Argo FCR512CL, AWR509CL, AFR509CL, AWR512CL, AER508SCLA Technical & Service Manual

...
Page 1
TECHNICAL& SERVICE MANUAL
AWR508CL + AER508SCLA AWR509CL + AER509SCLA
AFR509CL + AER509SCLA
Indoor Unit
Outdoor Unit
AWR508CL AWR509CL AWR512CL
AER508SCLA AER509SCLA AER512SCLA
FCR512CL + AER512SCLA
AWR512CL + AER512SCLA
Ceiling-Mounted
Floor-Mounted
FCR512CL
AFR509CL
0.8180.169.0 02/2001
®
Page 2
WARNING
CAUTION
WARNING
CAUTION
Page 3
Table of Contents
Page
1 OPERATING RANGE 1 2 SPECIFICATIONS
2-1 Unit Specification 2 2-2 Major Component Specifications 7
2-3 Other Component Specifications 15 3 DIMENSIONAL DATA 18 4 REFRIGERANT FLOW DIAGRAM 21 5 PERFORMANCE DATA
5-1 Air Throw Distance Chart 23 5-2 Performance Charts 26 5-3 Cooling Capacity 29
6 ELECTRICAL DATA
6-1 Electrical Characteristic 34
6-2 Electric Wiring Diagrams 36 7 INSTALLATION INSTRUCTIONS
7-1 Installation Site Selection 39 7-2 Remote Control Unit Installation Position 41 7-3 Recommended Wire Length and Diameter 42
8 FUNCTION 8-1 Room Temperature Control 43 8-2 Dry Operation 44 8-3 Freeze prevention 45 8-4 Outdoor fan speed control 46
9 REFRIGERANT R407C:SPECIAL PRECAUTION WHEN SERVICING UNIT 9-1 Characteristics of new refrigerant R407c 47 9-2 Checklist before servicing 47 9-3 Tools specifically for R407c 48 9-4 For tubing installation procedures 48 9-5 In case of compressor malfunction 49 9-6 In case refrigerant is leaking 51 9-7 Charging additional refrigerant 53 9-8 Retro-fitting existing systems 53
10 TROUBLESHOOTING
10-1 Check before and after troubleshooting 54
10-2 Air Conditioner Does not operate 55
10-3 Some Parts of Air Conditioner does not operate 59 10-4 Air Conditioner Operates, but abnormalities are observed 61 10-5 If a sensor is defective 62
Page 4
11 CHECKING ELECTRICAL COMPONENTS 11-1 Measurements of insulation resistence 63 11-2 Checking continuity of fuse on PCB ass’y 64 11-3 Checking motor capacitor 64
12 DISASSEMBLY PROCEDURE FOR INDOOR UNIT 12-1 Removing air intake grille 65 12-2 Removing side panels 66 12-3 Access and removal of electrical components box 66 12-4 Removing flap motor 67 12-5 Removing evaporator 67 12-6 Removing fan and fan motor 69
APPENDIX Instructions manual 70
Page 5
Page 6
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling
Capacity kW 2.05
BTU/h 6,991
Air circulation (High)
m3/h 430
Moisture removal (High) Liters/h 0.4
Electrical Rating Cooling
Available voltage range V 198 ~ 264 Running amperes A 3.2 Power input W 680 Power factor % 92 C.O.P. W/W 3.01 Compressor locked rotor amperes A 17
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R407c / 730 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 37 / 32 / 31
Outdoor : Hi dB-A 43 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 9.52(3/8) Refrigerant tube kit / Accessories Optional / Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 34.0
Shipping kg 10.0 37.0 Shipping volume
m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
Page 7
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling
Capacity kW 2.55
BTU/h 8700
Air circulation (High)
m3/h 470
Moisture removal (High) Liters/h 0.9
Electrical Rating Cooling
Available voltage range V 198 ~ 264 Running amperes A 4.4 Power input W 940 Power factor % 92 C.O.P. W/W 2.7 Compressor locked rotor amperes A 23
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R407c / 800 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 37 / 32 / 31
Outdoor : Hi dB-A 43 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 9.52(3/8) Refrigerant tube kit / Accessories Optional / Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 36.0
Shipping kg 10.0 37.0 Shipping volume
m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
Page 8
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling
Capacity kW 2.55
BTU/h 8700
Air circulation (High)
m3/h 380
Moisture removal (High) Liters/h 0.7
Electrical Rating Cooling
Available voltage range V 198 ~ 264 Running amperes A 4.4 Power input W 940 Power factor % 92 C.O.P. W/W 2.7 Compressor locked rotor amperes A 23
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Manual Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R407c / 800 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 37 / 32 / 31
Outdoor : Hi dB-A 43 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 9.52(3/8) Refrigerant tube kit / Accessories Optional / Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 700 540
Width mm 560 700
Depth mm 200 265 Package dimensions Height mm 770 568
Width mm 620 815
Depth mm 265 343 Weight Net kg 18 36.0
Shipping kg 20 37.0 Shipping volume
m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
Page 9
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling
Capacity kW 3.30
BTU/h 11400
Air circulation (High)
m3/h 490
Moisture removal (High) Liters/h 1.3
Electrical Rating Cooling
Available voltage range V 198 ~ 264 Running amperes A 6.5 Power input W 1380 Power factor % 92 C.O.P. W/W 2.4 Compressor locked rotor amperes A 33
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R407c / 750 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 39 / 35 / 33
Outdoor : Hi dB-A 45 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Accessories Optional / Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 37.0
Shipping kg 10.0 40.0 Shipping volume
m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
Page 10
6
Indoor Unit FCR512CL Outdoor Unit AER512SCLA
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling
Capacity kW 3.30
BTU/h 11400
Air circulation (High)
m3/h
700
Moisture removal (High) Liters/h 1.30
Electrical Rating Cooling
Available voltage range V 198 ~ 264 Running amperes A 6.5 Power input W 1.380 Power factor % 92 C.O.P. W/W 2.4 Compressor locked rotor amperes A 33
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R407c / 750 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 39 / 35 / 33
Outdoor : Hi dB-A 45 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Air Clean Filter Optional / Optional
Dimensions & Weight
Indoor Unit
Outdoor Unit
Unit dimensions Height mm 680 530
Width mm 900 750
Depth mm 190 270 Package dimensions Height mm 813 593
Width mm 1,011 895
Depth mm 296 348 Weight Net kg 23.5 35.5
Shi pp in g kg 30.0 38.0 Shipping volume
m
3
0.24 0.18
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
Page 11
Controller PCB
Part No. POW-K8E(A), POW-K8E(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8PS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,130 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT : 561.8
VLT-WHT : 197.4
VLT-ORG : 63.4
YEL-ORG : 155.7
YEL-PNK : 115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close
Run capacitor µF 0.6
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area
m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Page 12
Controller PCB
Part No. POW-K8E(A), POW-K8E(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8PS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,190 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT : 561.8
VLT-WHT : 197.4
VLT-ORG : 63.4
YEL-ORG : 155.7
YEL-PNK : 115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close
Run capacitor µF 0.8
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area
m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Page 13
Controller PCB
Part No. POW-K8E(A), POW-K8E(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8PS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,230 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT : 561.8
VLT-WHT : 197.4
VLT-ORG : 63.4
YEL-ORG : 155.7
YEL-PNK : 115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close
Run capacitor µF 1.0
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area
m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Page 14
10
Indoor Unit AFR509CL
Controller PCB
Part No. POW-K185GS5-N Controls Microprocessor Control circuit fuse 250 V 3 A
Remote Control Unit RCS-5PS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø100 / L410 Fan motor model ... Q'ty KR35406M01527 No. of poles ... rpm (230 V, High) 4 ... 1,140 Nominal output W 27 Coil resistance (Ambient temp. 20°C) Ω GRY-WHT : 545 - 630
WHT-VLT : 92 - 105
