Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES71PIC
220 - 230 - 240 V/1 phase/50/60 Hz
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
220230
13.312.8
3.002.982.98
Wired : REM HW Wireless : REM HLAWS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
285 (11-7/32)
995 (39-6/32)940 (37)
203 (8)340 (13- 3 /8)
347 (13-21/32)888 (34-31/32)
1,065 (41-30/32)
260 (10-8/32)409 (16-3/ 32)
12 (27)58 (128)
15 (33)67 (148)
0.096 (3.4)0.369 (13.0)
24,000 [7,500~27,000]
1,440/1,200/840 (720/600/420x2)
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access
(13A , OD18mm)
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
7.1 [2.2~8.0]
Rotary(SANYO)
3~30 (10~98)
R410A - 1.9
3.8 (1.9x2)
240
198 - 264
12.3
2.382.382.37
–
35/31/27
47
50 (164)
6.35 (1/4)
12.7 (1/2)
780 (30-23/32)
1015 (39-31/32)
1
1 - 3
)
1-1. Unit Specifications
Wall-Mounted Type AWS36PH
××
2 / AES71PIH
MODEL No. Indoor Unit
POWER SOURCE
PERFORMANCE
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Outdoor Unit
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
220 - 230 - 240 V/1 phase/50/60 Hz
CoolingHeating
7.1 [2.2~8.0]8.0 [2.2~9.0]
1,440/1,200/840 (720/600/420x2)
3.8 (1.9x2)–
198 - 264198 - 264
13.312.812.312.812.311.8
2.372.382.382.272.282.28
3.00
Wired : REM HW Wireless : REM HLAWS
2.983.51
3 and Automatic control/Variable
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
285 (11-7/32)
995 (39-6/32)940 (37)
203 (8)340 (13- 3 /8)
347 (13-21/32)888 (34-31/32)
1,065 (41-30/32)1015 (39-31/32)
260 (10-8/32)409 (16-3/ 32)
12 (27)58 (128)
15 (33)67 (148)
0.096 (3.4)0.369 (13.0)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
AWS36PH x 2
AES71PIH
27,000 [7,500~30,000]24,000 [7,500~27,000]
240220230240220230
2.983.52
Microprocessor/I.C.thermostat
ON/OFF 72-hours
Automatic (Remote control)
Washable, easy access
–
(13A , OD18mm)
Rotary(SANYO)
35/31/27
47/49
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
50 (164)
3~30 (10~98)
6.35 (1/4)
12.7 (1/2)
R410A - 1.9
780 (30-23/32)
3.51
1
1 - 4
)
1-1. Unit Specifications
Wall-Mounted Type AWS36PH
××
4 / AES125PIC
MODEL No. Indoor Unit AWS36PHx4
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECooling
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES125PIC
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
220230240
21.220.319.5
4.15
3.01
Wired : REM HW Wireless : REM HLAWS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
285 (11-7/32)1230 (48- 7/16)
995 (39-6/32) 940 (37)
203 (8) 340 (13-3 /8)
347 (13-21/32)1330 (52-3 /8)
1,065 (41-30/32) 1015 (39-31/32)
260 (10-8/32) 409 (16-3/32)
12 (27)100 (220)
15 (33)109 (240)
0.096 (3.4)0.552 (19.5)
42,500 [9,200~48,000]
2,880/2,400/1,680 (720/600/420x4)
Microprocessor/I.C.thermostat
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access
Munsell 3.0Y8.6/0.8
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
12.5 [2.7~14.0]
7.6 (1.9x4)
198 - 264
4.164.17
3.003.00
ON/OFF 72-hours
–
(13A , OD18mm)
Rotary(SANYO)
35/31/27
52
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
6.35 (1/4)
12.7 (1/2)
R410A - 3.6
1
1 - 5
)
1-1. Unit Specifications
Wall-Mounted Type AWS36PH
××
4 / AES125PIH
MODEL No. Indoor Unit AWS36PH x 4
POWER SOURCE
PERFORMANCECoolingHeating
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Outdoor Unit AES125PIH
220 - 230 - 240 V/1 phase/50/60 Hz
12.5 [2.7~14.0]14.0 [2.7~16.0]
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
42,500 [9,200~48,000]48,000 [9,200~54,500]
2,880/2,400/1,680 (720/600/420x4)
7.6 (1.9x4)
220230240220230240
198 - 264198 - 264
21.2
4.15
3.01
Wired : REM HW Wireless : REM HLAWS
20.3
4.16
3.00
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access
(13A , OD18mm)
Rotary(SANYO)
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
285 (11-7/32)1230 (48- 7/16)
995 (39-6/32) 940 (37)
203 (8) 340 (13-3 /8)
347 (13-21/32)1330 (52-3 /8)
1,065 (41-30/32) 1015 (39-31/32)
260 (10-8/32) 409 (16-3/32)
12 (27)100 (220)
15 (33)109 (240)
0.096 (3.4)0.552 (19.5)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
19.521.020.019.2
4.174.11
3.003.41
–
35/31/27
52/53
50 (164)
5~30 (16~98)
6.35 (1/4)
12.7 (1/2)
R410A - 3.6
–
4.114.12
3.413.40
1
1 - 6
)
1-1. Unit Specifications
Wall-Mounted Type AWS45PH
××
3 / AES125PIC
MODEL No.Indoor Unit
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECooling
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES125PIC
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
220230240
21.0
4.12
3.03
Wired : REM HW Wireless : REM HLAWS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
285 (11-7/32)1230 (48- 7/16)
995 (39-6/32) 940 (37)
203 (8) 340 (13-3 /8)
347 (13-21/32)1330 (52-3 /8)
1,065 (41-30/32) 1015 (39-31/32)
260 (10-8/32) 409 (16-3/32)
12 (27)100 (220)
15 (33)109 (240)
0.096 (3.4)0.552 (19.5)
42,500 [9,200~48,000]
2,160/1,800/1,260 (720/600/420x3)
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access
(13A , OD18mm)
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
AWS45PH x 3
12.5 [2.7~14.0]
5.7 (1.9x3)
198 - 264
20.119.4
4.134.14
3.033.02
–
Rotary(SANYO)
35/31/27
52
50 (164)
5~30 (16~98)
6.35 (1/4)
12.7 (1/2)
R410A - 3.6
1
1 - 7
)
1-1. Unit Specifications
Wall-Mounted Type AWS45PH
××
3 / AES125PIH
MODEL No. Indoor Unit AWS45PH x 3
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECoolingHeating
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Outdoor Unit AES125PIH
12.5 [2.7~14.0]14.0 [2.7~16.0]
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
(cu. Ft
m
42,500 [9,200~48,000]48,000 [9,200~54,500]
2,160/1,800/1,260 (720/600/420x3)
5.7 (1.9x3)–
220230240220
198 - 264198 - 264
21.020.119.420.819.819.1
4.12
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access
Wired : REM HW
(13A , OD18mm)
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
285 (11-7/32)1230 (48- 7/16)
995 (39-6/32) 940 (37)
203 (8) 340 (13-3 /8)
347 (13-21/32)1330 (52-3 /8)
1,065 (41-30/32) 1015 (39-31/32)
260 (10-8/32) 409 (16-3/32)
12 (27)100 (220)
15 (33)109 (240)
0.096 (3.4)0.552 (19.5)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3.023.43
Wireless : REM HLAWS
–
Rotary(SANYO)
35/31/27
52/53
50 (164)
5~30 (16~98)
6.35 (1/4)
12.7 (1/2)
R410A - 3.6
230240
4.094.134.144.084.08
3.433.423.033.03
1
1 - 8
)
1-1. Unit Specifications
Wall-Mounted Type AWS56PH
××
2 / AES100PIC
MODEL No. Indoor Unit AWS56PH x 2
