both sides
[Installation in front-rear rows]
[Obstacles to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
Dimension Q If a snow protection duct is
attached after the unit is
installed, verify that dimension Q is 500 mm or more.
Dimension Q If a snow protection duct is
attached after the unit is installed, verify that dimension Q is 500 mm or more.
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 28
Page 29
AS1S
29
3. HOW TO INSTALL THE INDOOR UNIT
1-Way Air Discharge Semi-Concealed Type
(AS1S Type)
3-1. Suspending the Indoor Unit
(1) Follow the diagrams to make the holes in the ceil-
ing. (Figs. 3-1 and 3-2)
(2) Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-3
or
Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-4.
Fig. 3-1
Fig. 3-2
Fig. 3-4
Fig. 3-3
4 – 12 × 37 oblong holes
74
74
780 (Ceiling opening dimension)
590
(Ceiling opening dimension)
652 (Suspension bolt pitch)
483
(Suspension bolt pitch)
20
20
Flared refrigerant connection outlet (gas tube)
Flared refrigerant connection outlet (liquid tube)
Power wiring outlet
Suspension lug
Drain outlet
560
268
15
15
100
115
40
287
20
60
30
65
Drain inspection port
Ceiling tiles
Ceiling support
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
WARNING
It is important that you use extreme care in supporting the indoor unit from the ceil­ing. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the unit, test the strength of each attached suspension bolt.
(3) Cut the ceiling material, if necessary.
(Figs. 3-1 and 3-2)
Unit: mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 29
Page 30
AS1S
30
Fig. 3-5
Fig. 3-6
Fig. 3-7
Fig. 3-8
177
For fresh air intake (ø125 hole) A
140
Nuts and washers
Suspension bolt
Suspension lug
Upper
Lower
Double nuts
Suspension bolts
Tubing side
Suspension bolts
20
20
74
74
37
5
Ceiling material
If the system requires fresh air to be drawn into the unit, cut and remove the insulation (both externally and inter­nally) at the location shown as in Fig. 3-5.
3-2. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts.
Tubing must be laid and connected inside the ceil­ing when suspending the unit. If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the the 4 suspension bolts as shown in Fig. 3-6. Use 1 nut and 1 washer for the upper side, and 2 nuts and 1 washer for the lower side, so that the unit will not fall off the suspension lugs.
(3) The distance between the unit and the opening of
the ceiling and the distance between the bottom surface of the ceiling and the bottom surface of the flange of the unit should follow the dimensions given in Figs. 3-7 and 3-8.
A
When making the cuts to the insulation, be careful not to damage the drain pan.
CAUTION
Unit: mm
Unit: mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 30
Page 31
AS1S
31
(4) Adjust the distance between the unit and the
opening in the ceiling to give clearances of 15 mm in the front and back directions and 70 mm in the right and left directions so that the height between the bottom surface of the flange of the unit and the bottom surface of the ceiling is 37 mm, and the air­intake side is 5 mm. To check these dimensions for positioning the unit, use the installation gauge which is taped on the unit. (Fig. 3-9)
(5) Confirm all clearances with the installation gauge
as follows:
Between each side of the unit and the opening of
the ceiling:
15 mm
70 mm
Between bottom of unit flange and ceiling material:
5 mm (2 corners)
37 mm (2 corners)
Improper clearance can lead to poor mounting of the ceiling panel, causing condensation and dripping. (Fig. 3-9)
3-3. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for
the drain and use the supplied drain hose and hose band to prevent water leaks. The PVC pipe must be purchased separately. The unit’s transparent drain port allows you to check drainage. (Fig. 3-10)
Fig. 3-9
Fig. 3-10
Fig. 3-11
37
70
5
Installation
gaug
e
15
Vinyl clamps
Drain insulator (supplied)
Drain hose
(supplied)
(not supplied)
(not supplied)
Packing (supplied)
VP-25
Align the hose band with end of the hose, and tighten so that it does not contact the bead.
Drainage check section on drain port (transparent)
Hard PVC socket VP-25
Hard PVC pipe
PVC adhesive
Bead
CAUTION
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe, then secure it with the supplied clamps. (Fig. 3-11)
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
NOTE
Do not use adhesive at the drain connection
port on the indoor unit.
Insert the drain pipe until it contacts the socket,
as shown in the figure at right, then secure it
tightly with the hose band.
Tighten the hose clamps so their locking nuts
face upward. (Fig. 3-10)
Do not use the supplied drain hose bent at a 90°
angle. (The maximum permissible bend is 45°.)
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 31
Page 32
AS1S
32
Do not install an air bleeder as this may cause
water to spray from the drain pipe outlet. (Fig. 3-12)
If it is necessary to increase the height of the
drain pipe, the section directly after the con­nection port can be raised a maximum of 50 cm. Do not raise it any higher than 50 cm, as this could result in water leaks. (Fig. 3-13)
Do not install the pipe with an upward gradient
from the connection port. This will cause the drain water to flow backward and leak when the unit is not operating. (Fig. 3-14)
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its connection to the unit. Fasten the pipe to a wall, frame, or other support as close to the unit as possible. (Fig. 3-15)
Provide insulation for any pipes that are run
indoors.
Fig. 3-12
Fig. 3-14
Fig. 3-13
Air bleeder
30 cm or less (as short as possible)
50 cm or less
Upward gradient prohibited
Fig. 3-15
Support pieces
CAUTION
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 32
Page 33
AS1S
33
3-4. Checking the Drainage
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Pour water into the drain pan about 500 cc using a
siphon pump through the air outlet grille. (Fig. 3-16)
(3) Short the check pin (CHK) on the indoor control
board and operate the drain pump. Check the water flow through the transparent drain pipe and see if there is any leakage.
(4) When the drainage check is complete, open the
check pin (CHK) and remount the insulator.
CAUTION
CAUTION
Be careful since the fan will start when you short the pin on the indoor control board.
The bottom drain port is for use only during test runs and servicing inspections. Do not connect the drain pipe to the bottom drain port.
Drain pan
Siphon pump
Fig. 3-16
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 33
Page 34
ASBS
34
Fig. 3-17
Fig. 3-18
Fig. 3-20
Fig. 3-21
1-Way Air Discharge Semi-Concealed Slim
Type (ASBS Type)
3-5. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the ceil-
ing at the spot where you want to install the indoor unit. Use a pencil to mark the drill holes. Refer to Table 3-1 and Figs. 3-17 and 3-19.
Since the diagram is made of paper, it may shrink or stretch due to high temperature or humidity. For this reason, before drilling the holes maintain the correct dimensions between the markings.
(2) Follow the diagrams to make the holes in the ceil-
ing. (Figs. 3-18 and 3-19)
Table 3-1
NOTE
Type
Length
AB
28, 36, 56 1,193 1,089
73 1,390 1,286
The distance between the bottom of the suspension bolts and the bottom surface of the ceiling should be 30 to 100 mm. (Fig. 3-24)
(3) Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-20.
or
Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-21.
WARNING
(4) Cut the ceiling material, if necessary.
(Figs. 3-18 and 3-19)
It is important that you use extreme care in sup­porting the indoor unit from the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the unit, test the strength of each attached suspension bolt.
Rear
Full-scale dia
g
ram
Front face
A (Ceiling opening dimension)
B (Suspension bolt pitch)
690(Ceiling
opening dimension)
Air discharge side
Drain hose
Refrigerant tube
(Suspension bolt pitch)
405197
40
1839
192221
52 (52)
Air-discharge side
Refrigerant tubing joint (liquid tube side)
Refrigerant tubing joint (gas tube side)
Drain connection port
157 28
Suspension lug
88 35
140
157
19815
221 4052
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
Ceiling tiles
Ceiling support
Fig. 3-19
Unit: mm
Unit: mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 34
Page 35
ASBS
35
(5) If the system requires fresh air to be drawn into
the unit, cut and remove the insulation (both exter­nally and internally) at the location shown as in Fig. 3-22.
3-6. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the sup­plied full-scale installation diagram. (Fig. 3-17)
Tubing must be laid and connected inside the ceil­ing when suspending the unit. If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the the 4 suspension bolts as shown in Fig. 3-23. Use 1 nut and 1 washer for the upper side, and 2 nuts and 1 washer for the lower side, so that the unit will not fall off the suspension lugs.
(3) The indoor unit should be suspended from the
suspension bolts (Fig. 3-23) so that the distance between the bottom of the suspension lug and the bottom surface of the ceiling is 30 to 40 mm. (Fig. 3-24) Clearance between the indoor unit and the bottom surface of the ceiling is adjustable after the ceiling panel is attached to the unit.
(4) The unit should be adjusted using water level or
as shown in Fig. 3-25 so that the drain pipe side is slanted 5 mm lower than the opposite side.
(5) After completing the adjustment of the clearance,
fasten all upper and lower suspension nuts tightly.
A
Fig. 3-22
Fig. 3-23
Fig. 3-24
Fig. 3-25
Power supply inlet
Fresh air intake knock-out hole ø125
635
125
88
88
Nuts and washers
Suspension bolt
Suspension lug
Upper
Lower
Double nuts
Full-scale installation diagram
Suspension lug
30 to 40 mm
30 to 40 mm
Drain pipe side
Poured water
Vinyl hose
0 to 5 mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 35
Page 36
ASBS
36
3-7. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for
the drain and use the supplied drain hose and hose band to prevent water leaks. The PVC pipe must be purchased separately. The unit’s transparent drain port allows you to check drainage. (Fig. 3-26a)
CAUTION
Fig. 3-26a
Fig. 3-26b
Drain hose
(supplied)
(not supplied)
(not supplied)
Packing (supplied)
VP-25
Align the hose band with end of the hose, and tighten so that it does not contact the bead.
Drainage check section on drain port (transparent)
Hard PVC socket VP-25
Hard PVC pipe
PVC adhesive
Bead
Vinyl clamps
Drain insulator (supplied)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe, then secure it with the supplied clamps. (Fig. 3-26b)
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
NOTE
Do not use adhesive at the drain connection
port on the indoor unit.
Insert the drain pipe until it contacts the sock-
et, as shown in the figure at right, then secure it tightly with the hose band.
Tighten the hose clamps so their locking nuts
face upward. (Fig. 3-26a)
Do not use the supplied drain hose bent at a 90°
angle. (The maximum permissible bend is 45°.)
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 36
Page 37
ASBS
37
Do not install an air bleeder as this may cause
water to spray from the drain pipe outlet.
(Fig. 3-27)
If it is necessary to increase the height of the drain
pipe, the pipe can be raised a maximum of 59 cm
from the bottom of the ceiling. Do not raise it any
higher than 59 cm, as this could result in water
leaks. (Fig. 3-28)
Do not install the pipe with an upward gradient from
the connection port. This will cause the drain water
to flow backward and leak when the unit is not
operating. (Fig. 3-29)
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should
not be allowed to hang unsupported from its con-
nection to the unit. Fasten the pipe to a wall, frame,
or other support as close to the unit as possible.
(Fig. 3-30)
Provide insulation for any pipes that are run
indoors.
3-8. Checking the Drainage
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Short the check pin (CHK) on the indoor control
board and operate the drain pump.
(3) Pour water into the drain pan using a siphon pump
through the air outlet grille. (Fig. 3-31) Check the water flow through the transparent drain pipe and see if there is any leakage.
CAUTION
Fig. 3-27
Fig. 3-28
Fig. 3-29
Fig. 3-30
Fig. 3-31
Air bleeder prohibited
CAUTION
Be careful since the fan will start when you short the pin on the indoor control board.
59 cm or less
30 cm or less (as short as possible)
Upward gradient
prohibited
Support pieces
Siphon pump
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 37
Page 38
ASBS
38
Fig. 3-33
Fig. 3-32
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the insulator.
Cleaning the sub drain pan
Before beginning work, make necessary preparations (e.g., prepare a bucket, wiping cloth, etc.).
(1) Unscrew the 2 screws securing the cover, and
place them on the reverse side to remove the cover.
(2) Release the screw securing the sub drain pan
support L-shape bracket, and remove the bracket while holding the sub drain pan with your hand.
(3) Drain any water and clean the sub drain pan by
tilting it downward. To remove the drain pump, remove the 4 drain pump installation screws, the drain hose, and the wiring.
Removing the side panel
(1) Push the tab on both sides of the side panel
inward (a) to disengage the tab (first stage) and move the panel horizontally (b).
(2) Push the area in the vicinity of the tab (second
stage) inward while holding both sides of the side panel to remove the side panel.
Drain pump installation screw
Drain pump
Drain hose
Sub drain pan
a
b
Tab (first stage)
Tab of both sides
Side panel
Tab (second stage)
CAUTION
Use 4 ××8 tapping screws to fasten cover drainage. If the screws used are longer than 8 mm, it may make a hole in the drain pan and cause leakage.
CAUTION
Continuing to work without holding the sub drain pan causes accumulated water in the sub drain pan to leak out.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 38
Page 39
AS2S
39
Fig. 3-34
Fig. 3-35
Fig. 3-36
Suspension bolt pitch B
Ceiling opening dimension A
Suspension bolt pitch
Ceiling opening dimension
Center of panel and ceiling opening
30
40
70
20 600
530
640
C
ED
Drain outlet
Refrigerant connection outlet (gas tube)
Refrigerant connection outlet (liquid tube)
Outlet for power cord, inter-unit wiring & optional cord
3508
115195
220
29060 – 65
110
600
7030
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
2-Way Air Discharge Semi-Concealed Type
(AS2S Type)
3-9. Suspending the Indoor Unit
(1) Follow the diagrams to make the holes in the ceil-
ing.