VLT-YEL : 62 - 71
BRN-YEL : 78 - 90
——
Safety devices Type Internal protector
Operating temp. Open °C 150±10
Close Automatic reclosing
Run capacitor µF 0.6
VAC 400
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area
m
2
0.185
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Page 15
11
Indoor Unit FCR512CL
Controller PCB
Part No. POW-K185GS-N Controls Microprocessor Control circuit fuse 250 V 3 A
Remote Control Unit RCS-5PS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 2 ... ø130 / L180 Fan motor model ... Q'ty K48407-M01416 ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,160 Nominal output W 20 Coil resistance (Ambient temp. 20°C) GRY-WHT : 311±7%
WHT-VLT : 97.6±7%
VLT-YEL : 97.6±7%
WHT-PNK : 425±7%
——
Safety devices Type Internal protector
Operating temp. Open °C 145±5
Close Automatic reclosing
Run capacitor µF 1.5
VAC 440
Flap Motor
Model M2LJ24ZE31 Rating AC 208 / 230 V, 50 / 60 Hz No. of poles ... rpm 8 ... 2.5 / 3.0 Nominal output W 3 / 2.5 Coil resistance (Ambient temp. 20°C) k 16.45 ± 15%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area
m
2
0.192
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Page 16
Compressor
Type Rotary (Hermetic) Compressor model C-1RN60H5C 802-060-35B Nominal output W 600 Compressor oil ... Amount cc DAPHNE FV68S ... 350 Coil resistance (Ambient temp. 25°C) C–R : 4.66
C–S : 8.89
Safety devices Type External(OLR A) External(OLR T)
Overload relay MRA38072-3229 CS-7C115 Operating temp. Open °C 145±5 115±3
Close °C 69±11 95±5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 13A
Run capacitor µF 17.5
VAC 450
Crank case heater
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty KR35410M01846 ... 1 No. of poles ... rpm (230 V, High) 6 ... 770 Nominal output W 20 Coil resistance (Ambient temp. 25°C) BLK-WHT : 211-242 / WHT-VLT : 244-281
VLT-YEL: 83.5-96.1 / BLK-PNK : 41.7-48
Safety devices Type Internal fuse
Operating temp. Open °C 150±10
Close °C
Run capacitor µF 1.5
VAC 450
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area
m
2
0.353
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Page 17
Compressor
Type Rotary (Hermetic) Compressor model C-RN80H5A 802-282-45G Nominal output W 800 Compressor oil ... Amount cc DAPHNE FV68S ... 470 Coil resistance (Ambient temp. 25°C) Ω C–R : 3.070
C–S : 7.97
Safety devices Type External(OLR A) External(OLR T)
Overload relay MRA38066-3229 CS-7C115 Operating temp. Open °C 150±5 115±3
Close °C 69±11 95±5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 16A
Run capacitor µF 22.5
VAC 450
Crank case heater
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty KR35410M01846 ... 1 No. of poles ... rpm (230 V, High) 6 ... 800 Nominal output W 56 Coil resistance (Ambient temp. 25°C) BLK-WHT : 211-242 / WHT-VLT: 244-281
VLT-YEL : 83.5-96.1 / BLK-PNK: 41.7-48
Safety devices Type Internal fuse
Operating temp. Open °C 150±10
Close °C
Run capacitor µF 1.5
VAC 450
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area
m
2
0.353
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Page 18
14
Outdoor Unit AER512SCLA
Controller PCB
Part No. POW-CLR128E Control circuit fuse 250 V 3.15 A
Compressor
Type Rotary (Hermetic) Compressor model C-R110H5HB 80235645B-S Nominal output W 1,100 Compressor oil ... Amount cc DAPHNE FV68S ... 510 Coil resistance (Ambient temp. 25°C) C–R : 1.962
C–S : 5.38
Safety devices Type External(OLR A) External(OLR T)
Overload relay MRA98596-9201 CS-7C115 Operating temp. Open °C 150±5 115±3
Close °C 69±11 95±5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 21A
Run capacitor µF 25.0
VAC 400
Crank case heater 240 V 20 W
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø400 Fan motor model ... Q'ty KR35410M01846 ... 1 No. of poles ... rpm (230 V, High) 6 ... 770 Nominal output W 20 Coil resistance (Ambient temp. 25°C) Ω BLK-WHT : 211-242
WHT-VLT : 244-281
VLT-YEL : 83.5-96.1
BLK-PNK : 41.7-48.0
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close °C
Run capacitor µF 2.0
VAC 450
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area
m
2
0.379
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Page 19
Thermistor (Room sensor) DTN-TKS134B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Thermistor (Coil sensor TH1) PBC–41E–S4
Resistance k –20°C 40.1± 5% 20°C 6.5± 5%
–10°C 24.4± 5% 30°C 4.4± 5%
0°C 15.3± 5% 40°C 3.0± 5%
10°C 9.9± 5% 50°C 2.1± 5%
Power Relay (PR) G7L-2A-TUB
Coil rating AC 200–240V, 50/60Hz Coil resistance (at 23°C) 21 ± 15% Contact rating AC 220V, 25A
Transformer (TR2) ATR-J65
Rating Primary AC 230V, 50Hz
Secondary 19V, 0.315A Capacity 6VA
Coil resistance (at 22°C) Primary (WHT – WHT): 455 ± 10%
Secondary (BRN – BRN): 2.85 ± 10%
Thermal cut-off temp. 145°C
15
Page 20
16
Transformer (TR) ATR-H85
Rating Primary AC 235V, 50Hz
Secondary 11V, 0.727A Capacity 8VA
Coil resistance (at 21°C) Primary (WHT – WHT): 214 ± 10%
Secondary (BRN – BRN): 1.58 ± 10%
Thermal cut-off temp. 145°C, 2A, 250V
Thermistor (Coil sensor TH1) DHPBC-41ES-14N
Resistance k –20°C40.1 ±5%
–10°C24.4 ±5%
0°C15.3 ±5%
-10°C9.9 ±5%
Thermistor (Room sensor TH2) DHKTEC-35-S6N
Resistance k -20°C 10 ±5%
-10° 7.9 ±5%
-20°C6.3 ±5%
-10°C5.0 ±5%
Indoor Unit AFR509CL
Page 21
17
Transformer (TR) ATR-H85
Rating Primary AC 230V, 50/60Hz
Secondary 11V, 0.727A Capacity 8VA
Coil resistance (at 21°C) Primary (WHT – WHT): 214 ± 10%
Secondary (BRN – BRN): 1.58 ± 10%
Thermal cut-off temp. 145°C, 2A, 250V
Thermistor (Coil sensor TH1) PBC-41E-S14
Resistance k –20°C 40.1 ± 5% 20°C 6.5 ± 5%
–10°C 24.4 ± 5% 30°C 4.4 ± 5%
0°C 15.3 ± 5% 40°C 3.0 ± 5%
10°C 9.9 ± 5% 50°C 2.1 ± 5%
Thermistor (Room sensor TH2) KTEC-35-S6
Resistance k 10°C 10.0 ± 4% 30°C 4.0 ± 4%
15°C 7.9 ± 4% 35°C 3.3 ± 4% 20°C 6.3 ± 4% 40°C 2.7 ± 4% 25°C 5.0 ± 4% 50°C 1.8 ± 4%
Indoor Unit FCR512CL
Page 22
18
3. DIMENSIONAL DATA
Indoor Unit FCR512CL
Remote control unit
86
74 74
Center of tubing hole ø75 (4 places)
Wide tube ø12.7 (1/2") Narrow tube ø6.35 (1/4")
Drain hose ø26
74 74
900
86
41
41
190
680
18.5
61
172.5
Unit : mm
Page 23
58.599.5
805 177
41.0
41.0 270
Narrow tube ø6.35 (1/4")
Wide tube ø9.52 (3/8") AWR508,AWR509 Wide tube ø12.7 (1/2") AWR512
Center of tubing hole (2 places)
Drain hose ø18
Remote control unit
18.5
61
172.5
Page 24
700
540
15
255
Narrow tube service valve ø6.35 (1/4")
Wide tube service valve ø9.52 (3/8") ø12.7 (1/2")
170
103 57
470
4 – ø12 holes
116
320
294
Air intake
Air discharge
AER508,AER509 AER512
Page 25
Indoor Unit
AWR508CL AWR509CL
AER509SCLA
Compressor
Accumulator
Wide tube service valve
Wide tube
O.D. ø9.52 mm (3/8 ")
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Condenser
Capillary tube
Indoor Unit Outdoor Unit
Evaporator
Muffler
Compressor
Accumulator
Wide tube service valve
Wide tube
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Condenser
Capillary tube
Indoor Unit Outdoor Unit
Evaporator
Muffler
O.D. ø12.7 mm (1/2 ")
AFR509CL
FCR512CL
Page 26
IMPORTANT
CAUTION
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
Page 27
Indoor inlet air
D.B. temp. (°C)
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube service valve MPa (kgf/cm
2
G)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
Cooling Characteristics
9 8 7 6 5 4 3 2 1
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
10
Indoor inlet air
D.B. temp. (°C)
32 27
19.4
32 27
19.4
32 27
19.4
NOTE
Page 28
Indoor inlet air
D.B. temp. (°C)
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube service valve MPa (kgf/cm
2
G)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
Cooling Characteristics
9 8 7 6 5 4 3 2 1
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
10
Indoor inlet air
D.B. temp. (°C)
32 27
19.4
32 27
19.4
NOTE
Page 29
Indoor inlet air
D.B. temp. (°C)
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube service valve MPa (kgf/cm
2
G)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
Cooling Characteristics
11 10
9 8 7 6 5 4 3
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
12
Indoor inlet air
D.B. temp. (°C)
32 27
19.4
32 27
19.4
NOTE
Page 30
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air verocity
Flap angle
0°
30°
Room air temp. : 27°C Fan speed : High
Indoor Unit AWR509CL