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECooling
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES100PIC
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
(cu. Ft
m
220230240
16.8
3.283.293.29
3.053.043.04
Wired : REM HW Wireless : REM HLAWS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
995 (39-6/32)940 (37)
203 (8)340 (13-3 /8)
347 (13-21/32)888 (34-31/32)
1,065 (41-30/32)1015 (39-31/32)
260 (10-8/32)409 (16-3/32)
12 (27)65 (143)
15 (33)73 (161)
0.096 (3.4)0.369 (13.0)
34,000 [7,500~38,000]
1,560/1,320/960 (780/660/480x2)
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
10.0 [2.2~11.2]
4.2 (2.1x2)
198 - 264
16.015.3
–
(13A , OD18mm)
Rotary(SANYO)
38/34/30
51
50 (164)
5~30 (16~98)
6.35 (1/4)
12.7 (1/2)
R410A - 2.8
780 (30-23/32) 285 (11-7/32)
1
1 - 9
)
1-1. Unit Specifications
Wall-Mounted Type AWS56PH
××
2 / AES100PIH
MODEL No. Indoor Unit AWS56PH x 2
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECoolingHeating
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Outdoor Unit AES100PIH
10.0 [2.2~11.2]11.2 [2.2~12.5]
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
34,000 [7,500~38,000]38,000 [7,500~42,500]
1,560/1,320/960 (780/660/480x2)
4.2 (2.1x2)–
220230240220
198 - 264198 - 264
16.816.015.315.6
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access
Wired : REM HW Wireless : REM HLAWS
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
285 (11-7/32)780 (30-23/32)
995 (39-6/32)940 (37)
203 (8)340 (13-3 /8)
347 (13-21/32)888 (34-31/32)
1,065 (41-30/32)1015 (39-31/32)
260 (10-8/32)409 (16-3/32)
12 (27)65 (143)
15 (33)73 (161)
0.096 (3.4)0.369 (13.0)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3.293.043.05
–
(13A , OD18mm)
Rotary(SANYO)
38/34/30
51/52
50 (164)
5~30 (16~98)
6.35 (1/4)
12.7 (1/2)
R410A - 2.8
230240
14.914.3
3.053.283.29
3.673.673.053.043.043.68
1
1 - 10
)
1-1. Unit Specifications
Wall-Mounted Type AWS71PH / AES71PIC
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Indoor Unit
Outdoor Unit
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
220 - 230 - 240 V/1 phase/50/60 Hz
220240
13.2
2.36
3.01
Microprocessor/I.C.thermostat
3 and Automatic control/Variable
Automatic (Remote control)
Wired : REM HW Wireless : REM HLAWS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
330 (13)
1,140 (44-28/32)
228 (8-31/32)
390 (15-11/32)
1,215 (47-27/32)
293 (11-17/32)
21 (46)
24 (53)
0.139 (4.9)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
AWS71PH
AES71PIC
Cooling
7.1 [2.2~8.0]
24,000 [7,500~27,000]
1,140/960/720
4.0
230
198 - 264
12.7
2.36
3.01
ON/OFF 72-hours
Washable, easy access
–
(13A , OD18mm)
Rotary(SANYO)
41/37/34
47
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
50 (164)
3~30 (10~98)
9.52 (3/8)
15.88 (5/8)
R410A - 1.9
780 (30-23/32)
888 (34-31/32)
1015 (39-31/32)
12.2
2.37
3.00
Outdoor unitIndoor unit
940 (37)
340 (13- 3 /8)
409 (16-3/ 32)
58 (128)
67 (148)
0.369 (13.0)
1
1 - 11
)
1-1. Unit Specifications
Wall-Mounted Type AWS71PH / AES71PIH
MODEL No.
Outdoor Unit
POWER SOURCE
PERFORMANCE
Capacity [minimum~maximum]kW
BTU/h
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
3
m
(cu. Ft
24,000 [7,500~27,000]
13.2
2.362.37
220 - 230 - 240 V/1 phase/50/60 Hz
Cooling
7.1 [2.2~8.0]
4.0
198 - 264198 - 264
12.7
2.36
3.01
3 and Automatic control/Variable
Wired : REM HW
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unit
330 (13)
228 (8-31/32)
390 (15-11/32)888 (34-31/32)
1,215 (47-27/32)
293 (11-17/32)
21 (46)
24 (53)
0.139 (4.9)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
AWS71PHIndoor Unit
AES71PIH
8.0 [2.2~9.0]
27,000 [7,500~30,000]
1,140/960/720
240230220230
12.2
3.003.01
Microprocessor/I.C.thermostat
ON/OFF 72-hours
Automatic (Remote control)
Washable, easy access
(13A , OD18mm)
Rotary(SANYO)
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
3~30 (10~98)
15.88 (5/8)
R410A - 1.9
220240
12.7
2.26
3.543.52
Wireless : REM HLAWS
–
41/37/34
47/49
50 (164)
9.52 (3/8)
Outdoor unit
780 (30-23/32)
940 (37)1,140 (44-28/32)
340 (13- 3 /8)
1015 (39-31/32)
409 (16-3/ 32)
58 (128)
67 (148)
0.369 (13.0)
Heating
–
12.2
3.54
11.7
2.272.26
1
1 - 12
)
1-1. Unit Specifications
Wall-Mounted Type AWS71PH
××
2 / AES125PIC
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Indoor Unit AWS71PH x 2
Outdoor Unit AES125PIC
220 - 230 - 240 V/1 phase/50/60 Hz
BTU/h
2,280/1,920/1,440 (1,140/960/720x2)
220230240
21.120.119.4
4.134.134.14
3.033.033.02
Wired : REM HW Wireless : REM HLAWS
Outdoor - HidB - A
Outdoor
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
330 (13)1230 (48- 7/16)
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
1,140 (44-28/32) 940 (37)
228 (8-31/32) 340 (13-3 /8)
390 (15-11/32)1330 (52-3 /8)
1,215 (47-27/32) 1015 (39-31/32)
293 (11-17/32) 409 (16-3/32)
21 (46)100 (220)
24 (53)109 (240)
0.139 (4.9)0.552 (19.5)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling
12.5 [2.7~14.0]
42,500 [9,200~48,000]
8.0 (4.0x2)
198 - 264
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access
–
(13A , OD18mm)
Rotary(SANYO)
41/37/34
52
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 3.6
1
1 - 13
)
1-1. Unit Specifications
Wall-Mounted Type AWS71PH
××
2 / AES125PIH
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit AWS71PH x 2
Outdoor Unit AES125PIH
220 - 230 - 240 V/1 phase/50/60 Hz
CoolingHeating
12.5 [2.7~14.0]14.0 [2.7~16.0]
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
(cu. Ft
m
42,500 [9,200~48,000]48,000 [9,200~54,500]
2,280/1,920/1,440 (1,140/960/720x2)
8.0 (4.0x2)–
220230240220
198 - 264198 - 264
20.1
4.134.134.144.094.084.09
3.033.023.42
Wired : REM HW Wireless : REM HLAWS
3.03
Microprocessor/I.C.thermostat
3 and Automatic control/Variable
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
330 (13)780 (30-23/32)
1,140 (44-28/32)940 (37)
228 (8-31/32)340 (13- 3 /8)
390 (15-11/32)888 (34-31/32)
1,215 (47-27/32)1015 (39-31/32)
293 (11-17/32)409 (16-3/ 32)
21 (46)
24 (53)67 (148)
0.139 (4.9)0.369 (13.0)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
230240
19.420.919.819.121.1
3.433.42
ON/OFF 72-hours
Automatic (Remote control)
Washable, easy access
–
(13A , OD18mm)
Rotary(SANYO)
41/37/34
52/53
Munsell 3.0Y8.6/0.8
Munsell 1Y 8.5/0.5
50 (164)
3~30 (10~98)
9.52 (3/8)
15.88 (5/8)
R410A - 1.9
58 (128)
1
1 - 14
)
1-1. Unit Specifications
Ceiling-Mounted Type ACS71PH / AES71PIC
MODEL No.