Table 3-2
(2) Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-36
or
Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-37.
WARNING
It is important that you use extreme care in supporting the indoor unit from the ceil­ing. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the unit, test the strength of each attached suspension bolt.
(3) Cut the ceiling material, if necessary. (Refer to
Figs. 3-34 and 3-35, and Table 3-2.)
ABCDE
22, 28, 36, 56 1,020 920 840 400 440
73 1,320 1,220 1,140 550 590
Fig. 3-37
Ceiling tiles
Ceiling support
Adjust so that the distance between the indoor unit and the ceiling bottom is 60 to 65 mm.
Unit: mm
Unit: mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 39
Page 40
AS2S
40
Fig. 3-38
Fig. 3-39
Fig. 3-40
Fig. 3-41
(5) If the system requires fresh air to be drawn into
the unit, cut and remove the insulation (both exter­nally and internally) at the location shown as in Fig. 3-38.
3-10. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts.
Tubing must be laid and connected inside the ceil­ing when suspending the unit. If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the the 4 suspension bolts as shown in Fig. 3-40. Use 1 nut and 1 washer for the upper side, and 2 nuts and 1 washer for the lower side, so that the unit will not fall off the suspension lugs.
(3) The distance between the unit and the opening in
the ceiling and the distance between the bottom surface of the ceiling and the bottom surface of the flange of the unit should follow the dimensions given in Figs. 3-39. Use the supplied installation gauge to check.
3-11. Installing the Drain Piping
(1) Prepare a standard hard PVC pipe (O.D. 32 mm)
for the drain and use the supplied drain hose and hose band to prevent water leaks. The PVC pipe must be purchased separately.
When doing this, leave a gap between the drain socket and the PVC pipe to allow the drainage to be checked. The unit’s transparent drain port allows you to check the drainage. (Fig. 3-41)
A
When making the cuts to the insulation, be careful not to damage the drain pan.
CAUTION
CAUTION
60
Nuts and washers
Suspension bolt
Suspension lug
Upper
Lower
Double nuts
Drain hose (supplied)
(not supplied)
(not supplied)
Packing (supplied)
VP-25
Align the hose band with end of the hose, and tighten so that it does not contact the bead.
Drainage check section on drain port (transparent)
Hard PVC socket VP-25
Hard PVC pipe
PVC adhesive
Bead
A
ø150
ø162
ø138
Do not use adhesive at the drain connection port
on the indoor unit.
Insert the drain pipe until it contacts the socket,
as shown in the figure at right, then secure it
tightly with the hose band.
Tighten the hose clamps so their locking nuts
face upward. (Fig. 3-41)
Do not use the supplied drain hose bent at a 90°
angle. (The maximum permissible bend is 45°.)
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 40
Page 41
AS2S
41
Do not install an air bleeder as this may cause
water to spray from the drain pipe outlet.
(Fig. 3-43)
If it is necessary to increase the height of the
drain pipe, the section directly after the con-
nection port can be raised a maximum of 50
cm. Do not raise it any higher than 50 cm, as
this could result in water leaks. (Fig. 3-44)
Do not install the pipe with an upward gradient
from the connection port. This will cause the
drain water to flow backward and leak when the
unit is not operating. (Fig. 3-45)
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe
should not be allowed to hang unsupported
from its connection to the unit. Fasten the pipe
to a wall, frame, or other support as close to
the unit as possible. (Fig. 3-46)
Provide insulation for any pipes that are
installed indoors.
Fig. 3-43
Fig. 3-45
Fig. 3-44
Air bleeder prohibited
30 cm or less (as short as possible)
50 cm or less
Upward gradient prohibited
Fig. 3-46
Support pieces
CAUTION
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe, then secure it with the supplied clamps. (Fig. 3-42)
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
NOTE
Fig. 3-42
Vinyl clamps
Drain insulator (supplied)
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 41
Page 42
AS2S
42
3-12. Checking the Drainage
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Remove the tube cover and through the opening,
slowly pour about 1,200 cc of water into the drain pan to check the drainage.
(3) Short the check pin (CHK) on the indoor control
board and operate the drain pump. Check the water flow through the transparent drain port and see if there is any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the tube cover. (Fig. 3-47)
CAUTION
CAUTION
Be careful since the fan will start when you short the pin on the indoor control board.
To mount the tube cover, use 4 ××8 tapping screws. (Fig. 3-47) Do not use long screws as they may puncture the drain pan and cause water leakage.
Water for checking drainage
(Approx. 1,200 cc)
Drainage check section
(transparent drain port)
Inspection cover
Fig. 3-47
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 42
Page 43
ASS
43
4-Way Air Discharge Semi-Concealed Type
(ASS Type)
3-13. Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to check that the unit is level.
3-14. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs. 3­48 and 3-49), by attaching them to the ceiling sup­port structure, or by any other method that ensures that the unit will be securely and safely suspended.
(2) Follow Fig. 3-49 and Table 3-3 to make the holes
in the ceiling.
Table 3-3
Unit: mm
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The diagram and table (Fig. 3-50 and Table 3-4) show the relationship between the positions of the sus­pension fitting, unit, and panel.
Table 3-4
Unit: mm
Fig. 3-48
Fig. 3-49
Fig. 3-50
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
Type
A
B
C
D
788
723
885
885
Length
28, 36, 56, 73, 106, 140
A
B
C
D
113
173
173
210
210
256
106, 140
E
88
88319
113
Type
Length
28, 36, 56, 73
D (ceiling opening dimension)
C (ceiling opening dimension)
A (suspension bolt pitch)
B (suspension bolt pitch)
E
A
B
C
D
35
Suspension lug
Refrigerant tubing joint (liquid side)
Refrigerant tubing joint (gas side)
(VP25)
Drain outlet
(other side)
Note: For DC Fan Tap Change Procedure for 4-Way
Cassette, see page 128.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 43
Page 44
ASS
44
Fig. 3-51
Fig. 3-52
3-15. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the sup­plied full-scale installation diagram. (Fig. 3-51)
Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring into position for connection to the unit before placing the unit inside the ceiling.
(2) The length of suspension bolts must be appropri-
ate for a distance between the bottom of the bolt and the bottom of the unit of more than 15 mm as shown in Fig. 3-51.
(3) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts as shown in Fig. 3-52. Use 1 nut and 1 washer for the upper side, and 2 nuts and 1 washer for the lower side, so that the unit will not fall off the suspension lugs.
(4) Adjust so that the distance between the unit and
the ceiling bottom is 12 to 17 mm. Tighten the nuts on the upper side and lower side of the suspen­sion lug.
(5) Remove the protective polyethylene used to pro-
tect the fan parts during transport.
Full-scale installation diagram (printed on top of container box)
Supplied bolt
Over 15 mm
12 – 17 mm
12 – 17 (mm)
Suspension bolt
Suspension lug
Nuts and washers (use for upper and lower)
Notch
Double nut
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 44
Page 45
ASS
45
3-16. Installing the Drain Piping
(1) Prepare a standard hard PVC pipe (O.D. 32 mm)
for the drain and use the supplied drain hose and hose band to prevent water leaks. The PVC pipe must be purchased separately. The unit’s transparent drain port allows you to check drainage. (Fig. 3-53)
Insert the drain pipe until it contacts the socket,
as shown in Fig. 3-53, then secure it tightly with
the hose band.
Do not use adhesive when connecting the sup-
plied hose.
Reasons: 1. It may cause water to leak from the
connection. Since the connection is slippery just after the adhesive has been applied, the pipe easily slips off.
2. The pipe cannot be removed when maintenance is needed.
Do not bend the supplied drain hose 90° or
more. The hose may slip off.
Align the hose bands with the end of the hose.
Tighten the hose band firmly. Please make sure that the bead is not covered by the hose band. (Fig. 3-53)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe. (Fig. 3-54)
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
NOTE
CAUTION
CAUTION
Tighten the hose clamps so their locking nuts face upward. (Fig. 3-53)
CAUTION
Do not install an air bleeder
as this may cause water to spray from the drain pipe outlet. (Fig. 3-55)
Fig. 3-53
Fig. 3-54
Fig. 3-55
Bead
Hose band
Supplied drain hose
Connection pipe
(drain port)
Align the hose band with the end of the pipe
(Field supply)
(Field supply)
Packing
(supplied)
VP-25
VP-25
Hard PVC socket
Hard PVC pipe
PVC adhesive
Vinyl clamps
Drain insulator (supplied)
Air bleeder prohibited
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 45
Page 46
ASS
46
Fig. 3-56
30 cm or less (as short as possible)
64 cm or less
Fig. 3-57
Upward gradient prohibited
Fig. 3-58
Fig. 3-59
Support pieces
Water (Approx. 1,200 cc)
Over 100 mm
Drain pan outlet
Drainage check
Plastic container for
water intake
CAUTION
If it is necessary to
increase the height of the drain pipe, the sec­tion directly after the connection port can be raised a maximum of 64 cm. Do not raise it any higher than 64 cm, as this could result in water leaks. (Fig. 3-56)
Do not install the pipe
with an upward gradient from the connection port. This will cause the drain water to flow back­ward and leak when the unit is not operating. (Fig. 3-57)
Do not apply force to the
piping on the unit side when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its connection to the unit. Fasten the pipe to a wall, frame, or other sup­port as close to the unit as possible. (Fig. 3-58)
Provide insulation for
any pipes that are run indoors.
3-17. Checking the Drainage
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour about 1,200 cc of water into the drain
pan to check drainage. (Fig. 3-59)
(3) Short the check pin (CHK) on the indoor control
board and operate the drain pump. Check the water flow through the transparent drain pipe and see if there is any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the tube cover.
CAUTION
Be careful since the fan will start when you short the pin on the indoor control board.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 46
Page 47
AWS
47
Wall-Mounted Type (AWS Type)
3-18. Removing the Rear Panel from the Unit
(1) Remove the set screws used to fasten the rear
panel to the indoor unit during transportation.
(2) Press up on the frame at the 2 locations shown by
the arrows in the figure at right, and remove the rear panel.
Tubing can be extended in 4 directions as shown in Fig. 3-61. Select the direction which will provide the shortest run to the outdoor unit.
3-19. Selecting and Making a Hole
(1) Remove the rear panel from the indoor unit and
place it on the wall at the location selected. Fix the rear panel and hook the unit onto it temporarily. Make sure the unit is horizontal using a carpen­ter’s level or tape measure to measure down from the ceiling.
(2) Determine which notch of the rear panel should be
used. (Fig. 3-62)
(3) Before drilling a hole, check that there are no
studs or pipes behind the determined location. The above precautions are also applicable if tub­ing goes through the wall in any other location.
(4) Using a sabre saw, key hole saw or hole-cutting
drill attachment, make a hole (dia. 80 mm) in the wall. (Fig. 3-63)
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut the PVC pipe at a slight angle 6 mm shorter than the thickness of the wall. (Fig. 3-64)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert in the wall. (Fig. 3-65)
The hole should be made at a slight downward gradi­ent to the outside.
NOTE
NOTE
Fig. 3-60
Fig. 3-61
Fig. 3-62
Fig. 3-63
Fig. 3-64Fig. 3-65
CAUTION
Avoid areas where electri­cal wiring or conduits are located.
Plastic cover
INSIDE
Wall
Slight angle
PVC pipe
OUTSIDE
Cut at slight angle
PVC pipe (locally purchased)
Indoor side
Outdoor side
Center of left rear tubing hole
Center of right rear tubing hole
Tubing hole diameter
ø80
Left tubing
Right-rear tubing (recommended)
Ri
g
ht tubin
g
Left-rear tubing
Remove the rear panel
Press
Screws used during transportation
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 47
Page 48
AWS
48
Fig. 3-66
3-20. Installing the Rear Panel onto the Wall
Confirm that the wall is strong enough to support the unit.
See either Item a) or b) below depending on the wall type.
a) If the Wall is Wooden
(1) Attach the rear panel to the wall with the 10 screws
provided. (Fig. 3-66) If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use Rawl plugs or toggle bolts to go through the holes on the panel or drill 5 mm dia. holes in the panel over the stud locations and then mount the rear panel.
(2) Check with a tape measure or carpenter’s level. This
is important so that the unit is correctly installed. (Fig. 3-67)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and vibration.
b) If the Wall is Brick, Concrete or Similar
Drill 4.8 mm dia. holes in the wall. Insert Rawl plugs for appropriate mounting screws. (Fig. 3-68)
3-21. Removing the Grille to Install the Indoor Unit
In principle, with this model wiring can be completed without removing the grille. However, if it is necessary to change the settings on the PCB, follow the procedure below.
Removing the grille
(1) Lift up on both sides of the air-intake grille to open it.
(Fig. 3-69)
(2) Remove the filter. (Fig. 3-69)
(3) Adjust the flap so that it is horizontal. (Fig. 3-70)
(4) Open the installation screw covers below the grille
(3 locations). (Fig. 3-70)
(5) Remove the screws. (Fig. 3-70)
(6) Remove the grille. (Fig. 3-71)
Attaching the grille
(1) Close the flap.