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air verocity
Flap angle
0°
30°
Room air temp. : 27°C Fan speed : High
26
Page 31
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air verocity
Flap angle
0°
30°
Room air temp. : 27°C Fan speed : High
Page 32
28
Indoor Unit FCR512CL
01234567
01234567
3
4
2
1
0
1
0
2
3
4
Horizontal distance (m)
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Axis air verocity
Flap angle
60°
45°
Axis air verocity
Flap angle
45°
30°
Floor mounted
Ceiling mounted
Page 33
RATING CAPACITY 2.05 kW AIR FLOW RATE 430 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 1.94 1.89 1.80 1.68 1.56
CM 0.56 0.60 0.64 0.70 0.77 21 SHC 1.33 1.31 1.26 1.21 1.15 23 SHC 1.51 1.48 1.44 1.38 1.32
15 25 SHC 1.68 1.65 1.60 1.55 1.49
27 SHC 1.86 1.82 1.78 1.68 1.56 29 SHC 1.94 1.89 1.80 1.68 1.56 31 SHC 1.94 1.89 1.80 1.68 1.56
TC 2.10 2.02 1.93 1.81 1.67
CM 0.57 0.61 0.66 0.73 0.79 21 SHC 1.17 1.13 1.09 1.03 0.97 23 SHC 1.34 1.30 1.26 1.20 1.14
17 25 SHC 1.52 1.48 1.43 1.38 1.31
27 SHC 1.69 1.64 1.60 1.55 1.48 29 SHC 1.87 1.82 1.77 1.72 1.65 31 SHC 2.05 1.99 1.93 1.81 1.67
TC 2.23 2.15 2.05 1.93 1.77
CM 0.60 0.63 0.68 0.75 0.81 21 SHC 0.98 0.94 0.90 0.85 0.78 23 SHC 1.15 1.12 1.07 1.02 0.96
19 25 SHC 1.31 1.29 1.24 1.19 1.13
27 SHC 1.48 1.46 1.42 1.36 1.30 29 SHC 1.65 1.63 1.59 1.54 1.47 31 SHC 1.82 1.80 1.76 1.71 1.64
TC 2.36 2.28 2.17 2.04 1.88
CM 0.61 0.65 0.70 0.77 0.83 23 SHC 0.96 0.93 0.89 0.83 0.77
21 25 SHC 1.13 1.10 1.06 1.01 0.94
27 SHC 1.30 1.27 1.23 1.18 1.11 29 SHC 1.46 1.44 1.40 1.35 1.29 31 SHC 1.64 1.62 1.57 1.52 1.46
TC 2.52 2.42 2.28 2.13 1.99
CM 0.63 0.67 0.72 0.78 0.85
23 25 SHC 0.95 0.90 0.86 0.80 0.75
27 SHC 1.11 1.07 1.03 0.97 0.92 29 SHC 1.27 1.25 1.20 1.15 1.09 31 SHC 1.46 1.42 1.37 1.31 1.27
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
5-3. Cooling Capacity
Indoor Unit AWR508CL Outdoor Unit
AER508SCLA
230V Single Phase 50Hz
29
Page 34
RATING CAPACITY 2.55 kW AIR FLOW RATE 470 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 2.42 2.34 2.23 2.10 1.93
CM 0.77 0.83 0.89 0.97 1.06 21 SHC 1.66 1.62 1.57 1.50 1.42 23 SHC 1.88 1.84 1.79 1.72 1.64
15 25 SHC 2.09 2.05 2.00 1.93 1.85
27 SHC 2.31 2.27 2.21 2.10 1.93 29 SHC 2.42 2.34 2.23 2.10 1.93 31 SHC 2.42 2.34 2.23 2.10 1.93
TC 2.62 2.52 2.39 2.25 2.07
CM 0.79 0.85 0.91 1.00 1.09 21 SHC 1.45 1.41 1.35 1.29 1.20 23 SHC 1.67 1.62 1.56 1.50 1.42
17 25 SHC 1.89 1.83 1.78 1.71 1.63
27 SHC 2.11 2.05 1.99 1.92 1.85 29 SHC 2.33 2.26 2.21 2.14 2.06 31 SHC 2.54 2.47 2.39 2.25 2.07
TC 2.77 2.68 2.55 2.39 2.21
CM 0.83 0.88 0.94 1.03 1.12 21 SHC 1.21 1.18 1.12 1.05 0.98 23 SHC 1.43 1.39 1.34 1.27 1.19
19 25 SHC 1.64 1.60 1.55 1.49 1.40
27 SHC 1.85 1.82 1.76 1.70 1.62 29 SHC 2.05 2.03 1.97 1.91 1.83 31 SHC 2.27 2.25 2.19 2.12 2.05
TC 2.94 2.84 2.71 2.54 2.34
CM 0.85 0.90 0.97 1.06 1.15 23 SHC 1.20 1.16 1.10 1.04 0.96
21 25 SHC 1.40 1.37 1.32 1.25 1.18
27 SHC 1.62 1.59 1.53 1.47 1.39 29 SHC 1.82 1.80 1.75 1.68 1.60 31 SHC 2.04 2.01 1.96 1.90 1.82
TC 3.14 3.00 2.84 2.66 2.47
CM 0.87 0.92 0.99 1.08 1.18
23 25 SHC 1.18 1.13 1.06 1.00 0.93
27 SHC 1.38 1.34 1.28 1.21 1.14 29 SHC 1.58 1.55 1.49 1.42 1.36 31 SHC 1.81 1.77 1.70 1.64 1.57
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
Outdoor Unit
Indoor Unit AWR509CL
AER509SCLA
230V Single Phase 50Hz
30
Page 35
RATING CAPACITY 2.55 kW AIR FLOW RATE 380 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 2.42 2.34 2.23 2.10 1.93
CM 0.77 0.83 0.89 0.97 1.06 21 SHC 1.66 1.62 1.57 1.50 1.42 23 SHC 1.88 1.84 1.79 1.72 1.64
15 25 SHC 2.09 2.05 2.00 1.93 1.85
27 SHC 2.31 2.27 2.21 2.10 1.93 29 SHC 2.42 2.34 2.23 2.10 1.93 31 SHC 2.42 2.34 2.23 2.10 1.93
TC 2.62 2.52 2.39 2.25 2.07
CM 0.79 0.85 0.91 1.00 1.09 21 SHC 1.45 1.41 1.35 1.29 1.20 23 SHC 1.67 1.62 1.56 1.50 1.42
17 25 SHC 1.89 1.83 1.78 1.71 1.63
27 SHC 2.11 2.05 1.99 1.92 1.85 29 SHC 2.33 2.26 2.21 2.14 2.06 31 SHC 2.54 2.47 2.39 2.25 2.07
TC 2.77 2.68 2.55 2.39 2.21
CM 0.83 0.88 0.94 1.03 1.12 21 SHC 1.21 1.18 1.12 1.05 0.98 23 SHC 1.43 1.39 1.34 1.27 1.19
19 25 SHC 1.64 1.60 1.55 1.49 1.40
27 SHC 1.85 1.82 1.76 1.70 1.62 29 SHC 2.05 2.03 1.97 1.91 1.83 31 SHC 2.27 2.25 2.19 2.12 2.05
TC 2.94 2.84 2.71 2.54 2.34
CM 0.85 0.90 0.97 1.06 1.15 23 SHC 1.20 1.16 1.10 1.04 0.96
21 25 SHC 1.40 1.37 1.32 1.25 1.18
27 SHC 1.62 1.59 1.53 1.47 1.39 29 SHC 1.82 1.80 1.75 1.68 1.60 31 SHC 2.04 2.01 1.96 1.90 1.82
TC 3.14 3.00 2.84 2.66 2.47
CM 0.87 0.92 0.99 1.08 1.18
23 25 SHC 1.18 1.13 1.06 1.00 0.93
27 SHC 1.38 1.34 1.28 1.21 1.14 29 SHC 1.58 1.55 1.49 1.42 1.36 31 SHC 1.81 1.77 1.70 1.64 1.57
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
Outdoor Unit
Indoor Unit AFR509CL
AER509SCLA
31
Page 36
RATING CAPACITY 3.3 kW AIR FLOW RATE 490 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 3.13 3.03 2.89 2.71 2.50
CM 1.14 1.21 1.30 1.43 1.56 21 SHC 2.14 2.10 2.03 1.94 1.84 23 SHC 2.43 2.38 2.31 2.22 2.12
15 25 SHC 2.71 2.65 2.58 2.50 2.40
27 SHC 2.99 2.93 2.86 2.71 2.50 29 SHC 3.13 3.03 2.89 2.71 2.50 31 SHC 3.13 3.03 2.89 2.71 2.50
TC 3.39 3.26 3.10 2.91 2.68
CM 1.16 1.25 1.34 1.47 1.60 21 SHC 1.88 1.82 1.75 1.66 1.56 23 SHC 2.16 2.09 2.02 1.94 1.84
17 25 SHC 2.44 2.37 2.30 2.22 2.11
27 SHC 2.72 2.65 2.58 2.49 2.39 29 SHC 3.01 2.93 2.86 2.77 2.66 31 SHC 3.29 3.20 3.10 2.91 2.68
TC 3.59 3.47 3.30 3.10 2.86
CM 1.22 1.29 1.38 1.51 1.64 21 SHC 1.57 1.52 1.45 1.36 1.26 23 SHC 1.85 1.80 1.73 1.64 1.54
19 25 SHC 2.12 2.07 2.00 1.92 1.82
27 SHC 2.39 2.35 2.28 2.20 2.09 29 SHC 2.65 2.63 2.55 2.48 2.37 31 SHC 2.93 2.91 2.83 2.75 2.65
TC 3.80 3.67 3.50 3.29 3.03
CM 1.25 1.32 1.42 1.56 1.69 23 SHC 1.55 1.50 1.43 1.34 1.24
21 25 SHC 1.82 1.77 1.71 1.62 1.52
27 SHC 2.09 2.05 1.98 1.90 1.79 29 SHC 2.36 2.32 2.26 2.17 2.07 31 SHC 2.63 2.60 2.53 2.45 2.35
TC 4.06 3.89 3.67 3.44 3.20
CM 1.27 1.35 1.46 1.59 1.73
23 25 SHC 1.52 1.46 1.38 1.29 1.21
27 SHC 1.78 1.73 1.65 1.56 1.48 29 SHC 2.05 2.01 1.93 1.84 1.76 31 SHC 2.34 2.29 2.20 2.12 2.04
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
Indoor Unit AWR512CL Outdoor Unit AER512SCLA
230V Single Phase 50Hz
32
Page 37
RATING CAPACITY 3.3 kW AIR FLOW RATE 700 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 3.13 3.03 2.89 2.71 2.50
CM 1.14 1.21 1.30 1.43 1.56 21 SHC 2.14 2.10 2.03 1.94 1.84 23 SHC 2.43 2.38 2.31 2.22 2.12
15 25 SHC 2.71 2.65 2.58 2.50 2.40
27 SHC 2.99 2.93 2.86 2.71 2.50 29 SHC 3.13 3.03 2.89 2.71 2.50 31 SHC 3.13 3.03 2.89 2.71 2.50
TC 3.39 3.26 3.10 2.91 2.68
CM 1.16 1.25 1.34 1.47 1.60 21 SHC 1.88 1.82 1.75 1.66 1.56 23 SHC 2.16 2.09 2.02 1.94 1.84
17 25 SHC 2.44 2.37 2.30 2.22 2.11
27 SHC 2.72 2.65 2.58 2.49 2.39 29 SHC 3.01 2.93 2.86 2.77 2.66 31 SHC 3.29 3.20 3.10 2.91 2.68
TC 3.59 3.47 3.30 3.10 2.86
CM 1.22 1.29 1.38 1.51 1.64 21 SHC 1.57 1.52 1.45 1.36 1.26 23 SHC 1.85 1.80 1.73 1.64 1.54
19 25 SHC 2.12 2.07 2.00 1.92 1.82
27 SHC 2.39 2.35 2.28 2.20 2.09 29 SHC 2.65 2.63 2.55 2.48 2.37 31 SHC 2.93 2.91 2.83 2.75 2.65
TC 3.80 3.67 3.50 3.29 3.03
CM 1.25 1.32 1.42 1.56 1.69 23 SHC 1.55 1.50 1.43 1.34 1.24
21 25 SHC 1.82 1.77 1.71 1.62 1.52
27 SHC 2.09 2.05 1.98 1.90 1.79 29 SHC 2.36 2.32 2.26 2.17 2.07 31 SHC 2.63 2.60 2.53 2.45 2.35
TC 4.06 3.89 3.67 3.44 3.20
CM 1.27 1.35 1.46 1.59 1.73
23 25 SHC 1.52 1.46 1.38 1.29 1.21
27 SHC 1.78 1.73 1.65 1.56 1.48 29 SHC 2.05 2.01 1.93 1.84 1.76 31 SHC 2.34 2.29 2.20 2.12 2.04
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
Indoor Unit FCR512CL Outdoor Unit AER512SCLA
33
Page 38
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230V 1-phase 50Hz Rating Conditions
Running Amps. A 0.13 0.28 6.09 6.5 Power Input kW 0.031 0.062 1.287 1.38
Full Load Conditions
Running Amps. A0.13 0.28 7.09 7.5 Power Input
kW 0.031 0.062 1.507 1.60
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23° C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.12 0.24 4.04 4.4
Power Input kW 0.027 0.055 0.858 0.94
Full Load Conditions Running Amps. A 0.12 0.24 4.54 4.9
Power Input
kW 0.027 0.055 0.998 1.08
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19° C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions
: Indoor Air Temperature 32°C D.B. / 23°C W.B. Outdoor Air Temperature 43°C D.B.