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCE
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Indoor Unit ACS71PH
Outdoor Unit
3
m
BTU/h
(cu. Ft
220230240
13.212.712.2
2.362.362.37
3.013.013.00
Microprocessor/I.C.thermostat
3 and Automatic control/Variable
Washable, easy access, long life (2,500 hr)
Wired : REM HW Wireless : REM HLACS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
210 (8-9/32)780 (30-23/32)
1,180 (46-15/32)
680 (26-25/32)
280 (11-1/32)888 (34-31/32)
1,255 (49-13/32)1015 (39-31/32)
780 (30-23/32)409 (16-3/ 32)
25 (55)58 (128)
28 (62)67 (148)
0.274 (9.7)0.369 (13.0)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
AES71PIC
Cooling
7.1 [2.2~8.0]
24,000 [7,500~27,000]
1,100/900/840
3.0
198 - 264
ON/OFF 72-hours
Automatic (Remote control)
–
(20A , OD26mm)
Rotary(SANYO)
38/36/33
47
Munsell 10Y9.3/0.4
Munsell 1Y 8.5/0.5
50 (164)
3~30 (10~98)
9.52 (3/8)
15.88 (5/8)
R410A - 1.9
940 (37)
340 (13- 3 /8)
1
1 - 15
)
1-1. Unit Specifications
Ceiling-Mounted Type ACS71PH / AES71PIH
ACS71PHMODEL No.Indoor Unit
Outdoor Unit AES71PIH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECoolingHeating
Capacity [minimum~maximum]kW
BTU/h
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
3
m
(cu. Ft
7.1 [2.2~8.0]8.0 [2.2~9.0]
24,000 [7,500~27,000]27,000 [7,500~30,000]
1,100/900/840
3.0–
220230240220230240
198 - 264198 - 264
13.312.812.312.812.311.8
2.352.352.352.252.252.25
3.023.023.023.56
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access, long life (2,500 hr)
Wired : REM HW Wireless : REM HLACS
–
(20A , OD26mm)
Rotary(SANYO)
38/36/33
47/49
Munsell 10Y9.3/0.4
Munsell 1Y 8.5/0.5
50 (164)
3~30 (10~98)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
9.52 (3/8)
15.88 (5/8)
R410A - 1.9
Indoor unitOutdoor unit
210 (8-9/32)780 (30-23/32)
1,180(46-15/32)940 (37)
680 (26-25/32)340 (13- 3 /8)
280 (11-1/32)888 (34-31/32)
1,255(49-13/32)1015 (39-31/32)
780 (30-23/32)409 (16-3/ 32)
25 (55)58 (128)
28 (62)67 (148)
0.274 (9.7)0.369 (13.0)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3.563.56
1
1 - 16
)
1-1. Unit Specifications
Ceiling-Mounted Type ACS71PH
××
2 / AES125PIC
MODEL No. Indoor Unit ACS71PH x 2
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECooling
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES125PIC
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
220230
21.320.319.5
4.124.124.12
3.033.033.03
Washable, easy access, long life (2,500 hr)
Wired : REM HW Wireless : REM HLACS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
210 (8-9/32)
1,180 (46-15/32) 940 (37)
680 (26-25/32) 340 (13-3 /8)
280 (11-1/32)1330 (52-3 /8)
1,255 (49-13/32) 1015 (39-31/32)
780 (30-23/32) 409 (16-3/32)
25 (55)100 (220)
28 (62)109 (240)
0.274 (9.7)
42,500 [9,200~48,000]
2,200/1,800/1,680 (1,100/900/840x2)
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Munsell 10Y9.3/0.4
Munsell 1Y 8.5/0.5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
12.5 [2.7~14.0]
6.0 (3.0x2)
198 - 264
–
(20A , OD26mm)
Rotary(SANYO)
38/36/33
52
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 3.6
240
1230 (48- 7/16)
0.552 (19.5)
1
1 - 17
)
1-1. Unit Specifications
Ceiling-Mounted Type ACS71PH
××
2 / AES125PIH
MODEL No. Indoor Unit ACS71PH x 2
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECoolingHeating
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Outdoor Unit AES125PIH
12.5 [2.7~14.0]14.0 [2.7~16.0]
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
42,500 [9,200~48,000]48,000 [9,200~54,500]
2,200/1,800/1,680 (1,100/900/840x2)
6.0 (3.0x2)
220240
21.320.3
4.12
3.033.033.033.443.453.44
Wired : REM HW Wireless : REM HLACS
230
198 - 264
4.12
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access, long life (2,500 hr)
Munsell 10Y9.3/0.4
Munsell 1Y 8.5/0.5
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
210 (8-9/32)
1,180(46-15/32)
680 (26-25/32)
280 (11-1/32)
1,255(49-13/32)
780 (30-23/32)
25 (55)
28 (62)
0.274 (9.7)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
220230240
19.521.020.019.2
4.124.074.064.07
–
(20A , OD26mm)
Rotary(SANYO)
38/36/33
52/53
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 3.6
–
198 - 264
1230 (48- 7/16)
940 (37)
340 (13-3 /8)
1330 (52-3 /8)
1015 (39-31/32)
409 (16-3/32)
100 (220)
109 (240)
0.552 (19.5)
1
1 - 18
)
1-1. Unit Specifications
Ceiling-Mounted Type ACS100PH / AES100PIC
MODEL No.
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECooling
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Indoor Unit ACS100PH
Outdoor Unit AES100PIC
10.0 [2.2~11.2]
34,000 [7,500~38,000]
1,650/1,380/1,200
3.9
198 - 264
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
–
(20A , OD26mm)
Rotary(SANYO)
41/38/35
51
Munsell 10Y9.3/0.4
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 2.8
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3
m
BTU/h
(cu. Ft
220230240
17.016.2
3.293.293.30
3.043.043.03
Washable, easy access, long life (2,500 hr)
Wired : REM HW Wireless : REM HLACS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
210 (8-9/32)780 (30-23/32)
1,595 (62-25/32)940 (37)
680 (26-25/32)340 (13-3 /8)
280 (11-1/32)888 (34-31/32)
1,670 (65-24/32)1015 (39-31/32)
780 (30-23/32)409 (16-3/32)
33 (73)65 (143)
37 (82)73 (161)
0.365 (12.9)0.369 (13.0)
15.5
1
1 - 19
)
1-1. Unit Specifications
Ceiling-Mounted Type ACS100PH / AES100PIH
MODEL No. Indoor Unit ACS100PH
Outdoor Unit AES100PIH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECoolingHeating
Capacity [minimum~maximum]kW
BTU/h
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
3
m
(cu. Ft
10.0 [2.2~11.2]11.2 [2.2~12.5]
34,000 [7,500~38,000]38,000 [7,500~42,500]
1,650/1,380/1,200
3.9–
220230240220230240
198 - 264198 - 264
17.016.215.515.815.114.5
3.293.293.303.05
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
Washable, easy access, long life (2,500 hr)
Wired : REM HW Wireless : REM HLACS
–
(20A , OD26mm)
Rotary(SANYO)
41/38/35
51/52
Munsell 10Y9.3/0.4
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
9.52 (3/8)
15.88 (5/8)
R410A - 2.8
Indoor unitOutdoor unit
1,595(62-25/32)
680 (26-25/32)
280 (11-1/32)
1,670(65-24/32)
780 (30-23/32)
33 (73)
37 (82)
0.365 (12.9)0.369 (13.0)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3.053.05
3.673.673.043.043.033.67
780 (30-23/32) 210 (8-9/32)
940 (37)
340 (13-3 /8)
888 (34-31/32)
1015 (39-31/32)
409 (16-3/32)
65 (143)
73 (161)
1
1 - 20
)
1-1. Unit Specifications
Ceiling-Mounted Type ACS125PH / AES125PIC
MODEL No. Indoor Unit ACS125PH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECooling
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES125PIC
12.5 [2.7~14.0]
3
m
BTU/h
(cu. Ft
220230240
21.220.319.5
4.124.124.12
3.033.033.03
Washable, easy access, long life (2,500 hr)
Wired : REM HW Wireless : REM HLACS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
210 (8-9/32)
1,595 (62-25/32)
680 (26-25/32)
280 (11-1/32)
1,670 (65-24/32)
780 (30-23/32)
33 (73)
37 (82)
0.365 (12.9)0.552 (19.5)
42,500 [9,200~48,000]
1,800/1,560/1,320
5.6
198 - 264
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
–
(20A , OD26mm)
Rotary(SANYO)
43/40/37
52
Munsell 10Y9.3/0.4
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 3.6
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1230 (48- 7/16)
940 (37)
340 (13-3 /8)
1330 (52-3 /8)
1015 (39-31/32)
409 (16-3/32)
100 (220)
109 (240)
1
1 - 21
)
1-1. Unit Specifications
Ceiling-Mounted Type ACS125PH / AES125PIH
MODEL No. Indoor Unit ACS125PH
Outdoor Unit AES125PIH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECoolingHeating
Capacity [minimum~maximum]kW
BTU/h
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
3
m
(cu. Ft
12.5 [2.7~14.0]14.0 [2.7~16.0]
42,500 [9,200~48,000]48,000 [9,200~54,500]
1,800/1,560/1,320
5.6–
220230240220230240
198 - 264198 - 264
19.521.0
4.124.124.12
3.033.03
Washable, easy access, long life (2,500 hr)
Wired : REM HW Wireless : REM HLACS
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unit
210 (8-9/32)
1,595(62-25/32)
680 (26-25/32)
280 (11-1/32)
1,670(65-24/32)
780 (30-23/32)
33 (73)
37 (82)
0.365 (12.9)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3.033.443.443.44
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Automatic (Remote control)
(20A , OD26mm)
Rotary(SANYO)
Munsell 10Y9.3/0.4
Munsell 1Y 8.5/0.5
5~30 (16~98)
15.88 (5/8)
R410A - 3.6
4.074.07
–
43/40/37
52/53
50 (164)
9.52 (3/8)
1015 (39-31/32)
20.019.221.220.3
4.07
Outdoor unit
1230 (48- 7/16)
940 (37)
340 (13-3 /8)
1330 (52-3 /8)
409 (16-3/32)
100 (220)
109 (240)
0.552 (19.5)