(2) Keep the grille installation tabs aligned with the top
portion of the grille, and reinstall the lower portion of the grille. Fit the installation tabs into the grooves and press the lower portion of the grille back into its original position to install it.
(3) Press on the installation tabs to completely close
the grille. Check that the grille and frame are fitted tightly together.
Fig. 3-67
Fig. 3-68
Fig. 3-69
Fig. 3-70
Fig. 3-71
4.8 mm dia. hole
Rawl plug
Intake grille
Filter
Flap
Open the
g
rille
Installation screw cover
Remove the grille
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 48
Page 49
AWS
49
3-22. Preparing the Tubing
(1) Arrangement of tubing by directions
a) Right or left tubing
The corner of the right or left frame should be cut with a hack saw or similar. (Fig. 3-72)
b) Right-rear or left-rear tubing
In this case, the corners of the frame do not need to be cut.
(2) Be sure to insulate the part of the drain hose that
is run indoors, and the refrigerant tubing. If these are not insulated, condensation may result in dripping and damage to walls and furniture. The flare nuts on the 73 type (only) are large; therefore, use the supplied insulation material.
(3) To mount the indoor unit on the rear panel.
1. When installing the indoor unit, position the indoor unit onto the installation tabs on the upper part of the rear panel. (Fig. 3-73)
2. Press on the air outlet to hold it in place, and press the lower part of the indoor unit until a “click” sound is heard and the indoor unit is securely fastened to the installation tabs on the lower side of the rear panel. (Fig. 3-74)
Raising the clamp to lift up the indoor unit will facili­tate this work. (Fig. 3-75)
To remove the indoor unit, press up on the 2 loca­tions (  marks) on the lower part of the unit frame to disconnect the installation tabs. Refer to Section 3-18. “Removing the Rear Panel from the Unit (Fig. 3-60).” Then lift up the indoor unit to remove it.
3-23. Shaping the Tubing
Right-rear tubing
(1) Shape the refrigerant tubing so that it can easily
go into the hole. (Fig. 3-76)
(2) After performing a leak test, wrap both the refriger-
ant tubing and drain hose together with insulating tape. The drain hose should be positioned below the refrigerant tubes, and should be given sufficient space so that no strong tension is applied to it.
(3) Push the wiring, refrigerant tubing and drain hose
through the hole in the wall. Adjust the indoor unit so it is securely seated on the rear panel.
Fig. 3-72
Frame
Right tubing outlet
When left and right side tubing
Fig. 3-73
Installation tabs
Installation tabs
Fig. 3-74
Press
Fig. 3-75
Clamp
Fig. 3-76
Insulating
tape
Refrigerant
tubing
Rear panel tab
Plastic cover
Indoor and outdoor unit connection wiring
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 49
Page 50
AWS
50
Fig. 3-79
Fig. 3-77
Insulation
Fig. 3-78
Insulating tape
Rear panel
Inter-unit wiring
Refrigerant tubing
Drain hose
Indoor unit
Slant
Refrigerant tubing
3-24. Installing the Drain Hose
a) The drain hose should be slanted downward to the
outside. (Fig. 3-79)
b) Never form a trap in the course of the hose.
c) If the drain hose will run in the room, insulate the
hose* so that chilled condensation will not damage furniture or floors.
* Foamed polyethylene or its equivalent is recom-
mended.
WARNING
Do not supply power to the unit or operate it until all tubing and wiring to the outdoor unit are completed.
Left or left-rear tubing
(1) Pass the tubing and drain hose into the rear of the
indoor unit. Provide sufficient length for the con­nections to be made. Next, bend the tubing with a pipe bender, and con­nect them.
(2) After performing a leak test, wrap the refrigerant
tubing and drain hose together with insulating tape, as shown in the figure at right. Then fit the tubing into the tubing storage space in the rear of the indoor unit and clamp in place.
(3) Adjust the indoor unit so that it is securely installed
onto the rear panel.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 50
Page 51
ACS
51
Ceiling-Mounted Type (ACS Type)
3-25. Required Minimum Space for Installation and Service
(1) Dimensions of suspension bolt pitch and unit
36, 56
73
106, 140
855
1125
1540
910
1180
1595
210
210
210
ABC
Length
Type
B
C
A
170
320
680
27.5
27.5
Ceiling side
(Suspension bolt pitch)
(Suspension bolt pitch)
Air intake
Air
(2) Refrigerant tubing • drain hose position
(3) Unit opening position (Refrigerant tubing • drain hose • power inlet port • remote controller wiring inlet port)
251 84 146 161
75 97 216
39
39
171
105
171
251
Gas tubing
Liquid tubing
Right side
Left side
Rear (Figure shows view from front)
Closed with rubber stopper at time of shipment.
Left drain position Right drain position
(Liquid tubing • Gas tubing)
53
70
123
110 76
216
50130
Left-side drain hose outlet port
Right-side drain hose outlet port
Top outlet port
Remote controller wiring inlet port (φ30, knock-out)
Power inlet port (φ40, knock-out)
Power inlet port (φ40, knock-out)
Knock-out
Side panel
Position of plate inside side panel
Side panel
Left-side drain hose outlet port
Rear tubing hole
84
32
32
60
171
347
125 72
85106
90
262
Remote controller wiring inlet port (φ30, rubber grommet on right side only)
Outside air intake duct connection port (φ100, knock-out)
Rear outlet port
*3
*1
*1
*2
*3
Fig. 3-80
Fig. 3-82
Fig. 3-81
*1 Use a compass saw, jig saw or simi-
lar tool and cut along the indented portion of the side panel.
*2 If the optional drain up kit is installed,
this becomes the upper tubing outlet port. For details, refer to the manual for the optional part.
*3 If the remote controller wiring inlet
port is changed to the left side or the left top side, change the location of the rubber grommet. Use aluminum tape or similar material to seal the unused inlet port on the right side.
Unit: mm
Unit: mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 51
Page 52
ACS
52
(4) Wall and ceiling side opening position
90
145
135
125
155
90
*
Figure shows view from front Figure shows view from top
φ100 wall side opening (for left-side drain hose)
φ100 wall side opening
φ100 ceiling opening
φ100 ceiling opening
Wall
Ceiling
Full-scale installation diagram
Wall
Ceiling
Fig. 3-84
Fig. 3-83
Fig. 3-85
3-26. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the ceil-
ing at the spot where you want to install the indoor unit. Use a pencil to mark the drill holes. (Fig. 3-84).
Since the diagram is made of paper, it may shrink or stretch slightly because of high temperature or humid­ity. For this reason, before drilling the holes maintain the correct dimensions between the markings.
(2) Drill holes at the 4 points indicated on the full-
scale diagram.
(3) Depending on the ceiling type:
a) Insert suspension bolts as shown in Fig. 3-85.
or
b) Use existing ceiling supports or construct a suit-
able support as shown in Fig. 3-86.
NOTE
WARNING
It is important that you use extreme care in supporting the indoor unit from the ceil­ing. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the ceiling unit, test the strength of each attached suspension bolt.
(4) Screw in the suspension bolts, allowing them to
protrude from the ceiling as shown in Figs. 3-85 and 3-86. The distance of each exposed bolt must be of equal length within 50 mm. (Fig. 3-87)
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
Fig. 3-86
Fig. 3-87
Ceiling tiles
Ceiling support
A
A
unit
Ceiling surface
Fixture
Within
50 mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 52
Page 53
ACS
53
Fig. 3-88a
Slide
Hinge
Air-intake grille
Pull out the air-intake grille pushing claws of the hinges
Screw
Latch
Fig. 3-88b
Slide toward front side
Side panel
Fig. 3-89a
Unit
Suspension bolt (field supply)
Ceiling surface
Washer (supplied)
Double nut (field supply)
Fixture
Fig. 3-89b
Unit
Suspension bolt (field supply)
Washer (supplied)
Washer (field supply)
Double nut (field supply)
Fig. 3-89c
Ceiling surface
Approx.
25 mm
Suspension bolt
Washer
(supplied)
Nut (field supply)
(5) Before suspending the indoor unit, remove the 2
or 3 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 3-88a. Then remove both side panels sliding them along the unit toward the front after removing the 2 attach­ment screws. (Fig. 3-88b)
(6) Carry out the preparation for suspending the
indoor unit. The suspension method varies depending on whether there is a suspended ceil­ing or not. (Figs. 3-89a and 3-89b)
(7) Suspend the indoor unit as follows:
a) Mount 1 washer and 2 hexagonal nuts on each
suspension bolt as shown in Fig. 3-89c.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 53
Page 54
ACS
54
Fig. 3-90
Fig. 3-91
Fig. 3-92
Indoor side
Outdoor side
Fig. 3-93
Cut at slight angle
PVC pipe (locally purchased)
INSIDE
Wall
Slight angle
PVC pipe
OUTSIDE
b) Lift the indoor unit, and place it on the washers
through the notches, in order to fix it in place. (Fig. 3-90)
c) Tighten the 2 hexagonal nuts on each suspen-
sion bolt to suspend the indoor unit as shown in Fig. 3-91.
The ceiling surface is not always level. Please confirm that the indoor unit is evenly suspended. For the installation to be correct, leave a clearance of about 10 mm between the ceiling panel and the ceiling sur­face and fill the gap with an appropriate insulation or filler material.
(8) If the tubing and wiring are to go towards the rear
of the unit, make holes in the wall. (Fig. 3-92)
(9) Measure the thickness of the wall from the inside
to the outside and cut PVC pipe at a slight angle to fit. Insert the PVC pipe in the wall. (Fig. 3-93)
NOTE
The hole should be made at a slight downward slant to the outside.
NOTE
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 54
Page 55
ACS
55
3-27. Duct for Fresh Air
There is a duct connection port (knock-out hole) at the right-rear of the top panel of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by opening the hole and con­necting the duct to the indoor unit through the con­nection port. (Fig. 3-94a)
3-28. Shaping the Tubing
The positions of the refrigerant tubing connections
are shown in the figure below. (The tubing can be routed in 3 directions.)
* When routing the tubing out through the top or right
sides, knock out the appropriate parts in the top panel and cut notches in the side panel as shown in Fig. 3-82.
* When routing the tubing out through the top, the
optional L-shape tubing kit is required.
3-29. Installing the Drain Piping
Prepare standard PVC pipe for the drain and con-
nect it to the indoor unit drain pipe with the sup­plied hose clamps to prevent water leaks.
(1) Drain hose connection
The drain hose is connected below the refrigerant
tubing.
(2) Installing the drain hose
To install the drain hose, first place 1 of the 2 hose
bands over the unit drain port and the other hose band over the hard PVC pipe (not supplied). Then connect both ends of the supplied drain hose.
On the unit drain side, grasp the hose band with
pliers and insert the drain hose all the way to the base.
Power inlet port (φ40, knock-out)
Left-side drain hose outlet port
Rear tubing hole
Remote controller wiring inlet port (φ30, rubber grommet on right side only)
Outside air intake duct connection port (φ100, knock-out)
Rear outlet port
Fig. 3-94a
Rear cover
CAUTION
Attach so that the hose
band fastener is on the side of the drain port. (Fig. 3-96)
Attach the hose bands so
that each is approximately 5 to 25 mm from the end of the supplied drain hose.
If the tubing is to be routed out together, use a box cutter or similar tool to cut out the part of the rear cover indicated by the marked area in the figure below, to match the positions of the tubes. Then draw out the tubing.
Fig. 3-94b
Fig. 3-94c
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 55
Page 56
ACS
56
140
25 25
5
5
Position to fasten hose bands
Drain hose (supplied)
Hose band (2 bands, supplied)
Unit drain pan
Unit drain port
Drain hose insulation (supplied)
Twist tie (4 ties, supplied)
Hard PVC pipe (equivalent to VP-20) (Field supply)
Fig. 3-96
Good
Min. 1/100
Not good
Fig. 3-95
If other commercially available hose bands are
used, the drain hose may become pinched or wrin­kled and there is danger of water leakage. There­fore be sure to use the supplied hose bands. When sliding the hose bands, be careful to avoid scratch­ing the drain hose.
Do not use adhesive when connecting the supplied
drain hose to the drain port (either on the main unit or the PVC pipe).
Wrap the hose with the supplied drain hose insula-
tion and use the 4 twist ties so that the hose is insulated with no gaps.
Connect the drain piping so that it slopes down-
ward from the unit to the outside. (Fig. 3-95)
Never allow traps to occur in the course of the piping.
Insulate any piping inside the room to prevent drip-
ping.
After the drain piping, pour water into the drain pan
to check that the water drains smoothly.
If the drain hose is to be raised, use the optional
drain up kit. The drain hose can be raised 60 cm above the top of the main unit. (For details, refer to the manual of the optional part.)
* If the drain hose is routed
through the left side, refer to Fig. 3-94b, and follow the procedure above to install the hose. Rettach the rub­ber stopper that was earlier removed onto the right side. The rubber stopper can be inserted easily by using a screwdriver or similar tool to press the stopper into the drain port on the main unit. Press the stop­per into the main unit drain port as far as it will go.
Screwdriver
Rubber stopper
Drain port
CAUTION
Check local electrical codes and regulations before wiring. Also, check any spec­ified instruction or limita­tions.
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 56
Page 57
ACS
57
* Insert the remote controller
wiring into the electrical component box from the inlet port as shown in the figure. This is done regardless of whether the wiring was inserted from the top, rear, or left side of the main unit.