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.11 0.24 2.85 3.2
Power Input kW 0.025 0.055 0.6 0.68
Full Load Conditions Running Amps. A 0.11 0.24 3.15 3.5
Power Input kW 0.025 0.055 0.681 0.76
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19° C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43
°C D.B.
Page 39
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V ~ 50Hz Rating Conditions Running Amps. A 0.12 0.24 4.04 4.4
Power Input kW 0.027 0.055 0.858 0.94
Full Load Conditions Running Amps. A 0.12 0.24 4.54 4.9
Power Input kW 0.027 0.055 0.998 1.08
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit AFR509CL Outdoor Unit AER509SCLA
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V ~ 50Hz Rating Conditions Running Amps. A 0.29 0.31 5.9 6.5
Power Input kW 0.070 0.07 1.20 1.38
Full Load Conditions Running Amps. A 0.29 0.31 6.7 7.3
Power Input kW 0.070 0.07 1.47 1.61
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit FCR512CL Outdoor Unit AER512SCLA
35
Page 40
AWR508CL AWR509CL AWR512CL
WARNING
Page 41
37
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
WARNING
Indoor Unit FCR512CL
.
Page 42
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
WARNING
Outdoor Unit
AER508SCLA
AER509SCLA
AER512SCLA
Outdoor Unit
38
Page 43
,

15 cm
min.
15 cm min.
15 cm min.
INDOOR UNIT
Front View
INDOOR UNIT
Tubing length (L)
OUTDOOR UNIT
Elevation difference (H)
Fig. 2
WARNING
Minimum height from floor level
1.5m
Indoor Unit
Wall
Floor level
CAUTION
Fig 2b < Only for AWR >
Page 44
Outdoor unit
Hot air
Heat source
Exhaust fan
Fig. 3
NO
Air intake
Min. 10 cm
Air discharge
Min.
5 cm
Min. 40 cm
Valve side Min. 25 cm
Top View
Air intake
Concrete or equal
About 10 cm
Min. 10 cm
Anchor bolts (4 pcs.)
About 40 cm
2 m
2 m
Ground
Obstacle
Obstacle above
Air discharge
Page 45
Wall
Special mounting screw
Screw
Wall
Page 46
NOTE
WARNING
WARNING
CAUTION
Outdoor
unit
Indoor
unit
L
N
1 2
4
1 2
4
Power supply
220 – 240 V 50Hz
A
B
Ground
Page 47
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes
3 minutes5 minutes
ON OFF ON OFF ON OFFCompressor
ON OFF ON OFF ON OFF
More than 5 minutes
Outdoor fan
Indoor fan
Set speed
T+1 °C
T °Cset temp.
Thermo. OFF
Thermo. OFF
Thermo. ON
Thermo. OFF
Thermo. ON
Thermo. ON
Thermo. ON
Room temp.
Signal from remote control unit
Page 48
NOTE
Room temp.
Cooling operation
T+2 °C
Set temp. T °C
T–1 °C
Monitor zone Both the indoor and outdoor units stop.
Room temp. 15 °C
*Dry A zone
Compressor : FMI (indoor fan) :
Continuous operation L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
*Dry B zone
Compressor : FMI (indoor fan) :
Intermittent operation (ON for 3 minutes and OFF for 9 minutes) L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
Page 49
NOTE
ON ON ON ON
OFFOFF
Set speed
More than
10 minutes
6 minutes
T+1 °C
Indoor heat exch. coil temp.
–1 °C
Compressor
Indoor fan
Room temp.
Thermo. OFF
Thermo. ON
Set temp. T °C
More than
10 minutes
More than
6 minutes
Set speed
*1) *1)
Page 50
8-4. Outdoor Fan Speed Control (for model AER512SCLA)
Low ambient fan speed control
This function protects the compressor from being damaged due to flowback of the liquid refrigerant to the
compressor when the outdoor temperature is very low.
When the air temp. thermistor (TH) on the outdoor unit detects a change in temperature, the controller (POW-
CL128E) on the electrical component box activates to control the fan speed automatically.
If the outdoor temperature falls below 14°C, the fan speed switches to MED.
If the outdoor temperature falls below –1°C, the fan speed switches to LOW.
46
Outdoor
temperature
14°C
–1°C
Fan speed Fan motor output
HIGH
MEDIUM
LOW
7 1 (YEL-BRN
)
3 1 (WHT-BRN
)
5 1 (VLT-BRN)
(Line voltage 220-240V)
1 2
1. Regardless of outdoor temperature, outdoor fan motor operates at first at HIGH speed for
23 ± 5 seconds to give the motor an initial boost.
2. When the fan speed switches, the controller terminal's location where line voltage comes
out (
) shifts accordingly.
NOTE
Page 51
9. REFRIGERANT R407C : SPECIAL PRECAUTIONS WHEN SERVICING UNIT
9-1. Characteristics of new refrigerant R407C
9-1-1.What is new refrigerant R407C
R407C is a new refrigerant that contains three types of non-azeotropy-type mixed refrigerant which does not adversely affect the Earth's ozone layer. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant R22
9-1-2.Components (mixing proportions)
HFC32 (23%) / HFC125 (25%) / HFC134a (52%)
9-1-3.Characteristics
Less toxic, more chemically stable refrigerant.
Composition of refrigerant R407C changes whether it is in gaseous phase or liquid phase. Thus, when there is a
refrigerant leak the basic performance of the air conditioner may be degraded because of a change in composition of the remaining refrigerant.
Therefore, do not add new refrigerant.
Instead, recover the remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified amount of refrigerant with the new refrigerant at its normal mixed composition state (liquid phase).
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or liquid
phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in gaseous state.
Thus, always charge the refrigerant while it is in the liquid phase.
Ether-type oil is used for the compressor oil for R407C-type units, which is
different from the mineral oil used for R22. Thus more attention to moisture prevention and faster replacement work compared with conventional models are required.
9-2. Checklist before servicing
Tubing precautions
Refrigerant R407C is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation.
No addition of compressor oil for R407C
No additional charge of compressor oil is permitted.
No use of refrigerant other than R407C
Never use a refrigerant other than R407C.
If refrigerant R407C is exposed to fire
Through welding, etc., toxic gas may be released when R407C refrigerant is exposed to fire. Therefore, be sure to provide ample ventilation during installation work.
Caution in case of R407C leak
Check for possible leak points with the special leak detector for R407C. If a leak occurs inside the room, immediately provide thorough ventilation.
CAUTION
47
Page 52
9-3. Tools specifically for R407C
For servicing, use the following tools for R407C
The above tools specifically for R407C must not be used for R22. Doing so will
cause malfunction of the unit.
For the above vacuum pump (✽1, ✽2) and vacuum pump adapter (✽3) , those for
R22-type units can be used for R407C-type. However, they must be used exclusively for R407C and never alternately with R22.
9-4. For tubing installation procedures
When the tubes are connected,
always apply HAB oil on the flare portions to improve the sealing of
tubing.
The following is the HAB oil generally used:
Esso: ZERICE S32
For details on tubing installation procedures, refer to the installation manuals attached to the indoor unit and outdoor unit.
48
Tool Distinction Tool Name
• Gauge manifold
• Charging hose
• Gas leak detector
• Refrigerant cylinder
• Charging cylinder
Tools specifically for R407C • Refrigerant recovery unit
• Vacuum pump with anti-reverse flow (✽1) (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.)
• Vacuum pump (✽2) ..... can be used if the following adapter is attached.
• Vacuum pump adapter (reverse-flow prevention adapter) (✽3). (Solenoid valve-installed adapter attached to a conventional vacuum pump.)
• Electronic scale for charging refrigerant
• Flare tool
• Bender
Tools which can be commonly • Torque wrench used for R22 and R407C • Cutter, Reamer
• Welding machine, nitrogen gas cylinder
CAUTION
NOTE
Page 53
9-5. In case of compressor malfunction
Should the compressor malfunction, be sure to replace compressor as quickly as
possible.
Use only the tools indicated exclusively for R407C. ➞ See "10-3. Tools specifically
for R407C".
9-5-1.Procedure for replacing compressor
(1) Recovering refrigerant
• Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the refrigerant recovery unit for R407C.
• Do not reuse the recovered refrigerant, since will contain impurities.
(2) Replacing compressor
• Soon after removing pinched pipes of both discharge and suction tubes of the new compressor, replace it quickly.
(3) Checking for sealing
• Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R407C. Also do not use oxygen or any flammable gas.
(4) Evacuation
Use a solenoid valve-installed vacuum pump
so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back.
• The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly.
• When using a vacuum pump with exhaust air volume more than 25L/min. and ultimate vacuum pressure rate of 0.05Torr:
49
CAUTION
(1). Recovering refrigerant
OK
(2). Replacing compressor
OK
(3). Checking for sealing
OK
(4). Evacuation
OK
(5). Recharging
Standard time of evacuation
Length of tubing Less than 10 m More than 10 m
Time More than 10 min. More than 15 min.
Page 54
Valve
Valve
Single valve
Charge the liquid refrigerant with the cylinder in the up-side-down position.
Single valve (with siphon tube)
Charge with the cylinder in the normal position.
Liquid
Liquid
50
Configurations and characteristics of cylinders
Charging
cylinder
Open
Refrigerant
cylinder
Liquid
NO!
Fig. 2
Fig. 1
Fig.3
(5) Recharging
Be sure to charge the specified amount of refrigerant in liquid state
using the service port of wide tube service valve. The proper amount is listed on the unit's nameplate.
When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation.
Never charge a large amount of liquid refrigerant at once to the unit. This may cause damage to the compressor.
• When charged with a refrigerant cylinder, use the electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change. Thus,
do not use the refrigerant if the amount in the refrigerant cylinder is less than 20%.
Also, charge the minimum necessary amount to the cylinder before using it for charging the air conditioning unit.
Example:
In case of charging refrigerant to a unit requiring
0.76Kg using a capacity of 10Kg-cylinder, the minimum necessary amount for the cylinder is:
0.76 + 10 x 0.20 = 2.76Kg
For the remaining refrigerant, refer to the instructions of the refrigerant manufacturer.