1
1 - 22
1-1. Unit Specifications
Concealed-Duct Type ADS71PH / AES71PIC
)
MODEL No. Indoor Unit ADS71PH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECooling
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
External static pressure (High)Pa(mmAq)
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES71PIC
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
50 (5.1) : at shipment,92 (9.4) : using the booster cable
220230240
13.713.312.8
2.492.512.52
2.852.83
Wired : REM HW Wireless : REM HL
Max.head 50 cm above drain connection (25A , OD32mm)
34/30/27, (38/34/30 : using the booster cable)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
310 (12-7/32)780 (30-23/32)
1,000 (39-12/32)940 (37)
630 (24-26/32)340 (13- 3 /8)
358 (14-3/32)888 (34-31/32)
1,191 (46-28/32)1015 (39-31/32)
783 (30-26/32)409 (16-3/ 32)
32 (71)58 (128)
37 (82)67 (148)
0.334 (11.8)0.369 (13.0)
24,000 [7,500~27,000]
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Munsell 1Y 8.5/0.5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
7.1 [2.2~8.0]
1,080/900/780
3.5
198 - 264
2.82
–
Field supply
–
Rotary(SANYO)
47
–
50 (164)
3~30 (10~98)
9.52 (3/8)
15.88 (5/8)
R410A - 1.9
1
1 - 23
1-1. Unit Specifications
Concealed-Duct Type ADS71PH / AES71PIH
)
MODEL No. Indoor Unit ADS71PH
Outdoor Unit AES71PIH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECoolingHeating
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
3
m
(cu. Ft
7.1 [2.2~8.0]8.0 [2.2~9.0]
24,000 [7,500~27,000]27,000 [7,500~30,000]
1,080/900/780
3.5–
50 (5.1) : at shipment,92 (9.4) : using the booster cable
220230240220
198 - 264198 - 264
13.713.312.813.2
2.492.51
2.852.832.823.363.353.32
Wired : REM HW
Max.head 50 cm above drain connection (25A , OD32mm)
34/30/27, (38/34/30 : using the booster cable)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
310 (12-7/32)780 (30-23/32)
1,000 (39-12/32)940 (37)
630 (24-26/32)340 (13- 3 /8)
358 (14-3/32)888 (34-31/32)
1,191 (46-28/32)1015 (39-31/32)
783 (30-26/32)409 (16-3/ 32)
32 (71)58 (128)
37 (82)67 (148)
0.334 (11.8)0.369 (13.0)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
2.522.38
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
–
Field supply
Wireless : REM HL
–
Rotary(SANYO)
47/49
–
Munsell 1Y 8.5/0.5
50 (164)
3~30 (10~98)
9.52 (3/8)
15.88 (5/8)
R410A - 1.9
230240
12.712.3
2.392.41
1
1 - 24
1-1. Unit Specifications
Concealed-Duct Type ADS71PH
××
2 / AES125PIC
)
MODEL No. Indoor Unit ADS71PH x 2
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCE
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
External static pressure (High)Pa(mmAq)
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES125PIC
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
50 (5.1) : at shipment,92 (9.4) : using the booster cable
220230
22.2
4.39 4.42 4.45
2.85 2.83
Wired : REM HW
Max.head 50 cm above drain connection (25A , OD32mm)
34/30/27, (38/34/30 : using the booster cable)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unit
310 (12-7/32)
1,000 (39-12/32)
630 (24-26/32)
358 (14-3/32)
1,191 (46-28/32)
783 (30-26/32)
32 (71)
37 (82)
0.334 (11.8)
42,500 [9,200~48,000]
2,160/1,800/1,560 (1,080/900/780x2)
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Munsell 1Y 8.5/0.5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling
12.5 [2.7~14.0]
7.0 (3.5x2)
198 - 264
21.3 20.6
–
Field supply
–
Rotary(SANYO)
52
–
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 3.6
240
2.81
Wireless : REM HL
Outdoor unit
1230 (48- 7/16)
940 (37)
340 (13-3 /8)
1330 (52-3 /8)
1015 (39-31/32)
409 (16-3/32)
100 (220)
109 (240)
0.552 (19.5)
1
1 - 25
1-1. Unit Specifications
Concealed-Duct Type ADS71PH
××
2 / AES125PIH
)
MODEL No. Indoor Unit ADS71PH x 2
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCE
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
External static pressure (High)Pa(mmAq)
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Color (Approximate value)Indoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Package dimensionsHeightmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Outdoor Unit AES125PIH
CoolingHeating
12.5 [2.7~14.0]14.0 [2.7~16.0]
BTU/h
Outdoor - HidB - A
Outdoor
Widthmm (in.)
Depthmm (in.)
Widthmm (in.)
Depthmm (in.)
3
m
(cu. Ft
42,500 [9,200~48,000]48,000 [9,200~54,500]
2,160/1,800/1,560 (1,080/900/780x2)
7.0 (3.5x2)–
50 (5.1) : at shipment,92 (9.4) : using the booster cable
220230240220
198 - 264198 - 264
22.2 21.3 20.6 21.9 21.0 20.2
4.39 4.42 4.45 4.33
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Wired : REM HW Wireless : REM HL
Max.head 50 cm above drain connection (25A , OD32mm)
Rotary(SANYO)
34/30/27, (38/34/30 : using the booster cable)
Munsell 1Y 8.5/0.5
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
310 (12-7/32)
1,000 (39-12/32)
630 (24-26/32)
358 (14-3/32)
1,191 (46-28/32)
783 (30-26/32)
32 (71)
37 (82)
0.334 (11.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
–
Field supply
–
52/53
–
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 3.6
230240
4.354.38
3.22
1230 (48- 7/16)
940 (37)
340 (13-3 /8)
1330 (52-3 /8)
1015 (39-31/32)
409 (16-3/32)
100 (220)
109 (240)
0.552 (19.5)
3.202.85 2.83 2.81 3.23
1
1 - 26
)
1-1. Unit Specifications
Concealed-Duct Type ADS100PH / AES100PIC
MODEL No. Indoor Unit ADS100PH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCECooling
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
External static pressure (High)Pa(mmAq)
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES100PIC
10.0 [2.2~11.2]
34,000 [7,500~38,000]
1,800/1,560/1,260
4.2
198 - 264
17.1 16.4
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
–
Field supply
–
Rotary(SANYO)
51
–
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 2.8
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3
m
BTU/h
(cu. Ft
79 (8.1) : at shipment, 122 (12.4) : using the booster cable
220230240
17.9
3.53 3.55
2.83 2.82 2.81
Wired : REM HW
Max.head 50 cm above drain connection (25A , OD32mm)
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
3
m
(cu. Ft
10.0 [2.2~11.2]11.2 [2.2~12.5]
34,000 [7,500~38,000]38,000 [7,500~42,500]
1,800/1,560/1,260
4.2–
79 (8.1) : at shipment, 122 (12.4) : using the booster cable
220230240220230240
198 - 264198 - 264
17.9 17.1
3.53 3.55 3.56 3.28
2.83 2.82
Wired : REM HW Wireless : REM HL
Max.head 50 cm above drain connection (25A , OD32mm)
0.468 (16.5)0.369 (13.0)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
16.4 16.6 16.0 15.4
2.81 3.41
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
–
Field supply
–
Rotary(SANYO)
51/52
–
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 2.8
3.303.31
3.393.38
340 (13-3 /8)
65 (143)
1
1 - 28
)
1-1. Unit Specifications
Concealed-Duct Type ADS125PH / AES125PIC
MODEL No. Indoor Unit ADS125PH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCE
Capacity [minimum~maximum]kW
Air circulation (Hi/Me/Lo)m3/h
Moisture removal (High)Liters/h
External static pressure (High)Pa(mmAq)
ELECTRICAL RATINGS
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Outdoor Unit AES125PIC
Cooling
12.5 [2.7~14.0]
42,500 [9,200~48,000]
1,980/1,560/1,320
6.6
198 - 264
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
–
Field supply
–
Rotary(SANYO)
52
–
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
9.52 (3/8)
15.88 (5/8)
R410A - 3.6
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3
m
BTU/h
(cu. Ft
78 (8.0) : at shipment, 113 (11.5) : using the booster cable
220230
22.0 21.1
4.34 4.36 4.37
2.88 2.87 2.86
Wired : REM HW Wireless : REM HL
Max.head 50 cm above drain connection (25A , OD32mm)
40/37/33, (44/40/37 : using the booster cable)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
Indoor unitOutdoor unit
310 (12-7/32)
1,480 (58-9/32)
630 (24-26/32)
358 (14-3/32)
1,671 (65-25/32)
783 (30-26/32)
47 (104)
52 (115)
0.468 (16.5)0.552 (19.5)
240
20.3
1230 (48- 7/16)
940 (37)
340 (13-3 /8)
1330 (52-3 /8)
1015 (39-31/32)
409 (16-3/32)
100 (220)
109 (240)
1
1 - 29
)
1-1. Unit Specifications
Concealed-Duct Type ADS125PH / AES125PIH
MODEL No. Indoor Unit ADS125PH
Outdoor Unit AES125PIH
POWER SOURCE220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCE
Voltage ratingV
Available voltage rangeV
Running amperes*A
Max–Running amperes**A
Power inputkW
C.O.PW/W
Max. Starting amperesA
FEATURES
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation soundIndoor - Hi/Me/LodB - A
Outdoor - HidB - A
Color (Approximate value)Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing lengthm (ft.)