Remote controller wiring inlet port
Power, inter-unit wiring
Power, inter-unit wiring, remote controller wiring inlet port
Clamp
How to carry out power supply wiring
(1) Wiring connection ports
The power inlet ports are located at the rear and top.
The remote controller wiring inlet ports are located at the rear and top (for use with the wired remote con­troller). For details, refer to Fig. 3-94a. For the method used to insert the wiring, refer to the figure below. (Fig. 3-97)
(2) How to carry out wiring
Open the knock-out hole on the rear or top of the
main unit. Attach the supplied rubber grommet and pull the power wiring into the main unit.
Feed the wiring into the wiring inlet port on the
electrical component box. Connect the wiring to the terminal plate and fasten in place with the supplied clamp.
Perform electrical and grounding work in accor-
dance with the package A/C power specifications, and following local electrical codes and regulations.
CAUTION
When removing the fasten­ing bracket from the cover of the electrical component box, use caution to avoid dropping the bracket.
Fig. 3-97
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 57
Page 58
ADS
58
Fig. 3-98
Fig. 3-99
Indoor unit
Inspection access 450 450
Air outlet duct flange
min. 250
min. 400
min. 650
580
A (Suspension bolt pitch)
Electrical
component box
Refrigerant tubing
min.
250
Concealed-Duct Type (ADS Type)
3-30. Required Minimum Space for Installation and
Service
This air conditioner is usually installed above the ceiling
so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below.
The minimum space for installation and service is
shown in Fig. 3-98 and Table 3-5.
It is recommended that space is provided (450 × 450
mm) for checking and servicing the electrical system.
Fig. 3-99 and Table 3-6 show the detailed dimensions
of the indoor unit.
Table 3-5
Table 3-6
Type
A (Length)
Number of duct flanges
106, 140
1,560
4
73
1,080
3
22, 28, 36, 56
780
2
Dimension
Type
22, 28, 36, 56
73
106, 140
E
F
G H
I
J
K
662
600
700 780 290 262 680 715 180 340 8 12
(200 × 3)
962
900
1,000 1,080 290 272 980 1,015 130
245
250 12 16
(180 × 5) (245 ×
1)
1,442
1,380
1,480 1,560
335
310
1,460 1,495 130
490
240 16 18
(230 × 6) (245 ×
2)
No. of holes
LM
C
D
B
A
Refrigerant tubing joint (liquid tube) Refrigerant tubing joint (gas tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 26 mm) Suspension lug Power supply outlet (2-ø30) Fresh air intake port (ø150) Flange for the flexible air outlet duct (ø200) Tube cover Electrical component box Flange for the air intake duct (Option or field supply)
9
10
9
10
11
11
(Suspension bolt pitch)
(Suspension bolt pitch)
M-ø3.3
(Hole)
4-ø12
(Hole)
(Hole)
A (O.D.)
L-ø6
I
10 10
10
5555 200
10
IJJK
B
C D(150)
40
EEEF75
65
285
70 130
25 210
310
25
175
35
90
3131
H (Duct suspension bolt pitch) G (Ceiling opening dimension)
25
100
185
58025
115
190
85
25
70 30
160
630 25
10
88
275
(Ceiling opening dimension)
260
(O.D.)
1919
Inspection access
(450 × 450)
(Field supply)
Inspection access panel
Ceiling
Unit: mm
Unit: mm
Unit: mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 58
Page 59
ADS
59
Fig. 3-100
3-31. Suspending the Indoor Unit
Depending on the ceiling type:
• Insert suspension bolts as shown in Fig. 3-100
or
• Use existing ceiling supports or construct a suit­able support as shown in Fig. 3-101.
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
Fig. 3-101
Fig. 3-102
Fig. 3-103
Ceiling tiles
Ceiling support
Suspension bolt
Suspension lug
Nuts and washers (use for upper and lower)
Double nuts
Notch
Suspension bolt
Hexagonal nut
Double nuts
WARNING
It is important that you use extreme care in supporting the indoor unit inside the ceiling. Ensure that the ceil­ing is strong enough to sup­port the weight of the unit. Before hanging the unit, test the strength of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts referring to the dimensional data on the previous page. (Fig. 3-98 and Table 3-5) Tubing must be laid and connected inside the ceil­ing when suspending the unit. If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to
protrude from the ceiling as shown in Fig. 3-100. (Cut the ceiling material, if necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts as shown in Figs. 3-102 and 3-103. Use 1 nut and 1 washer for the upper part, and 2 nuts and 1 wash­er for the lower part, so that the unit will not fall off the suspension lugs.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 59
Page 60
ADS
60
Fig. 3-104 shows an example of installation.
Air outlet duct
Air-outlet grille
Ceiling material Indoor unit
Bolt anchor
Suspension bolt
Air-intake duct
Air-intake grille
Fig. 3-104
Fig. 3-105a
Fig. 3-105b
Drain hose (supplied)
(not supplied)
(not supplied)
Packing (supplied)
VP-25
Align the hose band with end of the hose, and tighten so that it does not contact the bead.
Drainage check section on drain port (transparent)
Hard PVC socket VP-25
Hard PVC pipe
PVC adhesive
Bead
Vinyl clamps
Drain insulator (supplied)
3-32. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for
the drain and use the supplied hose band to pre­vent water leaks. The PVC pipe must be purchased separately. The transparent drain part on the unit allows you to check drainage. (Fig. 3-105a)
CAUTION
Do not use adhesive at the
drain connection port on the indoor unit.
Insert the drain pipe until it
contacts the socket, as shown in the figure at right, then secure it tightly with the hose band.
Do not use the supplied
drain hose bent at a 90° angle. (The maximum per­missible bend is 45°.)
Tighten the hose clamps so
their locking nuts face upward. (FIg. 3-105a)
(2) After connecting the drain piping securely, wrap
the supplied packing and drain pipe insulator around the pipe, then secure it with the supplied vinyl clamps. (Fig. 3-105b)
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
NOTE
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 60
Page 61
ADS
61
Fig. 3-106
Fig. 3-107
Fig. 3-108
Fig. 3-109
Fig. 3-110
Air bleeder
Prohibited
Good
30 cm or less
50 cm or less
Prohibited
Upward gradient
Support pieces
Water intake
If it is necessary to increase the height of the
drain pipe, the section directly after the con­nection port can be raised a maximum of 50 cm. Do not raise it any higher than 50 cm, as this could result in water leaks. (Fig. 3-107)
Do not install the pipe with an upward gradient from
the connection port. This will cause the drain water to flow backward and leak when the unit is not operating. (Fig. 3-108)
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its con­nection to the unit. Fasten the pipe to a wall, frame, or other support as close to the unit as possible. (Fig. 3-109)
3-33. Checking the Drainage
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Remove the tube cover and through the opening,
slowly pour about 1,200 cc of water into the drain pan to check drainage.
(3) Short the check pin (CHK) on the indoor control
board and operate the drain pump. Check the water flow through the transparent drain port and see if there is any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the insulator and drain cap onto the drain inspection port.
CAUTION
Do not install an air bleed-
er as this may cause water to spray from the drain pipe outlet. (Fig. 3-106)
CAUTION
Be careful since the fan will start when you short the pin on the indoor control board.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 61
Page 62
ADS
62
NOTE
HT : Using booster cable
H:
At shipment
5
Air Flow (m
3
/minute)
External Static Pressure
0
50
100
0
5
10
15150
10
(mmAq)
(Pa)
Limit line
Limit line
HT
H
M
L
20
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
10
15150
10
Limit line
Limit line
HT
H
L
100
M
(mmAq)
(Pa)
30 40
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
10
15
150
20
Limit line
Limit line
L
100
M
H
(mmAq)
(Pa)
HT
30
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
10
15
150
20
Limit line
HT
L
100
M
H
Limit line
(mmAq)
(Pa)
15
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
10
15150
10
Limit line
Limit line
HT
M
L
100
H
(mmAq)
(Pa)
56 Type22, 28, 36 Type
Indoor Fan Performance
73 Type 106 Type 140 Type
3-34. Increasing the Fan Speed
If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the fol­lowing procedure:
(1) Remove 4 screws on the electrical component box
and remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends)
clamped in the box.
(4) Securely connect the booster cable sockets
between the disconnected fan motor sockets in step 2 as shown in Fig. 3-111.
(5) Place the cable neatly in the box and reinstall the
cover plate.
Fig. 3-111
Fig. 3-112
Booster cable
Booster cable
Electrical component box
(At shipment) (Booster cable installed)
Fan motor socket
Fan
motor
How to read the diagram
The vertical axis is the external static pressure (Pa) while the horizontal axis represents the air flow (m
3
/minute). The characteristic curves for “HT,” “H,” “M” and “L” fan speed control are shown. The nameplate values are shown based on the “H” air flow. For the 73 type, the air flow is 18 m
3
/minute, while the external static pressure is 49 Pa at “H” position. If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed as explained above.
NOTE
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 62
Page 63
ADPS
63
Fig. 3-114
Concealed-Duct High Static Pressure Type
(ADPS Type)
3-35. Required Minimum Space for Installation
and Service (73, 106, 140 Type)
This air conditioner is usually installed above the
ceiling so that the indoor unit and ducts are not vis­ible. Only the air intake and air outlet ports are visi­ble from below.
The minimum space for installation and service is
shown in Fig. 3-113.
It is recommended that space be provided (600 ×
600 mm) for checking and servicing the electrical system.
Fig. 3-114 and Table 3-7 show the detailed dimen-
sions of the indoor unit.
Air suction side
Refrigerant tubing
Min. 600
Space for
service
Min. 130
Electrical
component
box
Inspection access (600 × 600)
(73 Type)
Min. 550
Min. 580
(106, 140 Type)
or
Suspension bolt pitch
Suspension bolt pitch
980
940
130 290
500
Min. 600
(Space for service)
Drain pan
Ceiling face
A
310
100
100
300
B
50
55
25
500 70
35 940 35
15
81
80 290
(Suspension bolt pitch)
130
23 5
60
90
20
40
55
7×100=700
4×100=400
500
980 (Suspension bolt pitch)
4-ø20 hole for suspension bolt
Drain pan
793
940
48
46
16 - ø3.2
Electrical component box
22 - ø3.2 (Hole for full circumference)
(Hole for full circumference)
(274)
100
1010
15
1010
620
55 55
100
100
Refrigerant liquid line (ø9.52 or ø6.35) Refrigerant gas line (ø19.05 or ø15.88) Power supply entry Drain connection (25A, O.D. 32 mm) Duct connection for suction Duct connection for discharge
Fig. 3-113
Unit: mm
Unit: mm
140
73, 106
A
420
450
B
395
425
C
68
98
Length
Type
Unit: mm
Table 3-7
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 63
Page 64
ADPS
64
Fig. 3-115
Fig. 3-116
Fig. 3-117
Hole-in-anchor Hole-in-plug
Concrete Inser t
Suspension bolt (M10 or 3/8") (field supply)
Ceiling tiles
Ceiling support
Suspension bolt
20~50 mm
Hexagonal nuts and washers
(2 sets)
3-36. Suspending the Indoor Unit
Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-115
or
Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-116.
WARNING
It is important that you use extreme care in supporting the indoor unit inside the ceiling. Ensure that the ceiling is strong enough to suport the weight of the unit. Before hanging the unit, test the strength of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts referring to the dimensional data on the previous page. (Fig. 3-113)
Tubing must be laid and connected inside the ceil­ing when suspending the unit. If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to
protrude from the ceiling as shown in Fig. 3-115. (Cut the ceiling material, if necessary.)
(3) Suspend and fix the indoor unit using the 2 hexag-
onal nuts (field supply) and special washers (sup­plied with the unit) as shown in Fig. 3-117.
Air-outlet grille
Air-intake grille
Fig. 3-118
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 64
Page 65
ADPS
65
Fig. 3-119a
Fig. 3-119b
Fig. 3-120
Min. 50 mm
Inspection plu
g
Min.
100 mm
Good
Min. 1/100
Not good
3-37. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for
the drain and use the supplied drain socket to pre­vent water leaks. The PVC pipe must be pur­chased separately. When doing this, apply adhesive for the PVC pipe at the connection point.
(2) If connecting a drain joint (supplied) to the thread-
ed drain port, first wrap the drain port threads with sealing tape, then connect the joint. (Fig. 3-119a)
(3) After connecting the drain pipe securely, wrap
insulator (field supply) around the pipe.
(4) Ensure the drain pipe has a downward gradient
(1/100 or more) and prepare traps as indicated in Fig. 3-119b.
(5) Also, in another part of the pipe arrangement, pre-
pare traps with an inspection plug to clean dust or debris that may cause leaking of water. (Fig. 3-120)
(6) After connecting the drain piping, slowly pour
water into the drain pan to check that the water drains smoothly.
Sealing tape
Drain joint (supplied)
Drain pan
Drain opening (25A male screw)
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 65
Page 66
ADPS
66
3-38. Caution for Ducting Work
This unit has high static pressure (applicable external
static pressure Max. 167 to 216 pa (17–22 mm Aq). In the case of small pressure resistance (for instance, a short duct), install a damper for adjust­ing air flow volume as air flow volume / air flow noise increases.
If the air conditioner is to be installed in a room
such as an office or meeting room which needs a low sound level, provide a supply and return noise absorption chamber with an acoustic liner.