• If using a charging cylinder, transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder.
Prepare an evacuated charging cylinder beforehand.
To prevent the composition
of R407C from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant. (Fig. 3)
Do not use the refrigerant if the amount in the charging cylinder is less than 20%.
CAUTION
CAUTION
Page 55
9-6. In case refrigerant is leaking
Never attempt to charge additional refrigerant when refrigerant has been leaking
from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant.
(1) Detecting Leaks
• Use the detector for R407C to locate refrigerant leak points.
(2) Recovering refrigerant
• Never release the gas to the atmosphere, recover residual refrigerant using the refrigerant recovery unit for R407C, instead.
• Do not reuse the recovered refrigerant because its composition will have been altered.
(3) Welding leaking points
• Confirm again that no residual refrigerant exists in the unit before starting welding.
• Weld securely using flux and wax for R407C.
• Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen (N2) in the refrigerant circuit of the unit. Leave ends of tubes open during welding.
(4) Checking for sealing
• Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R407C. Also do not use oxygen or any flammable gas.
(5) Evacuation
Use a solenoid valve-installed vacuum pump
so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back.
• The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly.
• When using a vacuum pump with exhaust air volume more than 25L/min. and ultimate vacuum pressure rate of 0.05Torr:
51
(2). Recovering refrigerant
OK
(3). Welding leaking points
OK
(4). Checking for sealing
OK
(5). Evacuation
OK
(6). Recharging
(1). Detecting leaks
OK
CAUTION
Standard time of evacuation
Length of tubing Less than 10 m More than 10 m
Time More than 10 min. More than 15 min.
Page 56
(6) Recharging
Be sure to charge the specified amount of refrigerant in liquid state
using the service port of wide tube service valve. The proper amount is listed on the unit's nameplate.
When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation.
Never charge a large amount
of liquid refrigerant at once to the unit. This may cause damage to the compressor.
• When charged with a refrigerant cylinder, use the electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change. Thus,
do not use the refrigerant if the amount in the refrigerant cylinder is less than 20%.
Also, charge the minimum necessary amount to the
cylinder before using it for charging the air conditioning unit.
Example:
In case of charging refrigerant to a unit requiring
0.76Kg using a capacity of 10Kg-cylinder, the minimum necessary amount for the cylinder is:
0.76 + 10 x 0.20 = 2.76Kg
For the remaining refrigerant, refer to the instructions of the refrigerant manufacturer.
• If using a charging cylinder, transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder.
Prepare an evacuated charging cylinder beforehand.
To prevent the composition
of R407C from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant. (Fig. 6)
Do not use the refrigerant if the amount in the charging cylinder is less than 20%.
52
CAUTION
CAUTION
Valve
Valve
Single valve
Charge the liquid refrigerant with the cylinder in the up-side-down position.
Single valve (with siphon tube)
Charge with the cylinder in the normal position.
Liquid
Liquid
Fig. 4
Fig. 5
Configurations and characteristics of cylinders
Charging
cylinder
Open
Refrigerant
cylinder
Liquid
NO!
Fig. 6
Page 57
9-7. Charging additional refrigerant
9-7-1.When tubes are extended
• Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit.
Charge additional refrigerant in liquid state.
Never charge additional refrigerant if refrigerant is leaking from the unit. Follow
instructions given in "10-6. In case refrigerant is leaking" and completely carry out repairs. Only then should you recharge the refrigerant.
9-8. Retro-fitting existing systems
9-8-1 Use of existing units
Never use new refrigerant R407C for existing units which use R22.
This will cause the air conditioner to
operate improperly and may result in a hazardous condition.
9-8-2 Use of existing tubing
• If replacing an older unit that used refrigerant R22 with a R407C unit,
do not use its existing tubing
. Instead,
completely new tubing must be used.
53
CAUTION
Page 58
Outdoor
unit
Indoor
unit
Power supply : Single phase 220–240V ~ 50Hz
Ground
Ground
Inter–unit power wiring
Power plug (Local supply)
L
1 2
4
1 2
4
N
WARNING
Page 59
NO
Measure insulation resistance of electrical parts in outdoor unit.
NO
Set circuit breaker to OFF.
*
Measure insulation resistance of electrical parts in indoor unit.
1
Remove inter-unit wires from terminal plate in outdoor unit.
Measure insulation resistance of outdoor unit.
2
Remove inter-unit wires from terminal plate in indoor unit. Then, pull the power plug out of the wall outlet
Measure insulation resistance of indoor unit.
Insulation of outdoor unit is defective.
Insulation of indoor unit is defective.
WARNING
11 22
44
Outdoor
unit
1
Indoor
unit
22
Inter–unit wiring
Circuit breaker
Ground
Ground
Power plug (Local supply)
Wall outlet (receptacle)
Single phase 220–240V ~ 50Hz
L
N
Page 60
Measure resistance of primary and secondary winding. (TR1)
YES
NO
OPERATION selector switch is set in ON position.
Set OPERATION selector switch to ON.
Indoor PCB Ass'y is defective.
NO
Check power supply. Power is being supplied to the
indoor unit.
Circuit breaker is tripped.
Power failure
Reset breaker.
Wait for recovery or contact power company.
Replace with suitable one (larger capacity).
NO
Check capacity of circuit breaker. Capacity of circuit breaker is
suitable.
Measure resistance of outdoor fan motor winding.
Measure resistance of compressor motor winding.
Page 61
Timer is turned ON. Check to see if or is displayed on remote control
YES
Cancel the timer mode.
ON
OK
OK
Check fuse on indoor PCB Ass'y for continuity. (F)
Check operation lamp to see if light is ON.
Light is OFF
Measure resistance of primary and secondary winding of transformer. (TR)
Indoor PCB Ass'y is defective.
OK
OK
Measure resistance of indoor and/or outdoor fan motor winding. (FM)
Measure resistance of compressor motor winding. (CM)
OK
Measure coil resistance of power relay in outdoor unit. (PR)
Replace the fuse.
If fuse has been blown,
OK
Try to run with another remote control unit.
First remote control unit is defective.
Check for residue buildup on transmitter of remote control unit.
Check for residue buildup on remote control receiver on front of indoor unit.
Clean transmitter.
Clean receiver.
Page 62
OK
Measure coil resistance of power relay.
Check indoor PCB Ass'y.
(PR)
OK
NO
Is room temperature too low ?
Try to lower setting temperature by temperature setting button ( button).
Outdoor unit still does not run.
Remote control unit is defective.
Try to run using another remote control unit.
Page 63
Fan cannot be turned.
OK
Check fan rotation. Turn fan gently once or twice by hand.
Check fan casing foreign matter on inside.
Fan motor burnout or foreign matter in bearings.
Remove foreign matter or repair.
Repair or replace.
Measure resistance of outdoor fan motor winding.
Check fan motor capacitor.
Fan cannot be turned.
OK
Check fan rotation. Turn fan gently once or twice by hand.
Check fan casing foreign matter on inside.
Fan motor burnout or foreign matter in bearings.
Remove foreign matter or repair.
Repair or replace.
Measure resistance of indoor fan motor winding.
Check fan motor capacitor.
Page 64
Measure resistance of flap motor winding.
Check compressor motor capacitor.
Measure resistance of compressor motor winding.
Measure resistance of power relay. (PR)
NO
YES
YES
Overload relay is working.
(Either OLR T or OLR A)
YES
Temperature of compressor is abnormally high.
Refrigerant gas shortage. Charge refrigerant gas (R407c).
Rotor may be locked up.
(C1)
Measure Power supply voltage. The voltage is too low.
No
Page 65
NO
NO
Set temperature is suitable.
Set temperature to higher value using temperature setting buttons of the remote control unit.
Remote control unit is placed where it can detect room temperature properly.
Change position of remote control unit.
Air filter is clogged.
NO
YES
Temperature difference is small.
YES
Temperature difference between suction and discharge air is large enough (approx. 10 deg. or more).
Possibility of gas shortage.
YES
Check position of remote control unit. Cool air from air conditioner reaches position directly.
Change position of remote control unit.
Wide and narrow tubes between indoor unit and outdoor unit are insulated.
Insulate both wide and narrow tubes separately and then tape together.
Measure temperature of suction and discharge air of air conditioner.
Charge refrigerant gas (R407c).
Check for clogging of air filter.
Fan speed is set to LOW.
Clean filter.
Set fan speed to either HIGH or MEDIUM.
Review cooling load estimate, if performance of air conditioner is normal.
Reduce cooling load or replace the air conditioner with larger capacity.
Page 66
NOTE
Temperature sensor
Lead wires
Thermistor Structure
NOTE
Operation lamp on front side of indoor unit is flashing on and off. (*)
YES
Replace thermistor.
Thermistor (TH1 ) is defective.
YES
Page 67
NOTE
Ground
power plug (Local supply)
probe
Insulation tester
Terminal plate
Copper tube or metallic part
Clip
Insulation tester
Probe
Copper tube or metallic part
Clip
Insulation tester
Probe
Clip
Insulation tester
Probe
Metallic part
From fan motor, compressor and other parts
NOTE
Page 68
Fuse
PCB Ass’y
Fuse
Compressor motor capacitor
Fan motor capacitor
Multimeter
Page 69
65
12-1. Removing Air Intake Grille
(1) Hold both ends and pull forward to open the
air intake grille. (Fig. 1)
(2) Remove the metal clips connecting the unit and the
grille. First, with a screwdriver, loosen the * marked screw a little at the right side clip (DO NOT loosen it too much, otherwise, the screw and small metal parts will fall off inside.), then press
on the stopper and pull off. (Fig. 2) (3) Do the same procedure for the left metal clip. (4) Unlatch the 2 tabs on the lower part of the grille to
take it off completely.
12. DISASSEMBLY PROCEDURE FOR INDOOR UNIT
IMPORTANT! Please Read Before Starting
Safety precautions for servicing the CEILING-MOUNTED indoor unit
Center latch
Air intake grille
Metal clip
*
Air intake grille
Unit
For Floor Installation
Fig.1
Fig.2
Before attempting to replace heavy and bulky parts such as the evaporator and fan motor, disconnect the indoor unit from the system and place it on the floor. Refer to the steps given below.