Limit of tubing length at shipmentm (ft.)
Limit of elevation differencem (ft.)
between the two units
Refrigerant tubeNarrow tubemm (in.)
outer diameterWide tubemm (in.)
Refrigerant amount at shipmentkg
DIMENSIONS & WEIGHT
Unit dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Package dimensionsHeightmm (in.)
Widthmm (in.)
Depthmm (in.)
Net weightkg (lb.)
Shipping weightkg (lb.)
Shipping volume
Cooling:
Rating conditions (*):Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
3
m
(cu. Ft
220230240220230240
22.0 21.1 20.3 21.7 20.7 19.9
4.34 4.36 4.37 4.29 4.29 4.31
2.88 2.87 2.86 3.26
CoolingHeating
12.5 [2.7~14.0]14.0 [2.7~16.0]
42,500 [9,200~48,000]48,000 [9,200~54,500]
1,980/1,560/1,320
6.6–
78 (8.0) : at shipment, 113 (11.5) : using the booster cable
198 - 264198 - 264
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
–
Field supply
Wired : REM HW Wireless : REM HL
–
Max.head 50 cm above drain connection (25A , OD32mm)
Rotary(SANYO)
40/37/33, (44/40/37 : using the booster cable)
52/53
–
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
9.52 (3/8)
15.88 (5/8)
R410A - 3.6
Indoor unitOutdoor unit
310 (12-7/32)
1,480 (58-9/32)
630 (24-26/32)
358 (14-3/32)1330 (52-3 /8)
1,671 (65-25/32) 1015 (39-31/32)
783 (30-26/32) 409 (16-3/32)
47 (104)
52 (115)109 (240)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
3.263.25
1230 (48- 7/16)
940 (37)
340 (13-3 /8)
100 (220)
0.552 (19.5)0.468 (16.5)
1
1 - 30
1-2. Major Component Specifications
(A) Indoor Units
Wall-Mounted Type AWS36-45PH
MODEL No.
Source
Controller P.C.B. Ass’y
Fan (Number…diameter)mm
Fan motor
Model…Nominal outputW
Source
No.of pole…rpm (230 V, High)rpm
Coil resistanceBRN – WHT: 490.5ORG – YEL: 39.18
(Ambient temperature 20°C)WHT – VLT: 78.43YEL – PNK: 213.5
VLT – ORG: 62.63
Safety device
Operating temperature
( 17AM033E5-4 )
Operating temperature
( 9700k211-215 )
Run capacitor
Electronic expansion valve
Open °C
Close °C
Open °C
Close °C
VAC, µF
AWS36PH / AWS45PH
220 - 230 - 240 V / 1 phase / 50/60 Hz
CR-KR74GXH56 (Microprocessor)
Cross-flow ( 1…ø88 / L740 )
UF4Q-31G5P-S…12W
220 - 230 - 240 V / 1 phase / 50/60 Hz
4P…1,164
130 ± 5
83 ± 15
130 ± 8
79 ± 15
440 VAC, 1.0µF
Coil
Coil resistance (at 20°C)
Valve body
Heat exchanger
Coil
Rows…fin pitchmm
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 25°C)
Drain Pump
Rated
Total head & capacity
VAC, W
–
: –YEL –ORG – GRY
RED – GRY: –BLK – GRY: –
–
Aluminum plate fin / Copper tube
2…1.3
2
m
0.231
–
–
–
–
–
–
–
GRY
: –
1
1 - 31
1-2. Major Component Specifications
(A) Indoor Units
Wall-Mounted Type AWS56PH
MODEL No.
Source
Controller P.C.B. Ass’y
Fan (Number…diameter)mm
Fan motor
Model…Nominal outputW
Source
No.of pole…rpm (230 V, High)rpm
Coil resistanceBRN - WHT: 490.5ORG – YEL: 39.18
(Ambient temperature 20°C)WHT – VLT: 78.43YEL – PNK: 213.5
Safety device
Operating temperature
( 17AM033E5-4 )
Operating temperature
( 9700k211-215 )
Run capacitor
Electronic expansion valve
Coil
Coil resistance (at 20°C)
Open °C130 ± 5
Close °C83 ± 15
Open °C
Close °C
VAC, µF440 VAC, 1.2µF
ORG – GRY
220 - 230 - 240 V / 1 phase / 50/60 Hz
CR-KR74GXH56 (Microprocessor)
Cross-flow ( 1…ø88 / L740 )
220 - 230 - 240 V / 1 phase / 50/60 Hz
VLT – ORG: 62.63
AWS56PH
UF4Q-31G5P-S…12W
4P…1,205
130 ± 8
79 ± 15
–
: –YEL – GRY: –
Valve body
Heat exchanger
Coil
Rows…fin pitchmm
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 25°C)
Drain Pump
Rated
Total head & capacity
VAC, W
RED – GRY: –BLK – GRY: –
–
Aluminum plate fin / Copper tube
2…1.3
2
m
0.231
–
–
–
–
–
–
–
1
1 - 32
1-2. Major Component Specifications
(A) Indoor Units
Wall-Mounted Type AWS71PH
MODEL No.
Source
Controller P.C.B. Ass’y
Fan (Number…diameter)mm
Fan motor
Model…Nominal outputW
Source
No.of pole…rpm (230 V, High)rpm
Coil resistanceBRN – WHT: 306.9ORG – YEL: 23.12
(Ambient temperature 20°C)WHT – VLT: 54.58YEL – PNK: 96.62
Safety device
Operating temperature
( 17AM033E5-4 )
Operating temperature
( 9700k211-215 )
Run capacitor
Electronic expansion valve
Coil–
Coil resistance (at 20°C)
Open °C130 ± 5
Close °C
Open °C130 ± 5
Close °C
VAC, µF440 VAC, 1.8µF
ORG – GRY: –YEL – GRY: –
220 - 230 - 240 V / 1 phase / 50/60 Hz
CR-KR254GXH56 (Microprocessor)
Cross-flow ( 1…ø100 / L848 )
220 - 230 - 240 V / 1 phase / 50/60 Hz
VLT – ORG: 33.91
AWS71PH
KFT4Q-31A5P-S…27W
4P…1,147
83 ± 15
79 ± 15
Valve body
Heat exchanger
Coil
Rows…fin pitchmm
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 25°C)
Drain Pump
Rated
Total head & capacity
VAC, W–
RED – GRY: –BLK – GRY: –
–
Aluminum plate fin / Copper tube
2…1.3
2
m
0.329
–
–
–
–
–
–
1
1 - 33
1-2. Major Component Specifications
(A) Indoor Units
Ceiling-Mounted Type ACS71PH
MODEL No.