Include an air filter (field supply) at the return duct.
Indoor Fan Performance
How to Read the Diagram
The vertical axis is the External Static Pressure (mmAq) while the horizontal axis represents the Air Flow (m
3
/minute). The characteristic curve for the “H,” “Med,” and “Lo” fan speed control. The nameplate values are shown based on the “H” air flow. Therefore in the case of 73 Type, the flow is 23 m3/minute, while the External Static Pressure is 19 mmAq at “H” position. If the external static pressure is too great (due to long extension of duct, for example), the air flow volume may drop too low at each air outlet.
External Static Pressure
Limit line
Limit line
H
H
M
M
L
Air Flow (m3/minute)
20
0
5
10
15
20
25
25 30
(Pa)
50
0
100
150
200
250
(mmAq)
Limit line
Limit line
H
H
M
M
L
25 30 35
Air Flow (m3/minute)
External Static Pressure
0
5
10
15
20
25
(Pa)
50
0
100
150
200
250
(mmAq)
Limit line
Limit line
H
H,M
M
L
30 35 40
Air Flow (m3/minute)
External Static Pressure
(Pa)
50
0
100
150
200
250
0
5
10
15
20
25
(mmAq)
NOTE
73 Type
106 Type 140 Type
H:
At shipment
Fig. 3-121
NOTE
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 66
Page 67
AFS
67
Floor-Standing Type (AFS Type)
Concealed Floor-Standing Type (AFNS Type)
3-39. Required Minimum Space for Installation and
Service
Install the unit where cooled or heated air from the unit can circulate well in the room. Do not put obstacles which may obstruct the air flow in front of the air intake and outlet grilles.
Ensure there is adequate space for maintenance of the electrical component box, air filter and, refrigerant tubes.
3-40. Dimensions and Part Names
Floor-Standing Type (AFS Type)
4-ø12 holes (for fastening the indoor unit to the
floor with screws)
Air filter
Refrigerant connection outlet (liquid tube)
Refrigerant connection outlet (gas tube)
Level adjusting bolt
Drain outlet (20 A)
Power cord outlet (downward, rear)
Refrigerant tubing outlet (downward, rear)
Location for mounting the remote controller (remote
controller is attachable in the room)
9
8
7
6
5
4
3
2
1
NOTE
Fig. 3-122
Fig. 3-123
min. 10 cm
min. 100 cm
min. 10 cm
min. 100 cm
Horizontal view Vertical view
36
54 54
161
26
15
57
100
177
230
615
25 R
155
107
205
260
213
76
67
156
C B A
Side panel Refrigerant tubing space for downward tubing
Air inlet
Rear-tube outlet
Air outlet
Table 3-8
Type
Length
A B C Liquid Gas
tube tube
22, 28, 36 1065 665 632 9.52 12.7
56, 73 1380 980 947 9.52 15.88
Unit: mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 67
Page 68
AFS
68
Fig. 3-124
Concealed Floor-Standing Type (AFNS Type)
4-ø12 holes (for fastening the indoor unit to the floor with screws)
Air filter
Refrigerant connection outlet (liquid tube)
Refrigerant connection outlet (gas tube)
Level adjusting bolt
Drain outlet (20A)
Flange for air-outlet duct
Table 3-9
7
6
5
4
3
2
1
Type
Length
A B C D Liquid Gas
tube tube
22, 28, 36 858 692 672 665 9.52 12.7
56, 73 1173 1007 1002 980 9.52 15.88
D
229
155
66
125
260
402
539
147
205
100
56
D
A
B C
166
374
147
30
30
70
616
46
Air outlet
(
Internal dimension)
Air inlet
Make an opening in the housing of the unit so that maintenance service can be peformed on the electric compo­nent box, air filter, refrigerant tubing connection, and drain pipe.
NOTE
Unit: mm
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 68
Page 69
AFS
69
Fig. 3-125
Fig. 3-126
B
A
Front panel
Tab
Side panel
Dew-prevention
heater
Fixture
Chain
Lead-wire connector
(2p Red)
Front panel
3-41. Removing and Attaching the Front Panel
(Floor-Standing Type)
A dew-prevention heater is secured behind the front panel. When removing or attaching the panel, take care not to damage the lead wire to the heater.
How to remove the front panel
(1) Remove the 2 screws at the lower part of the front
panel.
(2) Holding A at the upper right of the unit, push up at
B at the lower right of the panel. The right side of the front panel is removed. Then remove the left side of the front panel following the same proce­dure.
(3) Disengage the lead wire connector (2P red) for the
dew-prevention heater.
(4) Remove the chain connecting the front panel of
the unit by unhooking it from the fixture attached to the panel.
How to attach the front panel
(1) Hook the chain to the fixture of the front panel.
(2) Connect the lead wire connector.
(3) Align the slots at the lower part of the front panel
to the tabs at the lower part of the indoor unit and put the upper trim tab of the front panel on the groove of the unit. Then press down the panel.
(4) Insert the 2 screws at the lower part of the front
panel.
3-42. Installing the Refrigerant Tubing
(1) When connecting the wide tube use the supplied
tubing.
(2) Tubes can be extended in 2 directions: downward
and at rear.
For floor-standing type
When a rear tube is required, it can run through the
rear-tube outlet of the rear panel.
When a downward tube is required, refer to the
opening dimensions shown in Fig. 3-127.
NOTE
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 69
Page 70
AFS
70
Fig. 3-127
Fig. 3-128
CAUTION
Insulate both gas and liquid tubes.
To insulate tubes
(1) Wrap the flare nuts with the supplied white insulat-
ing tape.
(2) Wrap the flare nuts with the supplied flare insula-
tor.
(3) Fill the clearance between the union insulator and
flare insulator with black insulating tape. Fasten both ends of the flare insulator with the supplied vinyl clamps.
167
177
Holes for fixing the unit to the floor
Rear-tube outlet
Refrigerant tubing space for downward tubing
Insulating tape (black)
Insulating tape (white)
Flare insulator
Insulator
Flare nut
Vinyl clamps
Insulating tape
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 70
Page 71
AFS
71
Fig. 3-129
Fig. 3-130
Fig. 3-131
Fig. 3-132
Drain hose
Drain pipe (PVC)
Drain hose (supplied)
Drain insulator (supplied)
Vinyl clamp (supplied)
Hose band (supplied)
Hard PVC pipe VP20 (field supply)
Insulating tape (supplied)
Vinyl clamps
(supplied)
Drain hose insulator (field supply)
Lead wire guide
Remote controller
Screw
3-43. Installing the Drain Piping
(1) When rear-side drain piping is required bend the
drain hose attached to the indoor unit by 90°. Connect a drain pipe (field supply) to the drain hose through the rear tubing outlet in the rear panel. Use a hard PVC pipe (VP20) for the drain piping.
(2) Ensure that the drain pipe has a downward gradi-
ent of 1/100 or more and that there are no water traps.
(3) Provide insulation for the drain pipe.
(4) After the drain piping is completed, pour water
into the drain pan to check if the water drains smoothly.
(5) Remove any dust or debris in the drain pan so that
the pipe is not clogged.
3-44. Installing the Remote Controller
A remote controller (optional wired remote controller) can be mounted in the indoor unit (floor-standing type).
(1) Remove the cover of the optional wired remote
controller. (Fig. 3-131)
(2) Remove the front panel. Remove the screws and
fixture. (Fig. 3-132)
(3) Place the remote controller into the space in the
unit as shown in Fig 3-132. Assemble the lead wires of the remote controller to its rear side cen­ter and route them to the lead wire guide.
(4) Secure the fixture using the supplied screws.
CAUTION
Water leaks may occur if the drain pipes are connected inadequately.
To remove the cover from the remote controller, insert a screwdriver between the cover and the controller as shown in the figure above, and turn the screwdriver in the direction indicated by the arrow.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 71
Page 72
72
4. HOW TO INSTALL THE OUTDOOR UNIT
4-1. Installing the Outdoor Unit
Use concrete or a similar material to create the base,
and ensure good drainage.
Ordinarily, ensure a base height of 5 cm or more. If a
drain pipe is used, or for use in cold-weather regions, ensure a height of 15 cm or more at the feet on both sides of the unit. (In this case, leave clearance below the unit for the drain pipe, and to prevent freezing of drainage water in cold-weather regions.)
Refer to the Fig. 4-1 for the anchor bolt dimensions.
Be sure to anchor the feet with the anchor bolts
(M10). In addition, use anchoring washers on the top side. (Use large square 32 × 32 SUS washers with JIS nominal diameters of 10.) (Field supply)
4-2. Drainage Work
Follow the procedure below to ensure adequate drain­ing for the outdoor unit.
For the drain port dimensions, refer to the figure at
right.
Ensure a base height of 15 cm or more at the feet on
both sides of the unit.
When using a drain pipe, install the drain socket
(optional part STK-DS25T) onto the drain port. Seal the other drain port with the rubber cap supplied with the drain socket.
For details, refer to the instruction manual of the drain
socket (optional part STK-DS25T).
4-3. Routing the Tubing and Wiring
The tubing and wiring can be extended out in 4 direc-
tions: front, rear, right, and down.
The service valves are housed inside the unit. To
access them, remove the inspection panel. (To remove the inspection panel, remove the 3 screws, then slide the panel downward and pull it toward you.)
(1) If the routing direction is through the front, rear, or
right, use a nipper or similar tool to cut out the knockout holes for the inter-unit control wiring outlet, power wiring outlet, and tubing outlet from the appropriate covers A and B.
(2) If the routing direction is down, use a nipper or simi-
lar tool to cut out the lower flange from cover A.
Fig. 4-1
940
296
150
219
13 13
19
20
15 10380
405
340
1313
170 660 110
Drain port (2 locations)
Drain port
Anchor bolt (M10)
Fig. 4-2
Inter-unit control wiring outlet
Inspection panel
Cover A
Cover B
Power wiring outlet
Tubing outlet
Down
Front
Rear
Right
CAUTION
Route the tubing so that it does
not contact the compressor, panel, or other parts inside the unit. Increased noise will result if the tubing contacts these parts.
When routing the tubing, use a
tube bender to bend the tubes.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 72
Page 73
73
Control wiring
(C) Inter-unit (between outdoor and indoor units) control wiring
(D) Remote control wiring (E) Control wiring for group control
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Use shielded wiring* Use shielded wiring Use shielded wiring
Max. 1,000 m
Max. 500 m
Max. 500 m (Total)
5. ELECTRICAL WIRING
5-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and cir­cuit breaker for overcurrent protection should be provided in the exclusive line.
(3) To prevent possible hazards from insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done in accor-
dance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before begin­ning.
You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the inter-unit control
wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring
between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is dam-
aged, it must be replaced by a repair shop appointed by the manufacturer, because special purpose tools are required.
5-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit
(A) Power supply
Wire size Max. length
AES04MMIH 16 m 25 A AES05MMIH 24 m 35 A AES06MMIH 20 m 35 A
4 mm 6 mm 6 mm
2
2
2
Time delay fuse or circuit capacity
Indoor unit
Time delay fuse or
circuit capacity
(B) Power supply
2.5 mm
2
AWS Max. 150 m 10 – 16 A
ADPS Max. 60 m 10 – 16 A
AS1S, ASBS, AS2S, ASS,
ACS, ADS, AFS, AFNS
Max. 130 m 10 – 16 A
Type
NOTE
* With ring-type wire terminal.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 73
Page 74
74
5-3. Wiring System Diagram
U2
U1
3
1
2
1
2
N
L
1 2
2
1
WHT
Remote controller
BLK
2
1
U2
U1
3
1
2
1
2
U2
U1
3
1
2
1
2
U2
U1
3
1
2
1
2
2
1
WHT
Remote controller
Group control:
BLK
2
1
2
1
WHT
Remote controller
D
A
E
Indoor unit (No. n)
Indoor unit (No. 1)
Indoor unit (No. 2)
Indoor unit (No. 3)
C
B
Outdoor unit INV unit
L
Power supply
N
220–240V-1N 50Hz
Ground
Ground
L N
L N
L N
L N
BLK
2
1
Power supply 220-240V 50Hz
B
B
B
Ground
Ground
Ground
Ground
Power supply 220-240V 50Hz
Power supply 220-240V 50Hz
Power supply 220-240V 50Hz
Ground
C
Ground
D
D
C
Ground
C
Ground
NOTE
(1) Refer to Section 5-2. “Recommended Wire Length
and Wire Diameter for Power Supply System” for the explanation of “A,” “B,” “C,” “D,” and “E,” in the above diagram.
(2) The basic connection diagram of the indoor unit
shows the 7P terminal board, so the terminal boards in your equipment may differ from the dia­gram.
(3) Refrigerant Circuit (R.C.) address should be set
before turning the power on.