When checking or servicing the air intake grille, side panels, or electrical component box, first check that power is completely disconnected. Pay utmost care that your working platform is stable enough. Also, do not drop any replaced parts and tools on the floor.
Page 70
66
12-2. Removing Side Panels
(1) Remove the 3 screws attaching the left side panel.
(Fig. 3) (2) Note the position of the hook on the inside of the
left side panel. To disengage the hook from the slot,
slide down the panel for removal. (Fig. 3) (3) Do the same procedure for the right side panel.
12-3. Access and Removal of
Electrical Component Box
(1) Remove the front screw with a screwdriver. (Fig. 4) (2) Slide the lid out and up. (Fig. 4) (3) Disconnect the wiring as necessary. (4) Remove the 4 screws, then pull out the electrical
component box. (Fig. 5)
Side panel
Tapping screws (4 × 10 mm)
Hook
Hook
Slot
Screw
Screw
Electrical component box
Screw
Connectors
Connectors
Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect the power or turn off circuit breaker before you start checking or servicing.
WARNING
Fig.3
Fig.4
Fig.5
Page 71
67
12-4. Removing Flap Motor
(1) Remove the 3 screws used to mount the top panel.
(Fig. 6) (2) While unlatching the 2 tabs inside the back of the
top panel, lift the top panel diagonally in the
direction of the arrow.(Fig. 6) (3) Remove the 2 screws to pull off the flap motor.
The arm and cam come off together with the motor.
(Fig. 7)
12-5. Removing Evaporator (=Indoor Heat Exchange Coil)
(1) Remove the 7 screws used to mount the blades.
(Fig. 8) (2) Lift the blades in the direction of the arrow.(Fig. 8)
Top panel
Flap motor
Screw
Blade
Arm
Cam
Screw
Flap motor
Screw
Blades
Fig.6
Fig.7
Fig.8
Page 72
68
(3) Remove the 6 screws of the front panel and pull it
toward you. (Fig. 9)
(4) Remove the 2 screws used to mount the
evaporator. (Fig. 10) (5) Remove the rubber cap to pull the thermistor out of
the evaporator. (Fig. 10) (6) Cut the plastic clamp securing the drain hose to the
front fan casing. (Fig. 10)
(7) The evaporator is built into the drain pan. Pull out
the drain pan together with the evaporator in the
direction of the arrow. (Fig. 10)
The foamed polystyrene drain pan is fragile: DO NOT apply excessive force when removing it.
(8) The evaporator can be removed by sliding it out
from the drain pan in the direction of the arrow.
(Fig. 11)
Front panel
Screw
Plastic clamp
Drain pan
Screw
Rubber cap
Thermistor
Drain hose
Front fan casing
Drain pan
Evaporator (Indoor coil)
Mounting plate
Mounting plate
Fig.9
Fig.10
Fig.11
IMPORTANT
Page 73
69
12-6. Removing Fan and Fan Motor
(1) Unlatch the 2 hooks on each side to take off the
front fan casing. (Fig. 12)
(2) Remove the 2 screws attaching the rear fan casing
and then pull the fan casing out.
(3) Insert a hex wrench in the fan boss and turn it
counterclockwise to loosen the centrifugal fan.
The fan can be removed by sliding it to the left.
(Fig. 14)
(4) Remove the 4 bolts to remove the fan motor from
the frame. (Fig. 15)
Hook
Hook
Front fan casing
Rear fan casing
Hex wrench (3mm or 7/64")
Centrifugal fan
Bolts (M6)
Fan motor
Frame
Fig.12
Fig.13
Fig.14
Fig.15
Page 74
Page 75
Contents
Page
Features............................................................................................................ 2
Product Information........................................................................................ 3
Alert Symbols.................................................................................................. 3
Installation Location........................................................................................ 4
Electrical Requirements.................................................................................. 4
Safety Instructions .......................................................................................... 4
Names of Parts................................................................................................ 5
Using the Remote Control Unit ................................................................... 10
Operation with the Remote Control Unit ................................................... 12
1. Operation ......................................................................................... 12
2. Adjusting the Fan Speed................................................................ 13
3. Night Setback Mode ...................................................................... 14
Special Remarks ........................................................................................... 15
Setting the Timer........................................................................................... 16
Using the 1-Hour OFF Timer........................................................................ 18
Adjusting the Airflow Direction ................................................................... 19
Operation without the Remote Control Unit.............................................. 20
Care and Cleaning......................................................................................... 20
Troubleshooting ............................................................................................ 23
Tips for Energy Saving ................................................................................ 23
Product Information
If you have problems or questions concerning your Air Conditioner, you will need the following information. Model and serial numbers are on the nameplate on the bottom of the cabinet.
Model No.
Serial No.
Date of purchase
Dealer’s address
Phone number
DECLARATION OF CONFORMITY
This product is marked «
» as it satisfies EEC Directive No. 89/336/ EEC, 73/23/EEC, 93/68/EEC and 92/31/EEC. This declaration will become void in case of mis-usage and/or from non observance though partial of Manufacturer’s installation and/or operating instructions.
Alert Symbols
The following symbols used in this manual, alert you to potentially dangerous conditions to users, service personnel or the appliance:
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
3OI-859-03EG
Page 76
Installation Location
We recommend that this air conditioner be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the unit.
Before installation, check that the voltage of the electric supply in your home or office is the same as the voltage shown on the nameplate.
Do not install this air conditioner where there are fumes or flammable gases, or in an extremely humid space such as a greenhouse.
Do not install the air conditioner where excessively high heat­generating objects are placed.
Avoid:
To protect the air conditioner from heavy corrosion, avoid installing the outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa.
Electrical Requirements
1. All wiring must conform to the local electrical codes. Consult your
dealer or a qualified electrician for details.
2. Each unit must be properly grounded with a ground (or earth) wire
or through the supply wiring.
3. Wiring must be done by a qualified electrician.
Safety Instructions
Read this Instruction Manual carefully before using this air conditioner. If you still have any difficulties or problems, consult your dealer for help.
This air conditioner is designed to give you comfortable room conditions. Use this only for its intended purpose as described in this Instruction Manual.
Never use or store gasoline or other flammable vapor or liquid near the air conditioner — it is very dangerous.
This air conditioner has no ventilator for intaking fresh air from outdoors. You must open doors or windows frequently when you use gas or oil heating appliances in the same room, which consume a lot of oxygen from the air. Otherwise there is a risk of suffocation in an extreme case.
CAUTION
Do not turn the air conditioner on and off from the power mains switch. Use the ON/OFF operation button.
Do not stick anything into the air outlet of the outdoor unit. This is dangerous because the fan is rotating at high speed.
Do not let children play with the air conditioner.
Do not cool the room too much if babies or invalids are present.
4 OI-859-04EG
Page 77
Names of Parts
NOTE
This illustration is based on the external view of a standard model. Consequently, the shape may differ from that of the air conditioner which you have selected.
This air conditioner consists of an indoor unit and an outdoor unit. You can control the air conditioner with the remote control unit.
Air Intake Air from the room is drawn into this section and passes through
air filters which remove dust.
Air Outlet Conditioned air is blown out of the air conditioner through the
air outlet.
Remote Control Unit The wireless remote control unit controls power ON/OFF,
operation mode selection, temperature, fan speed, timer setting, and air sweeping.
Refrigerant Tubes The indoor and outdoor units are connected by copper tubes
through which refrigerant gas flows.
Drain Hose Moisture in the room condenses and drains off through this
hose.
Outdoor (Condensing) Unit The outdoor unit contains the compressor, fan motor, heat
exchanger coil, and other electrical components.
INDOOR UNIT
Air intake
Air outlet
Remote control unit
Drain hose
Refrigerant tubes
OUTDOOR UNIT
Air outlet
5OI-859-05EG
Page 78
Unit Display and Operation Selector
REMOTE CONTROL
receiver
This section picks up infrared signals from the remote control unit (transmitter).
Operation selector
ON position This position is for operating the air conditioner with the
wireless remote control unit. Set the selector normally in this position.
OFF position Switch the selector to the OFF position if you are not going to
use the air conditioner for a few days or longer.
The OFF position does not disconnect the power. Use the main power switch to turn off power completely.
TEST position This position is used only when servicing the air conditioner.
CAUTION
Do not set at the TEST position for normal operation.
OPERATION lamp This lamp lights when the system is in the continuous DRY and
COOL mode.
TIMER lamp This lamp lights when the system is being controlled by the
timer.
OPERATION
TIMER
ON 
OFF
TEST
OPERATION lamp TIMER lamp
Operation selector
REMOTE CONTROL receiver
INDOOR UNIT
IMPORTANT
Avoid using radio equipment such as mobile phone near (within 1 m) the indoor unit. Some radio equipment may cause malfunction of the unit.
If the trouble happens, disconnect power and restart the air conditioner after a few minutes.
6 OI-859-06EG
Page 79
Remote Control Unit (Display)
ON OFF
1HR.
C
SET TEMP
(1) Operation mode
COOL .......................................
MILD DRY................................
(2) Fan speed
Automatic operation ..............
HIGH ........................................
MEDIUM..................................
LOW.........................................
ON
Displayed when transmitting data
Displayed when setting temperature
Displayed when temperature is shown
Displayed when the temperature setting is at the upper or lower allowable limit
Displayed when setting timer
C
OFF
1HR.
Symbols
Displayed when main unit sensor is in use
(3) Set temperature
16–30°C
When set to 28 °C...........
Current temprature
indication .........................
(4) Timer
24-hour clock with ON/OFF
Program Timer........................
24-hour ON Timer ..................
24-hour OFF Timer.................
1-hour OFF Timer...................
(5) NIGHT SETBACK ....................
(6) Confirmation of
transmission ...........................
(7) Flap angle indication .............
(8) Sweep indication....................
7OI-859-07EG
Page 80
Remote Control Unit
NOTE
The illustration above pictures the remote control unit after the cover has been lowered and removed.
Transmitter When you press the buttons on the remote control unit, the mark
appears in the display to transmit the setting changes to the receiver in the air conditioner.
Sensor A temperature sensor inside the remote control unit senses the room
temperature.
Display Information on the operating conditions is displayed while the remote
control unit is switched on. If the unit is turned off, only the mode that was set previously is still displayed.
NIGHT SETBACK
button
For details, see ‘‘Night Setback Mode’’. When you press this button in the COOL mode, the
mark appears in the display, and the remote
control unit will automatically adjust the set temperature to save energy.