Source
Controller P.C.B. Ass’y
Fan (Number…diameter)mm
Fan motor
Model…Nominal outputW
Source
No.of pole…rpm (230 V, High)rpm
Coil resistance
(Ambient temperature 20°C)
Run capacitor
Safety device
Electronic expansion valve
Coil
Coil resistance (at 20°C)ORG – GRY: –YEL – GRY: –
Valve body
Heat exchanger
Coil
VAC, µF–
220 - 230 - 240 V / 1 phase / 50/60 Hz
CR-SRP50A-B (Microprocessor)
RED – GRY: –BLK – GRY: –
Aluminum plate fin / Copper tube
ACS71PH
Centrifugal ( 3…ø140 )
DK8-63B280H…40W
8P…980
RED – WHT: 53.0
WHT – BLK: 53.0
BLK – RED: 53.0
Thermal protector, fuse
–
–
Rows…fin pitchmm
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 25°C)
Drain Pump
Rated
Total head & capacity
VAC, W
3…1.4
2
m
0.222
–
–
–
–
–
–
–
1
1 - 34
1-2. Major Component Specifications
(A) Indoor Units
Ceiling-Mounted Type ACS100PH
MODEL No.
Source
Controller P.C.B. Ass’y
Fan (Number…diameter)mm
Fan motor
Model…Nominal outputW
Source
No.of pole…rpm (230 V, High)rpm
Coil resistanceRED – WHT: 37.0
(Ambient temperature 20°C)WHT – BLK: 37.0
Run capacitor
Safety device
Electronic expansion valve
Coil
Coil resistance (at 20°C)ORG – GRY: –YEL – GRY: –
Valve body
Heat exchanger
CoilAluminum plate fin / Copper tube
VAC, µF–
220 - 230 - 240 V / 1 phase / 50/60 Hz
CR-SRP50A-B (Microprocessor)
RED – GRY: –BLK – GRY: –
ACS100PH
Centrifugal ( 4…ø140 )
DK8-123B280H…80W
8P…1040
BLK – RED: 37.0
Thermal protector, fuse
–
–
Rows…fin pitchmm
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 25°C)
Drain Pump
Rated
Total head & capacity
VAC, W–
3…1.4
2
m
0.326
–
–
–
–
–
–
1
1 - 35
1-2. Major Component Specifications
(A) Indoor Units
Ceiling-Mounted Type ACS125PH
MODEL No.
Source
Controller P.C.B. Ass’y
Fan (Number…diameter)mm
Fan motor
Model…Nominal outputW
Source
No.of pole…rpm (230 V, High)rpm
Coil resistance
(Ambient temperature 20°C)
Run capacitor
Safety device
Electronic expansion valve
Coil
Coil resistance (at 20°C)ORG – GRY: –YEL – GRY: –
Valve body
VAC, µF
ACS125PH
220 - 230 - 240 V / 1 phase / 50/60 Hz
CR-SRP50A-B (Microprocessor)
Centrifugal ( 4…ø140 )
DK8-123B280H…80W
8P…1100
RED – WHT: 37.0
WHT – BLK: 37.0
BLK – RED: 37.0
–
Thermal protector, fuse
–
RED – GRY: –BLK – GRY: –
–
Heat exchanger
Coil
Rows…fin pitchmm
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 25°C)
Drain Pump
Rated
Total head & capacity
VAC, W–
Aluminum plate fin / Copper tube
3…1.4
2
m
0.326
–
–
–
–
–
–
1
1 - 36
1-2. Major Component Specifications
(A) Indoor Units
Concealed-Duct ADS71PH
MODEL No.
Source
Controller P.C.B. Ass’y
Fan (Number…diameter)mm
Fan motor
Model…Nominal outputW
Source
No.of pole…rpm (230 V, High)rpm
Coil resistanceΩBRN - WHT: 74.72ORG – YEL: 9.588
(Ambient temperature 20°C)WHT – VLT: 19.14YEL – BLK: 10.52
Refrigerant liquid line ø9.52 (narrow tube)
(Use the tube connector)
Refrigerant gas line ø15.88 (wide tube)
Upper drain port (O.D. 32 mm)
Bottom drain port (O.D. 32 mm)
Suspension lug
Power supply outlet (2-ø30)
Fresh air intake port (ø150)
Flange for the flexible air outlet duct (ø200)
9
Tube cover
10
Electrical component box
11
Flange for the air intake duct
(Option or field supply)
1
1 - 57
1-4. Dimensional Data
(A) Indoor Unit: Concealed-Duct Type
100, 125 Type
10
190
25
175
35
11
260
(Air outlet
duct flange)
40
1480
70130
(150)
285
115
65
310
25210
10
25
24
(Hole)
19
18-ø3.3
3131
230
6 = 1380
×
160
630
(450 × 450)
(Field supply)
Inspection access
25
7030
85
230 P
1442 (Air outlet duct flange)
(Suspension bolt pitch)
185
90
580
1560 (Suspension bolt pitch)
33533533531075
25
Refrigerant liquid line ø9.52 (narrow tube)
Refrigerant gas line ø15.88 (wide tube)
Upper drain port (O.D. 32 mm)
Bottom drain port (O.D. 32 mm)
Suspension lug
Power supply outlet (2-ø30)
Fresh air intake port (ø150)
Flange for the flexible air outlet duct (ø200)
9
Tube cover
10
Electrical component box
11
Flange for the air intake duct
(Option or field supply)
1
1 - 58
1-4. Dimensional Data
(A) Indoor Unit: Flange for Air Intake Duct (Field Supply)
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating
capacity found from the capacity graph by the correction coefficient from the table above.
1
1 - 64
1-8. Noise Criterion Curves
Wall-Mounted Type
Both 50Hz and 60Hz
Strong
Weak
MODEL:
SOUND LEVEL :36 dB(A)
CONDITION:
60
50
40
30
Approximate
20
minimum audible
(0dB = 0.0002µbar)
limit for
Sound pressure level (dB)
continuous noise
10
Overall
AWS36PH, AWS45PH
STRONG
HIGH
LOW
dB(A)
32
28 dB(A)
1 m in front at height of 1 m
NC-50
NC-40
NC-30
NC-20
400063125 250800020001000500
MODEL:
SOUND LEVEL :39 dB(A)
CONDITION:
AWS56PH
STRONG
HIGH
LOW
dB(A)
35
31 dB(A)
1 m in front at height of 1 m
60
50
40
30
Approximate
20
minimum audible
(0dB = 0.0002µbar)
limit for
Sound pressure level (dB)
continuous noise
10
Overall
Frequency at center of sound pressure band (Hz)Frequency at center of sound pressure band (Hz)
MODEL:
SOUND LEVEL :42 dB(A)
CONDITION
AWS71PH
STRONG
HIGH
LOW
:
1 m in front at height of 1 m
38
dB(A)
35 dB(A)
NC-50
NC-40
NC-30
NC-20
400063125 250800020001000500
60
50
40
30
Approximate
20
(0dB = 0.0002µbar)
minimum audible
Sound pressure level (dB)
limit for
continuous noise
10
Overall
Frequency at center of sound pressure band (Hz)
NC-50
NC-40
NC-30
NC-20
400063125 250800020001000500
1
1 - 65
MO DE L:
AC S 71P H
S OU ND LE VE L :39 dB (A)
LO W
HIG H
33 dB (A)
37 dB (A)
C OND ITI ON
:
MO DE L:
AC S 125P H
S OU ND LE VE L : S T RONG 44 dB (A)
LO W
HIG H
37 dB (A)
41 dB (A)
C OND ITI ON:
MO DE L:
AC S 100P H
S OU ND LE VE L :42 dB (A)
LO W
HIG H
35 dB (A)
40 dB (A)
C OND ITI ON
:
NC -20
NC -30
NC -40
NC -50
400 063125 250800 020001000500
60
50
40
30
20
10
NC -20
NC -30
NC -40
NC -50
400 063125 250800 020001000500
60
50
40
30
20
10
NC -20
NC -30
NC -40
NC -50
400 063125 250800 020001000500
60
50
40
30
20
10
S trong
Wea k
B oth 50Hz a nd 60H z
S TR O NG
S TR O NG
F requency a t c enter of s ound pres sure ba nd (Hz)F requency a t c enter of s ound pres sure ba nd (Hz)
F requency a t c enter of s ound pres sure ba nd (Hz)
Overa ll
S ound pres sure level ( dB )
(0dB = 0.00 02 ba r)
Approxima te
minimum a udible
limit for
continuous noise
Overa ll
S ound pres sure level ( dB )
(0dB = 0.00 02 ba r)
Approxima te
minimum a udible
limit for
continuous noise
Overa ll
S ound pres sure level ( dB )
(0dB = 0.00 02 ba r)
Approxima te
minimum a udible
limit for
continuous noise
1 m from front of outlet at height of 1.5 m1 m from front of outlet at height of 1.5 m
1 m from front of outlet at height of 1.5 m
1-8. Noise Criterion Curves
Ceiling-Mounted Type
1
1 - 66
1-8. Noise Criterion Curves
Concealed-Duct Type
S ingle P hase, 50 Hz
MO DE L:
ADS 71P H
S OUND LE V E L :
HI GH 34 dB (A ), N C 22 / LOW 27 dB (A) , N C 18
C OND ITIO N : Under the unit 1. 5 m
S OUR C E: 220 - 230 - 240
V,
60
50
40
30
20
10
AP PR O XIMA TE
TH RE S HO LD OF
HE AR IN G F OR
CO NT INU OUS
NOI SE
63 125 250 500 1 000 200 0 4000 800 0
NC -50
NC -40
NC -30
NC -20
S ound P res s ure L evel (dB )
(0 dB = 0.0002 bar)
F requency a t c enter of s ound pres sure ba nd (Hz)
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63 125 250 500 1000 2000 4000 8000
NC-50
NC-40
NC-30
NC-20
Frequency at center of sound pressure band (Hz)Frequency at center of sound pressure band (Hz)
REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values
shown in this graph because of the conditions of operation, the structure of the building, the background
noise and other factors.