(4) Regarding the R.C. address setting, refer to page
101. Auto. address setting can be executed by remote controller automatically. Refer to page 102 – 106.
1(L)2(N) Power
supply
U1
Inter-unit
control wiring
U2
Remote
controller
8P terminal board
R1 R2
1 2 U1 U2 R1 R2
AS1S, ASBS, ADS,
ADPS, AFS, AFNS Type
AWS Type
1(L)2(N)
45
123 45
Power
supply
Inter-unit
control wiring
5P terminal board
1(L) 2(N) Power
supply
U1 Inter-unit
control wiring
U2
Remote
controller
R1
R2
AS2S, ASS, ACS Ty pe
7P terminal board
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 74
Page 75
75
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit
more than 1 m
more than 1 m
Branch point
16 or fewer
Indoor unit
Indoor unit Indoor unit Indoor unit
less than 1 m
Indoor unit
Outdoor unit Indoor unit Indoor unit Indoor unit
Indoor unit Indoor unit Indoor unit
Outdoor unit
Indoor unit
NO
NO
Branch point
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the
short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no con­nection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-1)
Outdoor unit Outdoor unit Outdoor unit
Prohibited
Prohibited
Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit
Fig. 5-1
Fig. 5-2
Fig. 5-3
CAUTION
(3) Do not install inter-unit control wiring such as star
branch wiring. Star branch wiring causes mis-address setting.
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 1 m are not included in the total branch number.) (Fig. 5-3)
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 75
Page 76
76
Fig. 5-4
Shielded wire
Ground
Ground
Fig. 5-5
Stranded wire
Ring pressure terminal
Strip 10 mm
Fig. 5-6
Wire
Special washer
Screw
Ring pressure terminal
Terminal plate
Screw and Special washer
Ring pressure terminal
Wire
(5) Use shielded wires for inter-unit control wiring
(c) and ground the shield on both sides, other­wise misoperation from noise may occur. (Fig. 5-4) Connect wiring as shown in Section “5-3. Wiring System Diagram.”
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, fol­low the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal plate.
How to connect wiring to the terminal
For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends. (Fig. 5-5)
(2) Using a Phillips head screwdriver, remove the ter-
minal screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure terminal.
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screw­driver. (Fig. 5-6)
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 76
Page 77
REM
77
Fig. 6-2
120
120
4
2.7
16
Diagram of outer dimensions
6. HOW TO INSTALL THE REMOTE CONTROLLER (OPTIONAL PART)
Remote controller wiring can be extended to a maxi­mum of 1,000 m.
How to install the remote controller
(Optional Controller)
CAUTION
Do not twist the control
wiring with the power wiring or run it in the same metal conduit, because this may cause malfunction.
Install the remote con-
troller away from sources of electrical noise.
Install a noise filter or
take other appropriate action if electrical noise affects the power supply circuit of the unit.
The mounting position for the remote controller should be located in an accessible place for control. Never cover the remote controller or recess it into the wall.
(1) When you open the decorative cover, you will see 2
gaps under the remote controller. Insert a coin into these gaps and pry off the back case. (Fig. 6-1)
6-1. When Using a Wall Box for Flush Mounting
If local codes allow, this remote controller can be
mounted using a conventional wall box for flush mounting.
(2) Attach the back case with the 2 small screws pro-
vided. Using a screwdriver, push open the cut-outs on the back case. These holes are for screws. Use the spacers and take care not to tighten the screws excessively. If the back case will not seat well, cut the spacers to a suitable thickness. (Fig. 6-1)
(3) Connect the remote controller wiring (3 wires) cor-
rectly to the corresponding terminals in the electri­cal component box of the indoor unit.
(4) To finish, fit the back tabs of the case into the
remote controller and mount it.
CAUTION
When wiring, do not con­nect the remote controller wires to the adjacent termi­nal block for the power wiring. Otherwise, the unit will break down.
CAUTION
Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit is completed.
Fig. 6-1
Opening for switch box
Under case (Back case)
M4 × 25 screws (2)
Remote controller
Decorative cover
Spacer
1
2
2
3
2
Remote controller switch
(with 200 mm wire)
Small screws M4 × 25
Wood screws
4
2
5
2
Spacers
Wire joints
1
Supplied parts Supplied partsNo.No.
Q’tyQ’ty
Accessories for remote controller switch
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 77
Page 78
REM
78
6-2. Basic Wiring Diagram
CAUTION
Install wiring correctly (incorrect wiring will dam­age the equipment).
Use shielded wires for remote control wiring and
ground the shield on both sides. (Fig. 6-3) Other­wise misoperation due to noise may occur.
Fig. 6-3
Fig. 6-4
Shielded wire
Ground
1
2
1
1
2
1
2
1
12
1
1
2
1
: Ground
Outdoor unit
Indoor unit
No. 8
Indoor unit
No. 3
Indoor unit
No. 2
Indoor unit
No. 1
1
Group control
Connection wiring for group control
Standard remote control
Multiple remote control
1 1
1
Inter-unit control wiring
Terminal 3P
2
2
2
2
2
2
2
2
Remote control wiring
Inter-unit wiring
Group-control wiring
(Main) (Sub)
Indoor unit 8
Indoor unit 7
Indoor unit 2
Indoor unit 1
6-3. Wiring System Diagram for Group Control
This diagram shows when several units (maximum of
8) are controlled by a remote controller (master unit). In this case, a remote controller can be connected at any indoor unit.
Wiring procedure
Wire according to the right diagram:
Each successive unit will respond at 1-second
intervals following the order of the group address when the remote controller is operated.
Group control using 2 remote controllers
It does not matter which of the 2 remote controllers you set as the main controller.
When using multiple remote controllers (up to 2 can be used), one serves as the main remote controller and the other as the sub-remote controller.
1
2
1
1
2
1
2
1
1
2
1
1
2
1
Outdoor unit
Indoor unit
No. 8
Indoor unit
No. 3
Indoor unit
No. 2
Indoor unit
No. 1
1
Remote controller
Connection wiring for group control
Inter-unit control wiring
Terminal 3P
2
2
22
2
(sub)
3P terminal base for remote control wiring
Remote controller (main)
1
Indoor unit
No. 1
: Ground (earth)
Indoor unit
No. 2
Indoor unit
No. 8
Indoor unit
No. 3
Connection wiring for group control
1
1
1
2
2
2
2
1
2
1
2
Fig. 6-5
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 78
Page 79
REM
79
Cautions on group control
Group control within the same refrigerant tub-
ing system is recommended.
[Tubing system which is NOT recommended]
<Example 1> In the MULTISET system, group control
extending over tubing systems becomes impossible to set, which means the indoor units cannot operate.
While Group 4 is in heating operation, if later Group 3 begins cooling operation, indoor units 1, 2 of Group 3 can be operated, but the indoor units 3-6 of Group 4 cannot operate.
NOTE
3
45621
21321321
Indoor Units
Outdoor units
Group 4
Group 3 Group 2 Group 1
Remote controller
Group address
Tubing system 1
Tubing system 2
TIMER TMNL.
RCU
TMNL.
RCU.ADR
RCU.Main
RCU.Sub
RCU.CK
To Service Technicians
To display the sensor temperature:
WARNING
To avoid an electric shock hazard, DO NOT touch any ter­minal on the Printed Cir­cuit Board with a metal rod, a screwdriver edge or bare hand when power is supplied.
Press both and buttons on the remote controller for more than 4 seconds together. Change the sensor address (CODE NO.) with / (SET TEMP) buttons. Select the UNIT NO. that you want to call with button. Press the button to finish service mode.
To display the trouble history:
Press both and buttons on the remote controller for more than 4 seconds together. Change the alarm message: / (SET TEMP) buttons CODE NO.
Press the button to finish service mode.
On the remote controller, press + + at the same time for more than 4 seconds. Set CODE No. with / (SET TEMP) button.
Set DATA from to with / (TIMER) button. Press Finally, Press
(New) (Old)
Changing method for room temperature sensor (from Indoor unit to RCU)
1
2
3
4
Remote Controller (Main) Remote Controller (Sub)
Remote controller address connector
Setting the main and sub remote controllers
1. Set one of the 2 connected remote controllers as the main remote controller.
2. On the other remote controller (sub-remote controller), switch the remote controller address connector on the rear of the remote controller PCB from Main to Sub. When the connector has been switched, the remote con­troller will function as the sub-remote controller. The sub-remote controller will also operate when connected to the indoor unit (indoor unit 2 or 3).
Fig. 6-6
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 79
Page 80
REM
80
6-4. Switching the Room Temperature Sensors
Room temperature sensors are contained in the indoor unit and in the remote controller. One or the other of the temperature sensors is used for operation. Normally, the indoor unit sensor is set; however, the procedure below can be used to switch to the remote controller sensor.
(1) Press and hold the + + buttons for 4 seconds or longer.
The unit No. that is initially displayed is the indoor unit address of the group control master unit.
Do not press the button.
(2) Use the temperature setting / buttons to select item code 32.
(3) Use the timer time / buttons to change the setting data from 0000 to 0001.
(4) Press the button. (The change is completed when the display stops blinking.)
(5) Press the button.
The unit returns to normal stop status. At this time, “Remote controller sensor” is displayed on the LCD.
If 2 remote controllers are used for control, this setting can be made from either the main or sub remote con-
troller. However, the temperature sensor that is used is the sensor in the main remote controller.
When group control is used, the remote controller sensor will not function unless the group address is set to the
address of the master indoor unit.
If both the remote sensor and remote controller are used, do not use the temperature sensor in the remote con-
troller.
6-5. Connecting to a Ventilation Fan
If a commercially available ventilation fan or similar device is run from the ventilation fan output terminal (FAN DRIVE: 2P (white), DC 12 V) (Note) on the indoor unit PCB, use the button to enable fan operation and change the settings.
(1) Press and hold the + + buttons for 4 seconds or longer.
The unit No. that is initially displayed is the indoor unit address of the group control master unit.
Do not press the button.
(2) Use the temperature setting / buttons to select item code 31.
(3) Use the timer time / buttons to change the setting data from 0000 to 0001.
(4) Press the button. (The change is completed when the display stops blinking.)
(5) Press the button.
The unit returns to normal stop status. Press the button and check that “Fan” is displayed on the LCD display.
(Note) A special adapter (optional) is required to convert the signal for use at the no-voltage A contact.
NOTE
NOTE
NOTE
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 80
Page 81
REM
81
6-6. Wiring the Remote Controller
<Flush Mounting>
Connection diagram
Use 0.5 mm
2
– 2 mm2wires.
(1) Strip the insulation to approximately 14 mm from
the ends of the wires that will be connected.
(2) Twist together the 2 wires and create a crimp con-
nection at the wire joint.
(3) If a special crimping tool is not used, or if the con-
nection is soldered, insulate the wires using insu­lation tape.
Use the remote controller cord (optional) for remote
controller wiring.
(1) Disconnect the lead wire that is wound around the
lead wire anchor on the remote controller unit. Dis­connect the connector and connect the remote controller cord (optional) to the connector on the remote controller unit. Insert the remote controller cord (optional) into the groove and bend it into the correct shape, then wind it around the lead wire anchor.
(2) If the remote controller cord (optional) is used,
refer to the installation manual that is provided with the cord.
Terminal board for indoor unit remote controller wiring
1 2
1 2
W
BK
Remote controller wiring (field supply)
Connector
Remote controller unit
Power wire from remote controller unit
Approx. 200 mm
Remote controller wiring
Power wire from remote controller unit
Provided wire joint (white)
Wire joint CE-1, white
Remote controller cord (optional)
Connector
Lead wire anchor
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 81
Page 82
82
7. HOW TO PROCESS TUBING
7-1. Connecting the Refrigerant Tubing
Use of the Flaring Method
Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 30 – 50 cm longer than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 7-1)
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 7-2)
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a flare
tool.* (Fig. 7-3)
(*Use “RIGID
®
” or equivalent.)
A good flare should have the following characteristics:
inside surface is glossy and smooth
edge is smooth
tapered sides are of uniform length
NOTE
NOTE
Deburring
Before
After
Fig. 7-1
Reamer
Copper tubing
Fig. 7-2
Flare tool
Flare nut
Copper tubing
Fig. 7-3
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 82
Page 83
83
Caution Before Connecting Tubes Tightly
(1) Apply a sealing cap or water-proof tape to prevent
dust or water from entering the tubes before they are used.
(2) Be sure to apply refrigerant lubricant to the match-
ing surfaces of the flare and union before connect­ing them together. This is effective for reducing gas leaks. (Fig. 7-4)
(3) For proper connection, align the union tube and
flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 7-5)
Adjust the shape of the liquid tube using a tube
bender at the installation site and connect it to the liquid tubing side valve using a flare.
Cautions During Brazing
Replace air inside the tube with nitrogen gas to
prevent copper oxide film from forming during the brazing process. (Oxygen, carbon dioxide and Freon are not acceptable.)
Do not allow the tubing to get too hot during
brazing. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool when brazing.
Use a reducing valve for the nitrogen cylinder.
Do not use agents intended to prevent the for-
mation of oxide film. These agents adversely affect the refrigerant and refrigerant oil, and may cause damage or malfunctions.
7-2. Connecting Tubing Between Indoor and Out-
door Units
(1) Tightly connect the indoor-side refrigerant tubing
extended from the wall with the outdoor-side tub­ing.
(2) To fasten the flare nuts, apply specified torque as
at right:
When removing the flare nuts from the tubing con-
nections, or when tightening them after connecting the tubing, be sure to use 2 monkey wrenches or spanners as shown. (Fig. 7-6) If the flare nuts are over-tightened, the flare may be damaged, which could result refrigerant leakage and cause in injury or asphyxiation to room occu­pants.
For the flare nuts at tubing connections, be sure to
use the flare nuts that were supplied with the unit, or else flare nuts for R410A (type 2). The refriger­ant tubing that is used must be of the correct wall thickness as shown in the table at right.