TEMP. setting buttons Press the
button to increase the set temperature.
Press the
button to reduce the set temperature.
ON/OFF operation
button
This button is for turning the air conditioner on and off.
Timer setting buttons First, press the PROGRAM button to select the mode you want.
Each time you press the ‘‘HH’’ button, the hours advance by one. Each time you press the ‘‘MM’’ button, the minutes advance by one.
PROGRAM button For details, see ‘‘Setting the Timer’’.
Press this button to select the mode you want to program.
AIR CONDITIONER
Transmitter
Display
ON/OFF operation button
FLAP button
TEMP. setting buttons
1 HR. TIMER button
NIGHT SETBACK button
MODE selector button
Battery compartment (Pull off the cover to expose the batteries.)
FAN SPEED
selector button
ACL button
Program button
A/C SENSOR button
Timer setting buttons
ON I /OFF
1HR.
TIMER
TEMP.
MODE
FLAP
FAN SPEED
SELECT
HH
TIMER
SELECT
MM
TIME SET
NIGHT
SETBACK
BATTERIES
ACL
A/C
SENSOR
OFF ON
CLOCK
ON OFF
1HR.
C
SET TEMP
AIR CONDITIONER
A
(Cover closed)
Sensor
TIMER SELECT button
8 OI-859-08EG
Page 81
Remote Control Unit (continued)
NOTE
The remote control unit sends the temperature signal to the air conditioner regularly at three minute intervals. If the signal from the remote control unit stops for more than ten minutes due to the loss of the remote control unit or other trouble, the air conditioner will switch to the temperature sensor which is built into the indoor unit and control the room temperature. In these cases, the temperature around the remote control unit may differ from the temperature detected at the air conditioner’s position.
TIMER SELECT button No display : The timer does not operate.
: The air conditioner stops at the set time. : The air conditioner starts at the set time. : The air conditioner stops and starts, or starts and stops,
at the set times every day.
MODE selector button
(COOL)
(DRY)
Use this button to select COOL or DRY mode.
: The air conditioner makes the room cooler. : The air conditioner reduces the humidity in the room.
FLAP button Press this button either to select to set the airflow direction to one of
the six possible positions manually, or to select the sweep function, which moves the flap up and down automatically.
: The airflow direction can be set manually. (six positions) : The flap moves up and down automatically.
NOTE
To switch to the sweep function ( ) when in the manual ( ) mode, hold down the FLAP button.
FAN SPEED selector
button
: The air conditioner automatically decides the fan speeds. : High fan speed : Medium fan speed : Low fan speed
1 HR. TIMER button
(1-HOUR OFF TIMER)
: When you press this button, regardless of whether the unit
is operating or stopping, the unit operates for one hour and then shuts down.
ACL button
(ALL CLEAR)
Puts the remote control unit into pre-operation status. Always press this button after replacing the batteries.
A/C SENSOR button When you press this button (use a small-tipped object such as a
ballpoint pen), the
mark will appear at the display. And the room temperature is detected by the sensor which is built into the indoor unit and the air conditioner is controlled accordingly.
NOTE
If the remote control is located near a heat source, such as a space heater or in direct sunlight, press the A/C SENSOR button to switch to the sensor on the indoor unit.
OFF
ON
1HR.
9OI-859-09EG
Page 82
Using the Remote Control Unit
How to Install Batteries
1. Slide the cover in the direction
indicated by the arrow and remove it.
2. Install two AAA alkaline batteries. Make sure the batteries point in the direction marked in the battery compartment.
3. Use a thin object such as the tip of a pen to press the ACL button.
NOTE
The batteries last about six months, depending on how much you use the remote control unit. Replace the batteries when the remote control unit’s display fails to light, or when the remote control cannot be used to change the air conditioner’s settings.
Use two fresh leak-proof type-AAA alkaline batteries.
In replacing batteries, follow the instructions as mentioned in the sub-section ‘‘How to Install Batteries’’.
If you do not use the remote control unit more than 1 month, take out the batteries.
How to Use the Remote
Control Unit
When using the remote control unit, always point the unit’s transmitter head directly at the air conditioner’s receiver.
Remote Control Unit
Installation Position
The remote control unit may be operated either from a non-fixed position or from a wall-mounted position. To ensure that the air conditioner operates correctly, DO NOT install the remote control unit in the following places:
DO NOT
In direct sunlight
Behind a curtain or other places where it is covered
More than 8 m away from the air conditioner
In the path of the air conditioner’s airstream
Where it may become extremely hot or cold
Where it may be subject to electrical or magnetic noise
Where there is an obstacle between the remote control unit and air conditioner (since a check signal is sent from the remote control unit every 3 minutes)
ACL button
Air conditioner (Indoor unit)
Remote control unit
Receiver
(Transmitter head)
10 OI-859-10EG
Page 83
Using the Remote Control Unit (continued)
Mounting the Remote
Control Unit
Mounting on a wall A. Removable mounting
1) Momentarily hold the remote control unit at the desired mounting position.
2) Confirm that the air conditioner responds correctly when you press keys on the remote control from that position.
3) After confirming correct operation, use a screwdriver to screw the mounting screw into the wall.
4) Hang the remote control unit from the mounting screw.
B. Non-removable mounting
1) Momentarily hold the remote control unit at the desired mounting position.
2) Confirm that the air conditioner responds correctly when you press keys on the remote control from that position.
3) After confirming correct operation, use a screwdriver to screw the mounting screw into the wall.
4) Remove the batteries of the remote control unit.
5) Use a screwdriver to screw the remote control unit securing screw into the wall through the hole in the battery compartment.
6) Replace the batteries.
7) Again confirm that the remote control unit operates correctly.
(Packed in the indoor unit)
(Packed in the indoor unit)
Removable mounting Non-removable mounting
Wall Wall
11OI-859-11EG
Page 84
Operation with the Remote Control Unit
1. Operation
NOTE
Check that the circuit breaker on the power panel is turned on and that the operation selector of the indoor unit is in the ON position.
Press the setting buttons as described below and change the settings as desired.
STEP 1 Set the MODE selector button to COOL or DRY.
For cooling operation For dehumidifying operation
STEP 2 To start the air conditioner, press the ON/OFF
operation button.
STEP 3 Press the TEMP. setting buttons to change the
temperature setting to the desired temperature.
Adjustable temperature range:
30 °C max. 16 °C min.
STEP 4 Set the FAN SPEED selector button to the setting
you want.
NOTE
If the fan speed is set to (Automatic), the fan speed switches automatically, according to the difference between the actual room temperature and the temperature setting.
STEP 5 Press the FLAP button and set the airflow direction
as desired. (Refer to ‘‘Adjusting the Airflow Direction’’ on page
19.)
To stop the air conditioner, press the ON/OFF operation button again.
ON I /OFF
1HR.
TIMER
TEMP.
MODE
FLAP
FAN SPEED
SELECT
HH TIMER
SELECT
MM
TIME SET
NIGHT
SETBACK
BATTERIES
ACL
A/C
SENSOR
OFF ON
CLOCK
HR.
C
SET TEMP
1
AIR CONDITIONER
A
STEP 5
STEP 1
STEP 4
STEP 3
STEP 2
12 OI-859-12EG
Page 85
Operation with the Remote Control Unit (continued)
NOTE
Choose the best position in the room for the remote control unit, which also acts as the sensor for room comfort and transmits the operating instructions. Once you’ve found this best position, always keep the remote control unit there.
This appliance has a built-in 3-minute time delay circuit to ensure reliable operation. When the operation button is pressed, the compressor will start running within three minutes. In the event of power failure, the unit will stop. When the power is restored, the unit will restart automatically after three minutes.
2. Adjusting the Fan Speed
A. Automatic Simply set the FAN SPEED selector to the position.
A microcomputer in the air conditioner automatically controls the fan speed when the
mode is selected. When the air conditioner starts operating, the difference between the room temperature and the set temperature is detected by the microcomputer which then automatically switches the fan speed to the most suitable level.
Cooling and DRY mode:
When difference between room temperature and set temperature is
FAN SPEED
2 °C and over High Between 2 °C and 1 °C Medium Below 1 °C Low
NOTE
The above table assumes that the sensor on the remote control is being used. If the sensor on the indoor unit is being used (the
indicator is on), actual operation may differ slightly from the operation described in the table. (Refer to ‘‘A/C SENSOR button’’ on page 9.)
B. Manual If you want to adjust fan speed manually during operation, just set the
FAN SPEED selector as desired. [
, ,or ]
13OI-859-13EG
Page 86
Operation with the Remote Control Unit (continued)
3. Night Setback Mode
Night Setback Mode is used for saving energy.
Press the NIGHT SETBACK button while operation. The
mark appears in the display.
To release the night setback function, press the NIGHT SETBACK button again.
In Cooling and DRY Mode:
(
and )
ON I /OFF
1HR.
TIMER
TEMP.
MODE
FLAP
HH TIMER
SELECT
NIGHT
SETBACK
OFF ON
CLOCK
HR.
C
SET TEMP
1
AIR CONDITIONER
A
When the night setback mode is selected, the air conditioner automatically raises the temperature setting 1 °C when 30 minutes have passed after the selection was made, and then another 1 °C after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed.
Setting temperature
Press the NIGHT SETBACK button
1°C
1°C
30 min. 30 min.
Time
14 OI-859-14EG
Page 87
Special Remarks
‘‘DRY’’ ( ) Operation
How it works?
Once the room temperature reaches the level that was set, the unit repeats the cycle of turning on and off automatically.
During DRY operation, the fan speed is automatically set to LOW or VERY LOW; the fan speed then switches back and forth between LOW (for 20 seconds) and VERY LOW (for 10 seconds).
‘‘DRY’’ operation is not possible if the indoor temperature is 15 °C or less.
Power failure
during operation
In the event of power failure, the unit will stop. When the power is resumed, the unit will restart automatically after three minutes.
Clicking Sound
Clicking sound is
heard from the air
conditioner
In cooling operation, any plastic parts may expand or shrink due to a sudden temperature change. In this event, a clicking sound may occur. This is normal, and the sound will soon disappear.
Remote Control Unit
The remote control unit sends the setting condition to the air conditioner regularly at three minute intervals.