2.
The test results were obtained from an anechoic room.
NOTE
To evaluate the noise level, the maximum value of the measured sound pressure level is used. Read the value at
each frequency level (on horizontal axis, center of the sound pressure band) from 63 Hz to 8000 Hz, and select the
corresponding maximum value indicated on the vertical axis.
1
1 - 68
1-9. Indoor Fan Performance
Concealed-Duct Type
If external static pressure is too great (due to long
extension of ducts, for example), the air flow volume
may drop too low at each air outlet. This problem may
be solved by increasing the fan speed using the following procedure:
(1) Remove 4 screws on the electrical component box
and remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends)
clamped in the box.
(4) Securely connect the booster cable sockets
between the disconnected fan motor sockets in
step 2 as shown in Fig. 1-1.
(5) Place the cable neatly in the box and reinstall the
cover plate.
Fig. 1-1
Fig. 1-2
■ How to read the diagram
The vertical axis is the external static pressure (Pa) while the horizontal axis represents the air flow (m
3
/minute). The
characteristic curves for “HT,” “H,” “M” and “L” fan speed control are shown. The nameplate values are shown based
on the “H” air flow. For the 25 type, the air flow is 18 m3/minute, while the external static pressure is 49 Pa at “H”
position. If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may
drop too low at each air outlet. This problem may be solved by increasing the fan speed as explained above.
Air s pee d a t c enter of discha rge a irflow (m/s)
Vertica l air throw distance (m)
Air s pee d a t c enter of discha rge a irflow (m/s)
Vertica l air throw distance (m)
Air s pee d a t c enter of discha rge a irflow (m/s)
Horiz ontal air throw dis ta nce (m)Horiz ontal air throw dis ta nce (m)
Horiz ontal air throw dis ta nce (m)
*
C oolingHe ating
*
C oolingHe ating
*
C oolingHe ating
1
1 - 70
Ceiling-Mounted Type
AC S 71 P H
AC S 100 P H
AC S 12 5P H
1023456
1
2
3
4
0
789 10
5
102 345 6
1
2
3
4
0
789 10
5
102345 6
1
2
3
4
0
789 10
5
P ath at center
Horiz ontal air throw dis ta nce (m)
*
*
Vertica l air throw distance (m)
Air s pee d a t c enter of discha rge a irflow (m/s)
Dis charge angle is approx. –7 during c ooling
and approx. 54 during heating.
C ooling
Horiz ontal air throw dis ta nce (m)
*
*
Vertica l air throw distance (m)
Air s pee d a t c enter of discha rge a irflow (m/s)
Dis charge angle is approx. –7 during c ooling
and approx. 54 during heating.
C ooling
Horiz ontal air throw dis ta nce (m)
*
*
Vertica l air throw distance (m)
Air s pee d a t c enter of discha rge a irflow (m/s)
Dis charge angle is approx. –7 during c ooling
and approx. 54 during heating.
C ooling
He atingHe ating
He ating
Air s pee d a t c enter
P ath at center
P ath at centerP ath at centerP ath at center
Air s pee d a t c enter
Air s pee d a t c enter
P ath at center
1
1 - 71
1-11. Installation Instructions
■ TUBING LENGTH
(A) Single type
● Keep refrigerant tubing between the indoor and
outdoor units as short as possible.
● The length of the refrigerant tubes between the
indoor and outdoor units is limited by the elevation
difference between the 2 units. During tubing work,
try to make both the tubing length (L) and the difference in elevation (H1) as short as possible.
Refer to Table 1-5.
Table 1-1
Indoor unit type 71 types 100, 125 types
Maximum allowable tubing length50 m50 m
Charge-less tubing length (actual length)30 m30 m
Additional refrigerant charge per 1 m40g
Minimum tubing length3 m5 m
Single
L
H1
1
1 - 72
(B) Simultaneous operation multi (Twin, Triple, Double-Twin)
Because the indoor units run simultaneously, install them within the same room.
● For refrigerant tube branches, use the optional distribution joints.
● For cautions on the use of the optional distribution joints, be sure to refer to the provided instruction sheet. Also,
be careful to install them in the correct direction (orientation).
NOTE
Allowable
tubing
lengths
Maximum branch tubing
length
Maximum difference between lengths of No. 1 distribution tubing
(Double-Twin)
Maximum difference between lengths of No. 2 distribution tubing
(Double-Twin)
Maximum
allowable
height
difference
Item
Maximum allowable
tubing length
Maximum distribution
tubing length
Maximum indoor-outdoor
height difference
Maximum height difference between indoor units
One-way length of tubing from outdoor
unit to the most distant indoor unit
Maximum length following the first
branch point (No. 1 distribution)
Difference between the maximum
length and minimum length in tubing
following the first branch point
Description
If outdoor unit is higher
If outdoor unit is lower
* For connection tubing sizes, refer to table above.
Twin
Main
tubing L
1
Double-Twin
Single
L
–
–
–
–
–
A
Distribution joint
2
Twin
L + 1
L + 2
1, 2
1 > 2
1 – 2
––
––
H2
Triple
L + 1, L + 2
L + 3
1, 2, 3
1 > 2 > 3
1 – 2
1 – 3
2 – 3
H2, H3, H4H2, H3, H4, H5, H6, H7
Triple
H1
H2
Symbol
H1
H1
Main
tubing L
1
Double-Twin
L + L1 + 1, L + L1 + 2
L + L2 + 3, L + L2 + 4
L1 + 1, L1 + 2
L2 + 3, L2 + 4
Max.: L2 + 4
Min.: L1 + 1
(L2 + 4) – (L1+ 1)
L2 > L1
L2 – L1
2 > 1
4 > 3
2 – 1
4 – 3
B
Distribution tubing
3
2
H4H3
H2
H1
Actual
length (m)
≤ 50
≤ 15
≤ 10
≤ 10
≤ 10
≤ 30
≤ 15
≤ 0.5
Main tubing L
A
L1
A
1
2
Distribution joint No. 1
L2
Distribution joint
(purchase separately)
A = DDVI16
B = DTVP
H1
H7
Distribution joint
No. 2
3
A
4
H6
H2
H3
H5
NOTE
1
1 - 73
Table 1-2 Tubing Data for Models (Single, Twin, Triple, Double-Twin)
Table 1-3 List of Connection Tube Sizes
Charge with an amount of additional refrigerant calculated using the formula below, based on the values in Table 1-3
and the size and length of the liquid (narrow) tubing.
Amount of additional refrigerant charge (g)
Do not remove refrigerant from the system, even if the result of the calculation is negative. (Use with the current
refrigerant charge.)
(a) Actual length (m) of main tubing (φ9.52) Refrigerant charge per 1 m of actual length = 40 g/m (25 – 48 type)
(b) Total length of distribution tubing (φ9.52)Refrigerant charge per 1 m of actual length = 40 g/m
(c) Total length of distribution tubing (φ6.35)Refrigerant charge per 1 m of actual length = 20 g/m
Example
● Sample tubing lengths
L = 35 m1 = 5 m
L1 = 10 m2 = 5 m
L2 = 5 m3 = 5 m
4 = 10 m
● Find the liquid (narrow) tube size from Table 1-3.