Apply refrigerant lubricant here and here
Fig. 7-4
Flare nut
Union
Fig. 7-5
Fig. 7-6
Indoor unit
Outdoor unit
Spanner
Torque wrench
Tube diameter
ø6.35 (1/4")
ø9.52 (3/8")
ø12.7 (1/2")
ø15.88 (5/8")
ø19.05 (3/4")
Tightening torque, approximate
14 – 18 N
·
m
(140 – 180 kgf · cm)
34 – 42 N
·
m
(340 – 420 kgf · cm)
49 – 61 N
·
m
(490 – 610 kgf
·
cm)
68 – 82 N
·
m
(680 – 820 kgf · cm)
100 – 120 N
·
m
(1000 – 1200 kgf · cm)
0.8 mm
0.8 mm
0.8 mm
1.0 mm
1.0 mm
Tube thickness
Because the pressure is approximately 1.6 times higher than conventional refrigerant pressure, the use of ordinary flare nuts (type 1) or thin-walled tubes may result in tube rupture, injury, or asphyxi­ation caused by refrigerant leakage.
In order to prevent damage to the flare caused by
over-tightening of the flare nuts, use the table above as a guide when tightening.
When tightening the flare nut on the liquid tube,
use a monkey wrench with a nominal handle length of 200 mm.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 83
Page 84
84
Fig. 7-8
Fig. 7-9
7-3. Insulating the Refrigerant Tubing
Tubing Insulation
Thermal insulation must be applied to all unit tub-
ing, including distribution joint (purchased sepa­rately).
* For gas tubing, the insulation material must be
heat resistant to 120°C or above. For other tubing, it must be heat resistant to 80°C or above.
Insulation material thickness must be 10 mm or greater.
If the conditions inside the ceiling exceed DB 30°C and RH 70%, increase the thickness of the gas tubing insulation material by 1 step.
Taping the flare nuts
Wind the white insulation tape around the flare nuts at the gas tube connections. Then cover up the tubing connections with the flare insulator, and fill the gap at the union with the supplied black insulation tape. Finally, fasten the insulator at both ends with the sup­plied vinyl clamps. (Fig. 7-8)
Insulation material
The material used for insulation must have good insu­lation characteristics, be easy to use, be age resis­tant, and must not easily absorb moisture.
After a tube has been insu­lated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
CAUTION
CAUTION
Never grasp the drain or refrigerant connecting outlets when moving the unit.
Unit side insulator
Insulation tape (white)
(supplied)
Sealer (supplied)
Flare insulator (supplied)
Tube insulator (not supplied) Heat resistant 120°C or above
Vinyl clamps (supplied)
Flare nut
The procedure used for installing the insulator for both gas and liquid tubes is the same.
Seal
Flare insulator
Vinyl clamp
Insulation tape
Refrigerant tubing and insulator (not supplied)
Drain pipe and insulator (not supplied)
Drain insulator and clamp. Large (supplied)
Packing clamp. Small hose band (supplied)
Gas tubing
Liquid tubing
Insulation
Two tubes arranged together
If the exterior of the outdoor unit valves has been finished with a square duct covering, make sure you allow sufficient space to use the valves and to allow the panels to be attached and removed.
Fig. 7-7
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 84
Page 85
85
Fig. 7-10
Fig. 7-11
7-4. Taping the Tubes
(1) At this time, the refrigerant tubes (and electrical
wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To pre­vent the condensation from overflowing the drain pan, keep the drain hose separate from the refrig­erant tubing.
(2) Wrap the armoring tape from the bottom of the
outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1
clamp approx. each meter. (Fig. 7-10)
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also ensure that the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing.
7-5. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to pre­vent rain and draft from entering. (Fig. 7-11)
NOTE
Insulated tubes
Drain hose
Clamp
Tubin
g
Apply putty here
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 85
Page 86
86
Fig. 8-1
Fig. 8-2
8. AIR PURGING
Air and moisture in the refrigerant system may have undesirable effects as indicated below.
pressure in the system risesoperating current risescooling (or heating) efficiency dropsmoisture in the refrigerant circuit may freeze and
block capillary tubing
water may lead to corrosion of parts in the refriger-
ant system
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evac­uated to remove any noncondensables and moisture from the system.
Air Purging with a Vacuum Pump (for Test Run)
Preparation
Check that each tube (both liquid and gas tubes) between the indoor and outdoor units has been prop­erly connected and all wiring for the test run has been completed. Remove the valve caps from both the gas tube and liquid tube service valves on the outdoor unit. Note that both liquid and gas tube service valves on the outdoor unit are kept closed at this stage.
Leak test
(1) Attach a manifold valve (with pressure gauges)
and dry nitrogen gas cylinder to this service port with charge hoses.
(2) Pressurize the system to no more than 36 kgf/cm
2
G with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 36 kgf/cm2G. Then, test for leaks with liquid soap.
Manifold gauge
Outlet Inlet
Vacuum pump
Manifold valve
Pressure gauge
Lo Hi
Charge hose
Outdoor unit
Liquid tube
Gas tube
Nitrogen gas cylinder (In vertical standing position)
Close
Open
Close
Open
Cylinder valve
Service port ø7.94 m
m
Use a manifold valve for air purging. If it is not available, use a stop valve for this pur­pose. The “Hi” knob of the manifold valve must always be kept closed.
CAUTION
CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than the bottom when you pres­surize the system. Usually, the cylinder is used in a ver­tical standing position. (Refer to the previous page.)
Fig. 8-3
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 86
Page 87
87
(3) Do a leak test of all joints of the tubing (both
indoor and outdoor) and both gas tube and liquid tube service valves. Bubbles indicate a leak. Wipe off the soap with a clean cloth after the leak test.
(4) After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Evacuation
(1) Attach the charge hose end described in the pre-
ceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm that the “Lo” knob of the manifold valve is open. Then, run the vacu­um pump. The operation time for evacuation varies with the tubing length and capacity of the pump. The following table shows the amount of time for evacuation:
The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is less than 667 Pa (–755 mm Hg, 5 Torr).
(2) When the desired vacuum is reached, close the
“Lo” knob of the manifold valve and turn off the vacuum pump. Confirm that the gauge pressure is under 667 Pa (–755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum pump operation.
Manifold valve
Pressure gauge
Lo Hi
Vacuum pum
p
Outdoor unit
Liquid tube
Gas tube
Close
Open
Close
Open
Service port ø7.94 m
m
Required time for evacuation
when 30 gal/h vacuum pump is used
If tubing length is If tubing length is
less than 15 m longer than 15 m
45 min. or more 90 min. or more
NOTE
Fig. 8-4
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 87
Page 88
88
Fig. 8-5
Fig. 8-6
Charging additional refrigerant
Charging additional refrigerant (calculated from the
liquid tube length as shown in Section 1-7 “Addi­tional Refrigerant Charge”) using the liquid tube service valve. (Fig. 8-5)
Use a balance to measure the refrigerant accurately.
If the additional refrigerant charge amount cannot
be charged at once, charge the remaining refriger­ant in liquid form by using the gas tube service valve with the system in cooling operation mode at the time of test run. (Fig. 8-6)
Finishing the job
(1) With a hex wrench, turn the liquid tube service
valve stem counter-clockwise to fully open the valve.
(2) Turn the gas tube service valve stem counter-
clockwise to fully open the valve.
(3) Loosen the charge hose connected to the gas
tube service port (for ø7.94 mm tube) slightly to release the pressure, then remove the hose.
(4) Replace the service port cap on the gas tube ser-
vice port and fasten the cap securely with an mon­key spanner or box wrench. This process is very important to prevent gas from leaking from the system.
(5) Replace the valve caps at both gas tube and liquid
tube service valves and fasten them securely.
This completes air purging with a vacuum pump. The air conditioner is now ready for a test run.
CAUTION
Use a cylinder designed for use with R410A respectively.
CAUTION
To avoid gas from leaking when removing the charge hose, make sure the stem of the gas tube is turned all the way out (“BACK SEAT” position).
Valve
Liquid
Manifold valve
Pressure gauge
Lo Hi
Outdoor unit
Liquid tube
Gas tube
Close
Open
Close
Close
R410A
Outdoor unit
Liquid tube
Gas tube
Open
Close
Open
Open
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 88
Page 89
AS1S
89
9. HOW TO INSTALL THE CEILING PANEL
1-Way Air Dischange Semi-Concealed Type (AS1S Type)
9-1. Installing the Ceiling Panel
(1) Screw the M5 × 40 screws supplied (in the unit packing) into 4 points on the flange surface of the unit bolted to
the ceiling. Insert the screws so that the distance between the bottom of the screw head and the bottom surface of the flange is at least 19.05 mm. (Fig. 9-1)
(2) Next, lift the ceiling panel in this position so that the 4 protruding screws pass through the key hole-shaped
openings in the panel, then shift the panel sideways until it is caught by the screws.
(3) Keeping the ceiling panel in this position, check to see if the joining edge of the ceiling panels are in line with
those of the ceiling material. If they are not in line, remove the ceiling panel and finely adjust the suspension position of the unit.
(4) Once the joining edges are properly aligned with each other, install the supplied stoppers into the key hole-
shaped openings, then insert the 4 screws until the ceiling panel touches the flange surface of the unit.
Fig. 9-1
Unit
Ceiling face
Ceiling panel
Air-intake grille
Chain
Hook
Screw
M5 × 40 small screw (4)
Key hole-shaped opening
Stopper
20 mm
123
Stoppers (2) are supplied with the ceiling panel at the time of shipment.
NOTE
9-2. How to Use the Stoppers
(1) Pass through screws on the unit into the key hole-shaped openings on the panel.
(2) Then, shift the panel sideways until it is caught by the screws.
(3) Insert the stoppers in the direction of the arrow as shown, confirm that the bent portion of each stopper is
securely in the hole, A and B, then tighten the screw. (Fig. 9-1)
Accessory
Mounting
Insertion direction
Accessory part
Insertion direction
A
B
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 89
Page 90
ASBS
90
1-Way Air Discharge Semi-Concealed Slim Type
(ASBS Type)
9-3. Installing the Ceiling Panel
(1) Hook the 2 panel catches of the ceiling panel to
the tubing side (stationary side) of the indoor unit. Then, press up on the opposite side to engage the level catch to install by opening the level catch (pressed with fingers.) (Fig. 9-2) Make sure the ceiling panel is mounted correctly.
(2) Fasten the M6 screws (supplied) into 4 points as
shown in Fig. 9-3.
(3) Install the wiring con­nector from the ceiling panel to the connector from the indoor unit.
If the connector is not connected, a misoperation sig­nal (“P9” on the remote control display) will be dis­played when the unit is turned on.
NOTE
Never attempt to move the
louver by hand.
Since the louver has an
automatic air-sweeping
mechanism, it may be
damaged.
CAUTION
Panel catch (level catch side)
Panel catch (stationary side)
Side panel
Connector (panel side)
Connector (unit side)
Electrical component box
Side panel
Fig. 9-2
Fig. 9-3
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 90
Page 91
ASBS
91
Fig. 9-4
Suspension bolt
Nut, washer
Ceiling material
Ceiling panel
Fig. 9-5
Center recess
Center claw
Claw
Side panel
Safety cord
Safety cord
(4) Check to see that the ceiling panel is properly
aligned with the seamline of the ceiling. If not, readjust the indoor unit by adjusting the nuts to the proper suspension point. (Fig. 9-4)
(5) For attaching and removing the side panels, see
Fig. 9-5.
Attaching the side panels
Put the center claw of the side panel into the center recess of the indoor unit. Pressing 2 claws of the both sides of the side panel toward the inside, press the side panel onto the indoor unit.
Removing the side panels
Remove the side panel by pressing the 2 claws at both ends of the panel, disengage the claws and slide the panel horizontally.
When attaching the side
panels, be sure to hook
the safety cords in the
holes of the side panels.
CAUTION
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 91
Page 92
AS2S
92
2-Way Air Discharge Semi-Concealed Type
(AS2S Type)
9-4. Before Installing the Ceiling Panel
(1) Adjust the distance between the unit and the sur-
face of the ceiling (60 mm) using the 2 hexagonal nuts as shown in Fig. 9-6 while following the instal­lation gauge.
(2) Remove the air-intake panel and the air filter from
the ceiling panel as shown in Figs. 9-7 and 9-8.
How to remove the air-intake panel (from either side). (Fig. 9-8)
(1) Push in. (2) Slide. (3) Pull. (4) Remove.
Fig. 9-6
Indoor unit
Ceilin
g
60
60
Fig. 9-7
Fig. 9-8
Electrical component box
Ceiling panel
Indoor unit
M4 × 25 screw, 2 pcs.
(Only 73 Type)
M5 × 40 screw, 4 pcs.
Latch
Air filter
Air-intake panel
Filter installation section
Filter installation section
Never touch or attempt to move the air-direction lou­ver by hand or you may damage the unit. Instead, use the remote controller if you want to change the direction of air flow.
CAUTION
3
1
2
4
Air-intake panel
Unit: mm
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 92
Page 93
AS2S
93
Fig. 9-9
Panel catch (level catch side)
Panel catch (stationary side)
Fig. 9-10
Electrical component box
Connector
9-5. Installing the Ceiling Panel
(1) Lift the ceiling panel and position it to align the
panel catches with the catch recesses of the indoor unit.