15OI-859-15EG
Page 88
Setting the Timer
1. How to set the present time
(Example) To set to 21:10
2. How to set the OFF time (Example) To stop the air conditioner at 23:30
ON I /OFF
MODE
FLAP
FAN SPEED
SELECT
HH TIMER
SELECT
MM
TIME SET
NIGHT
SETBACK
BATTERIES
ACL
A/C
SENSOR
OFF ON
CLOCK
Operation Indication
1. Press the Program button (
OFF ON
CLOCK
)
three times.
The time indication alone flashes.
2.
Press the HH button until 21 is displayed.
Press the MM button until 10 is displayed.
The display will auto­matically stop flashing except for the ‘‘:’’ symbol after 10 sec.
OFF
1. Press the Program button (
OFF ON
CLOCK
)
once.
The timer
OFF
and
time indications flash.
2.
Press the HH button until 23 is displayed.
Press the MM button until 30 is displayed.
The display will change automatically back to show the present time after 10 sec.
3. Press the ON/OFF button to start the air conditioner.
The present time is displayed.
4. Press the TIMER SELECT button to set OFF time.
The present time and
OFF
are displayed.
16 OI-859-16EG
Page 89
Setting the Timer (continued)
3. How to set the ON time (Example) To start operation at 7:10
4. How to set a program for daily ON/OFF operation
(Example) To start operation at 7:10 and stop the air conditioner at
23:30
NOTE
You can check the timer ON/OFF times after you have set them by pressing the PROGRAM button.
ON
Operation Indication
1. Press the Program button (
OFF ON
CLOCK
)
twice.
The timer ON and time indications flash.
2.
Press the HH button until 7 is displayed.
Press the MM button until 10 is displayed.
The display will change automatically back to show the present time after 10 sec.
3. Press the ON/OFF button to start the air conditioner.
The present time is displayed.
4. Press the TIMER SELECT button to set ON time.
The present time and
ON
are displayed.
1. Set the timer ON/OFF times as shown in 2 and 3.
2. Press the ON/OFF button to start the air conditioner.
3. Press the TIMER SELECT button to set the ON/OFF combination timer.
is displayed.
17OI-859-17EG
Page 90
Using the 1-Hour OFF Timer
1. 1-Hour OFF Timer This function causes the unit to operate for one hour and then stop,
regardless of whether the unit is on or off when this button is pressed.
The
1HR.
indicator in the display indicates that this function is
operating.
Setting procedure:
Regardless of whether the unit is operating or stopped, press the 1 HR. TIMER button.
1HR.
appears in the display.
Cancellation procedure:
Press the ON/OFF operation button to turn the unit off, wait for the unit to stop operating, and then press the ON/OFF operation button again. The 1-Hour Timer function is now cancelled and the unit operates normally.
NOTE
If, while the 1-Hour Timer function is operating, the 1 HR. TIMER button is pressed once to cancel the function and then again, the unit continues to operate for one hour from that point in time and then stops.
2. Operation Together with the Program
Timer
The Program Timer and 1-Hour OFF Timer may be used together.
It is not possible to use the OFF Timer and 1-Hour OFF Timer together. Whichever function is set last takes precedence. If the 1 HR. TIMER button is pressed while the TIMER OFF function operates, the OFF Timer is cancelled and the unit will stop operating one hour later.
1HR.
ON I /OFF
1HR.
TIMER
TEMP.
FLAP
HH TIMER
18 OI-859-18EG
Page 91
Adjusting the Airflow Direction
1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with
your hands to the left or right.
CAUTION
When the humidity is high, the vertical vanes should be in the front position during the cooling or dehumidifying operation. If the vertical vanes are positioned all of the way to the right or left, condensation may begin to form around the air vent and drip down.
2. Vertical The vertical airflow can be adjusted by moving the flap with the remote
control unit. Do not move the flap with your hands. Confirm that the remote control unit has been turned on. Use the FLAP button to set either the sweep function or one of the six airflow direction settings.
A. Sweep function B. Setting the Airflow Manually
The flap starts moving up and down to deliver air over the sweep range.
Referring to the above illustration, use the FLAP button to set the airflow direction within the range used during the cooling or dehumidifying operation.
NOTE
The flap automatically closes when the unit is off.
CAUTION
Use the FLAP button on the remote control to adjust the position of the flap. If you move the flap by hand, the flap position according to the remote control and the actual flap position may no longer match. If this should happen, shut off the unit, wait for the flap to close, and then turn on the unit again; the flap position will now be normal again.
Do not have the flap pointed down during cooling operation. Condensation may begin to form around the air vent and drip down.
COOL
and
DRY
SWEEP
1
2
3
4
5
6
ON I /OFF
MODE
FLAP
FAN SPEED
SELECT
HH TIMER
SELECT
MM
TIME SET
NIGHT
SETBACK
BATTERIES
ACL
A/C
SENSOR
OFF ON
CLOCK
19OI-859-19EG
Page 92
Operation without the Remote Control Unit
If you have lost the remote control unit or it has trouble, follow the steps below.
1. When the air conditioner is not running If you want to turn on the air conditioner, switch the operation selector to the OFF position, and then to the ON position.
NOTE
The set temperature and fan speed are automatically set at the last selection before stopping.
2. When the air conditioner is running If you want to turn off the air conditioner, switch the operation selector to the OFF position.
Care and Cleaning
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.
2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
Casing and Grille
(Indoor Unit)
Clean the casing and grille of the indoor unit with a vacuum cleaner brush, or wipe them with a clean, soft cloth.
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When cleaning the grille, be careful not to force the vanes out of place.
CAUTION
1. Never use solvents, or harsh chemicals when cleaning the indoor unit. Do not wipe the plastic casing using very hot water.
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts.
3. The internal coil and other components of the outdoor unit must be cleaned every year. Consult your dealer or service center.
ON 
OFF
TEST
Operation selector
INDOOR UNIT
20 OI-859-20EG
Page 93
Care and Cleaning (continued)
Anti-Mold Filter The anti-mold filter behind the air intake grille should be checked and
cleaned at least once every two weeks.
How to remove the
anti-mold filter
1. Grasp both ends of
the air intake grille and pull it out and up.
2. Push the anti-mold filter up slightly, and then pull it down.
Cleaning Use a vacuum cleaner to remove light dust. If there is sticky dust on the
filter, wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.
How to replace the
anti-mold filter
1. With the ‘‘FRONT’’ mark
facing you, slide the anti-mold filter up into the unit and then lower the handle into the groove on the unit.
2. After installing the anti-mold filter, press the locations marked by the arrows (
) and close the air intake grille.
Air intake grille
Anti-mold filter
Air intake grille
Anti-mold filter
Insert into the groove on the unit.
21OI-859-21EG
Page 94
Care and Cleaning (continued)
Air Clean Filter
(not provided)
The air cleaning filter removes dust and dirt from the air, and reduces odors and smoke from tobacco.
NOTE
The air clean filter is not provided with the air conditioner and must be purchased separately. The first time that you buy the air clean filter, it is necessary to get the STK-ARF4B-50 model with frame. When changing the filter subsequently, it is only necessary to replace the filter itself (model STK-F4B-50).
This air clean filter cannot remove harmful gases or vapors nor ventilate air in the room. You must open doors or windows frequently when you use gas or oil heating appliances. Otherwise there is a risk of suffocation in extreme cases.
How to install the air clean
filter
The air clean filter needs to be installed behind the anti-mold filter.
1. Remove the anti-mold filter.
2. Install the air clean filter in
the position shown in the diagram, with the ‘‘
’’ symbols (meaning ‘‘FRONT’’) facing the front.
3. Reinstall the anti-mold filter.
Cleaning the main unit and
remote control unit
Wipe clean using a soft, dry cloth.
To remove stubborn dirt, moisten a cloth in warm water no hotter than 40°C, wring thoroughly, and then wipe.
The air intake grille can be removed in order to wash it with water.
Removing and remounting
the air intake grille
With the air intake grille open all the way, grip both arms with your hands and pull toward you to remove. To remount, hold the air intake grille roughly horizontal and push it in until the arm shafts fit into the indentations in the main unit, then fit the grille into place.
CAUTION
When using a footstool or the like, be careful not to let it tip over.
Washing the grille with
water
Clean the grille gently using a soft sponge, or the like. Then wipe away any remaining moisture.
Neutral detergent may be used to remove stubborn dirt. Then rinse thoroughly with water and wipe away any remaining moisture.
Air clean filter
Air intake grille
Arm
22 OI-859-22EG
Page 95
Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or service center.
Trouble Possible Cause Remedy
Air conditioner does not run at all.
1. Power failure. 1. Restore power.
2. Leakage breaker tripped. 2. Contact service center.
3. Line voltage is too low. 3. Consult your electrician or dealer.
4. Operation button is OFF. 4. Press the button again.
5. Batteries in remote control unit have run down.
5. Replace batteries.
OPERATION lamp flashes and air conditioner does not operate.
Trouble in wiring system. Contact service center.
Compressor runs but soon stops.
Obstruction in front of condenser coil. Remove obstruction.
Poor cooling performance.
1. Dirty or clogged air filter. 1. Clean air filter to improve airflow.
2. Heat source or many people in room.
2. Eliminate heat source if possible.
3. Doors and/or windows are open. 3. Shut them to keep the heat out.
4. Obstacle near air intake or air discharge port.
4. Remove it to ensure good airflow.
5. Thermostat is set too high for cooling.
5. Set the temperature lower.
Clicking sound is heard from the air conditioner.
In cooling operation, any plastic parts may expand or shrink due to a sudden temperature change. In this event, a clicking sound may occur.
This is normal, and the sound will soon disappear.
OPERATION lamp lights but outdoor unit will not run.
1. The use of portable telephones near the air conditioner may cause disturbance to its normal operation.
1. Turn off the power then restart the air conditioner after 1 minute.
2. Consult your dealer.
Tips for Energy Saving
Do not
Block the air intake and outlet of the unit. If they are obstructed, the unit will not work well, and may be damaged.
Let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls and ceiling of the room are warmed by the sun, it will take longer to cool the room.
Do
Always try to keep the air filter clean. (Refer to ‘‘Care and Cleaning’’.) A clogged filter will impair the performance of the unit.
To prevent conditioned air from escaping, keep windows, doors and any other openings closed.
23OI-859-23EG
Page 96
Printed in italy
Via Varese, 90 - 21013 Gallarate - Va - Italy
Tel. +39 0331 755111 - Fax +39 0331 776240
www.argoclima.it
Loading...