(2) Hook the stationary catch first and then press up
on the opposite side to engage the level catch to install as shown in Fig. 9-9.
The ceiling panel must be mounted correctly. Listen for the click to determine it is securely shut.
(3) Next, check to see that the ceiling panel is proper-
ly aligned with the seamline of the ceiling. If it is not, remove the ceiling panel and slightly readjust the indoor unit body to the proper suspension point.
(4) When the ceiling panel has been properly aligned,
use the 4 supplied mounting screws (M5) with washers to permanently fasten the ceiling panel.
(5) Install the wiring connector from the ceiling panel
to the connector in the electrical component box of the indoor unit (8P connector if heat pump model). After installing the connector, use the clamp on the body of the indoor unit to secure the wiring.
If the connector is not connected, a misoperation sig­nal (“P9” on the remote control display) will be dis­played when the unit is turned on.
(6) Install the air filter and air-intake grille by perform-
ing the steps in Figs. 9-7 and 9-8 in reverse.
9-6. When Removing the Ceiling Panel for
Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the wiring connector inside the electrical component box, and then remove the 4 mounting screws.
Release one side of the panel by pressing the panel catch in the direction of the arrow. (See Caution.) Completely remove the ceiling panel by disengaging the stationary catch. (Fig. 9-9)
NOTE
NOTE
When the air filter is removed, the rotator and live parts are exposed at the openings and these can cause a danger. Therefore be particularly careful.
CAUTION
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 93
Page 94
ASS
94
4-Way Air Discharge Semi-Concealed Type
(ASS Type)
Checking the unit position
(1) Check that the ceiling hole is within this range:
860 × 860 to 910 × 910 mm
(2) Use the full-scale installation diagram (from the
packaging) that was supplied with the unit to deter­mine the positioning of the unit on the ceiling sur­face. If the positions of the ceiling surface and unit do not match, air leakage, water leakage, flap operation failure, or other problems may result.
CAUTION
Never place the panel
face-down. Either hang it vertically or place it on top of a projecting object. Placing it face­down will damage the surface.
Do not touch the flap or
apply force to it. (This may cause flap malfunction.)
must be within the range of 12 – 17 mm.
If not within this range, malfunction or other trouble may result.
A
Ceiling side
Main unit
Ceiling opening dimension
A
Fig. 9-11
Wing
Fig. 9-12a
Fig. 9-12b
2
Fig. 9-14
9-7. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 9-12b, 9-13 and 9-14)
a) Remove the 2 screws on the latch of the air-
intake grille. (Fig. 9-12b)
b) Slide the air-intake grille catches in the direc-
tion shown by the arrows to open the grille. (Fig. 9-13)
c) With the air-intake grille opened, remove the
grille hinge from the ceiling panel by sliding it in the direction shown by the arrow . (Fig. 9-14)
(2) Removing the corner cover
a) Slide the corner cover to the direction shown
by the arrow to remove the corner cover. (Fig. 9-15).
1
2
1
Corner cover
Ceiling panel
Strap
Push
1
Corner cover
Fig. 9-15
Air-intake grille
Ceiling panel
Air-intake grille hinge
1
1
Fig. 9-13
Latch
Screw
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 94
Page 95
ASS
95
CAUTION
9-8. Installing the Ceiling Panel
The power must be turned ON in order to change the flap angle. (Do not attempt to move the flap by hand. Doing so may damage the flap.)
(1) Insert the temporary fasteners (stainless steel) on
the inside of the ceiling panel into the square holes on the unit to temporarily fasten the ceiling panel in place. (Fig. 9-16)
The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE and DRAIN marks on the ceiling panel corner with the correct positions on the unit.
To remove the ceiling panel, support the ceiling
panel while pressing the temporary fasteners toward the outside. (Fig. 9-16)
(2) Align the panel installation holes and the unit
screw holes.
(3) Tighten the supplied washer head screws at the 4
panel installation locations so that the panel is attached tightly to the unit. (Fig. 9-17)
(4) Check that the panel is attached tightly to the ceil-
ing.
At this time, make sure that there are no gaps
between the unit and the ceiling panel, or between the ceiling panel and the ceiling surface. (Fig. 9-18)
Square hole in unit
Temporary fastener
Push when you remove
Temporary fastener
Fig. 9-16
Drain tubing corner
Refrigerant tubing corner
Panel installation hole (4 locations)
Ceiling panel
Washer head screws
DRAIN mark
REF. PIPE mark
Fig. 9-17
Do not allow
gaps
Ceilin
g
panel
Main unit
Ceiling surface
Fig. 9-18
Insert a wrench or other tool into the corner cover installation hole and make fine adjustments to the unit nut.
Air leakage
Air leakage from ceiling surface
Staining
Condensation, water leakage
Adjust so that there are no gaps.
Fig. 9-19
Fig. 9-20
If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling. (Fig. 9-19)
If the screws are not sufficiently
tightened, trouble such as that shown in the figure below may occur. Be sure to tighten the screws securely.
If a gap remains between the
ceiling surface and the ceiling panel even after the screws are tightened, adjust the height of the unit again.
The height of the unit can be adjusted from the ceiling panel corner hole, with the ceil­ing panel attached, to an extent that does not affect the unit levelness, the drain hose, or other elements.
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 95
Page 96
ASS
96
9-9. Wiring the Ceiling Panel
(1) Open the cover of the electrical component box.
(2) Connect the 7P wiring connector (red) from the
ceiling panel to the connector in the unit electrical component box.
If the connectors are not connected, the Auto flap
will not operate. Be sure to connect them securely.
Check that the wiring connector is not caught
between the electrical component box and the cover.
Check that the wiring connector is not caught
between the unit and the ceiling panel.
9-10. How to Attach the Corner & Air Intake Grille
Attaching the corner cover and air-intake grille
A. Attaching the corner cover
(1) Check that the safety cord from the corner cover is
fastened to the ceiling panel pin, as shown in the figure.
(2) Use the supplied screws to attach the corner cover
to the ceiling panel.
B. Attaching the air-intake grille
To install the air-intake grille, follow the steps for
Removing the grille in the reverse order. By rotat­ing the air-intake grille, it is possible to attach the grille onto the ceiling panel from any of 4 directions. Coordinate the directions of the air-intake grilles when installing multiple units, and change the directions according to customer requests.
When attaching the air-intake grille, be careful
that the flap lead wire does not become caught.
Be sure to attach the safety cord that prevents
the air-intake grille from dropping off to the ceiling panel unit as shown in the figure at right.
(Direction that the unit faces has been changed to facilitate explanation.)
Ceiling panel wiring connector
Ceiling panel side
Screws (3 locations)
Mains side
Clamp
Electrical component box cover
* Pass the wiring connector through the clamp to fasten it in place,
as shown in the figure.
Place the corner cover so that the 3 tabs fit into the holes in the ceiling panel. Then fasten it in place with the supplied screws.
Pin
With this ceiling panel, the directions of the air-intake grille lattices when installing multiple units, and the position
of the label showing the company name on the corner panel, can be changed according to customer requests, as shown in the figure below. However, the optional wireless receiver kit can only be installed at the refrigerant­tubing corner of the ceiling unit.
Unit electrical component box
Unit drain hose side
Unit refrigerant tube side
Optional wireless receiver kit * Can only be installed in this position.
Can be installed rotated 90˚
Locations of the air-intake grille catches at the time the product is shipped. * The grille can be installed with these
catches facing in any of 4 directions.
Fig. 9-21
Fig. 9-22
Hole for ceiling panel hook
Hook that prevents the
g
rille from droppin
g
Fig. 9-23
Fig. 9-24
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 96
Page 97
ASS
97
9-11. Checking After Installation
Check that there are no gaps between the unit and
the ceiling panel, or between the ceiling panel and the ceiling surface. Gaps may cause water leakage and condensation.
Check that the wiring is securely connected.
If it is not securely connected, the auto flap will not operate. (“P09” is displayed on the remote con­troller.) In addition, water leakage and condensa­tion may occur.
9-12. When Removing the Ceiling Panel for
Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the wiring connector inside the electrical component box, and then remove the 4 mounting screws.
9-13. Adjusting the Auto Flap
The air-direction louver on the ceiling panel outlet can be adjusted as follows.
Adjust the louver to the desired angle using the
remote controller. The louver also has an automatic air-sweeping mechanism.
Never attempt to move the louver by hand.
Proper air flow depends on the location of the air
conditioner, the layout of the room and furniture, etc. If cooling or heating seems inadequate, try changing the direction of the air flow.
NOTE
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 97
Page 98
98
10. TEST RUN
10-1. Preparing for Test Run
Before attempting to start the air conditioner,
check the following.
(1) All loose matter is removed from the cabinet,
especially steel filings, bits of wire, and clips.
(2) The control wiring is correctly connected and all
electrical connections are tight.
(3) The transportation pads for the indoor fan have
been removed. If not, remove them now.
(4) The power has been connected to the unit for at
least 5 hours before starting the compressor. The bottom of the compressor should be warm to the touch and the crankcase heater around the feet of the compressor should be hot to the touch. (Fig. 10-1)
(5) Both the gas and liquid tube service valves are
open. If not, open them now. (Fig. 10-2)
(6) Request that the customer be present for the trial
run. Explain the contents of the instruction manual, then have the customer actually operate the system.
(7) Be sure to give the instruction manual and warran-
ty certificate to the customer.
(8) When replacing the control PCB, be sure to make
all the same settings on the new PCB as were in use before replacement. The existing EEP ROM is not changed, and is connected to the new control PCB.
Fig. 10-1
Fig. 10-2
Power mains switch
(Power must be turned ON at least 5 hours before attempting test run)
ON
Liquid tube service cap
Gas tube service cap
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 98
Page 99
99
YES
Make necessary corrections.
Check the alarm
contents.
Check the alarm contents.
Turn OFF the indoor and
NO
YES
NO
*1
*2
*3 *3
*2
CASE 1
CASE 2
CASE 3B CASE 3A
YES
YES
NO
YES
NO
NO
NO
YES
YES
NO
Recheck the items to check before the test run.
Have the outdoor sub units been connected?
Are the inter-unit control wires
connected to more than 1 refrigerant
system?
Is it possible to turn ON the power only
for the 1 refrigerant system where the
test run will be performed?
Will automatic address setting be
performed in Heating mode?
Is it OK to start the compressors?
Turn ON the indoor and
outdoor unit power.
Short-circuit the mode change pin
(CN50) on the outdoor main unit PCB.
At the same time, short-circuit the
automatic address pin (CN51) for 1
second or longer, then pull it out.
Short-circuit the automatic address
pin (CN51) on the outdoor unit PCB
for 1 second or longer,
then release it.
Short-circuit the automatic address pin (CN51)
on the outdoor unit PCB for 1 second or longer,
then release it.
Start indoor and outdoor unit
cooling operation.
LED 1 and 2 blink alternately.
Start indoor and outdoor unit
heating operation.
LED 1 and 2 blink alternately.
LED 1 and 2 blink alternately
(about 2 or 3 minutes).
Is it OK to start the compressors?
Turn ON the indoor and
outdoor unit power.
Turn OFF the indoor
and outdoor unit
Turn ON the indoor and
outdoor unit power for that
refrigerant system only.
Are LEDs 1 and 2 on the
outdoor unit PCB OFF?
Are LEDs 1 and 2 on the outdoor unit PCB OFF?
Set the unit address.
Set the No. of outdoor units.
Set the No. of indoor units.
Set the system address.
When multiple outdoor units exist, disconnect the terminals
extended from the shorted plugs (CN33) at all outdoor main unit
PCBs except for 1.
Alternatively, move the sockets to the OPEN side.
<Outdoor unit control PCB>
Unit No. setting switch
(S004)
<Outdoor unit control PCB>
Unit No. setting switch
(S002 and S003)
Refer to Fig. 10-4
(Check the link wiring.)
*1
The unit with the unit
No. set to 1 is the main unit. All other units are sub units.
Refer to “Table of Self-Diagnostic Functions and Description of Alarm Displays.”
*2 A minimum of 5 hours must have passed after the
power was turned ON to the outdoor unit.
*3 All indoor units operate in all refrigerant systems
where the power is ON.
Check that test run preparation is OK.
(Do not allow the short-circuited pins to remain short-circuited.)
Refer to the remote
controller test-run
settings.
Set the wired remote controller for test run.
Does system operate?
Return remote control to normal mode
Check and make corrections according to
“Table of Self-Diagnostic Functions.”
End test run.
Make necessary
corrections
10-2. Test Run Procedure
Items to Check Before the Test Run
1. Turn the remote power switch on at least 5 hours before the test, in order to energize the crank case heater.
2. Turn the outdoor service valves (2 locations) to the full-open positions.
Use caution when making the set-
tings. If there are duplicated system addresses, or if the settings for the Nos. of the indoor units are not con­sistent, an alarm will occur and the system will not start.
These settings are not made on the
indoor unit PCB.
Fig. 10-3
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 99
Page 100
100
10-3. Outdoor Unit PCB Setting
CN51
CN50
D043
(LED2)
D042
(LED1)
S003
CN33
S002
S004
Fig. 10-4
06-065 Mini ECO-i II for ARGO 2/8/06 4:37 PM Page 100
Loading...