L: φ9.52 (48 type)
L1 : φ9.52 (Total type capacity of indoor units 24)
L2 : φ9.52 (Total type capacity of indoor units 24)
1 – 4 : φ6.35
● The amount of additional on-site refrigerant charge is found by subtracting the outdoor unit
charge-less refrigerant amount from the total charge amount for all tube sizes.
φ9.52 → L: 35 m× 40 g / m = 1400
φ9.52 → L1 + L2 : (10 + 5) m× 40 g / m = 600
φ6.35 →1 – 4 : (5 + 5 + 5 + 10) m × 20 g / m = 500
Outdoor unit charge-less refrigerant amount –1200
Total +1300
● The amount of additional on-site refrigerant charge is 1,300 g.
Additional refrigerant amount (g) = Additional refrigerant for main tubing (g) + Additional refrigerant for distribution tubing (g)
No additional charge of compressor oil is necessary.
1
*
If total tubing length becomes 30 to 50 m, charge additional refrigerant by 40 g/m.
Double-Twin distribution tube (L1, L2)
Total type capacity of indoor units connected after
the branch
Type capacity of indoor units
Wide tube
Narrow tube
Amount of additional charge per 1 m
Main tubing (L)
25 – 48
φ15.88
φ9.52φ6.35
40 g
AES100PIC-PIHAES125PIC-PIH
505050
303030
151515
3 – 303 – 305 – 30
a) 40b) 40b) 40
Indoor unit connection tube
( 1, 2, 3, 4)
25
φ15.88
φ9.52
40 g
25 – 48
φ15.88
φ9.52
40 g
12 – 18
φ12.7
20 g
Outdoor unit
L
L1
21
L2
3
Indoor unit (12 type × 4)
4
1
1 - 74
CAUTION
1. This unit requires no additional refrigerant charge up to tubing length 30 m.
In case of more than 30 m, additional
refrigerant charge is required. Refer to
Tables 1-2 and 1-3.
2. In case of multi type installation,
indoor units should be installed within
the same room. If multi type indoor
units are installed in different rooms,
temperature control may develop problems because thermostat operation
must follow the thermostat condition
of 1 indoor unit only (the main unit).
Always check the gas density
for the room in which the unit is
installed.
Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can collect,
since refrigerant gas is heavier than air.
■ Check of limit density
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally escapes, its density does not exceed the limit level.
If the density might exceed the limit level, it is necessary to set up an opening between it and the adjacent
room, or to install mechanical ventilation which is interlocked with a leak detector.
(Total refrigerant charged amount: kg)
(Min. indoor volume where the indoor unit is installed: m
3
)
≤ Limit density 0.3 (kg/m3)
The limit density of refrigerant which is used in this unit
is 0.3 kg/m
3
(ISO 5149).
The shipped outdoor unit comes charged with the
amount of refrigerant fixed for each type, so add it to
the amount that is charged at the field. (For the refrigerant charge amount at shipment, refer to the unit’s
nameplate.)
Minimum indoor volume & floor area relative to
the amount of refrigerant is roughly as given in
the following table.
WARNING
3
2
m
m
135
50
121.5
45
40
35
30
25
20
15
Min. indoor floor area
(when the ceiling is 2.7 m high)
Min. indoor volume
10
5
Range below the
density limit of
0.3 kg/m
108
(Countermeasures
not needed)
94.5
81.0
67.5
54.0
40.5
27.0
13.5
3
Range above the
density limit of
0.3 kg/m
(Countermeasures
needed)
10
Total amount of refrigerant
203040 kg
3
CAUTION
1
1 - 75
■ SELECTING THE INSTALLATION SITE
AVOID:
● areas where leakage of flammable gas may be
expected.
● places where large amounts of oil mist exist.
● direct sunlight.
● locations near heat sources which may affect the
performance of the unit.
● locations where external air may enter the room
directly. This may cause “sweating” on the air discharge ports, causing them to spray or drip.
● locations where the remote controller will be splashed
with water or affected by dampness or humidity.
● installing the remote controller behind curtains or fur-
niture.
● locations where high-frequency emissions are gener-
ated.
DO:
● select an appropriate position from which every cor-
ner of the room can be uniformly cooled.
● select a location where the ceiling is strong enough
to support the weight of the unit.
● select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
● allow room for operation and maintenance as well as
unrestricted air flow around the unit.
● install the unit within the maximum elevation differ-
ence above or below the outdoor unit and within a
total tubing length (L) from the outdoor unit as
detailed in Tables 1-1 and 1-2.
● allow room for mounting the remote controller about
1m off the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.
Indoor Unit
Fig. 1-1
Fig. 1-2
Fig. 1-3
Ceiling-Mounted Type
Ceiling
Wall
min. 25 cm
Front view
min. 25 cm
NOTE
The rear of the indoor unit can be installed flush
against the wall.
Air
discharge
min. 50 cm
Side view
Air intake
Max. 25 cm
Obstacle
Concealed-Duct Type
1m
1m
1m
1m
1m
Wall-Mounted Type
min.
15 cm
min.15 cm
min.
15 cm
Front View
1
1 - 76
AVOID:
● heat sources, exhaust fans, etc. (Fig. 1-4)
● damp, humid or uneven locations
DO:
● choose a place as cool as possible.
● choose a place that is well ventilated and outside
air temperature does not exceed maximum 45°C
constantly.
● allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 1-5)
● use lag bolts or equal to bolt down unit, reducing
vibration and noise.
Installation space
Distance between obstructions and the unit air inlet
and outlet must be as shown below.
Outdoor Unit
Fig. 1-4
Fig. 1-5
Fig. 1-6
Fig. 1-7
In case of multiple installations
● provide a solid base (concrete block, 10 × 40 cm
beams or equal), a minimum of 15 cm above
ground level to reduce humidity and protect the unit
against possible water damage and decreased service life. (Fig. 1-7)
● use lug bolts or equal to bolt down unit, reducing
vibration and noise.
● Concerning inlet-side distance “C” (Fig. 1-5)
The minimum for distance “C” is 15 cm if there are no obstructions on the outlet side
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
“C” is 20 cm.
● If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
tions on 2 of the remaining 3 sides: *2, *3, *4.
● If wall *1 is on the outlet side (Fig. 1-5), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 1-5), then the minimum distance for “A” and “B” is 2 m (Fig. 1-6). Even
if there is no wall on the outlet side, a minimum of 100 cm is required.
*3
More than 1 cm
*2
Inlet side C
Outlet side
More than
100 cm
*1
More than 1 cm
*4
Air direction chamber
(field supply)
Hot air
Outdoor
unit
(Obstruction above unit)
*1
Exhaust fan
A
Inlet side
More than 20 cm
Heat source
B
(Obstruction on
inlet side)
CAUTION
Air in
Air
discharge
Anchor bolts
(4 pieces)
(Ground)
Air in
Min. 15 cm
1
1 - 77
■ ELECTRICAL WIRING
● General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the
wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be
provided in the exclusive line.
(3) To prevent possible hazards from insulation fail-
ure, the unit must be grounded.
(4) Each wiring connection must be done in accor-
dance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or
become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, please refer to
your LOCAL ELECTRICAL CODES before beginning.
You must ensure that installation complies with all
relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken
when wiring as follows:
● The remote control wiring and the inter-unit con-
trol wiring should be wired apart from the interunit power wiring.
● Use shielded wires for inter-unit control wiring
between units and ground the shield on both
sides.
(9) If the power supply cord of this appliance is dam-
aged, it must be replaced by a repair shop
appointed by the manufacture, because specialpurpose tools are required.
Recommended Wire Length and Wire Diameter for Power Supply System
* With ring-type wire terminal.
Outdoor unit
(A) Power supply
Wire size
AES71PIC-PIH 24 m
AES100PIC-PIH 22 m 25 A
AES125PIC-PIH 30 m 35 A
4 mm
4 mm
6 mm
Max. length
2
2
2
Time delay fuse or
circuit capacity
25 A
Indoor unit
Type
AWS
ACS, ADS
(B) Power supply
2.5 mm
Max. 150 m
Max. 130 m
Time delay fuse or
2
circuit capacity
10 A
10 A
Control wiring
(C) Inter-unit (between outdoor and
indoor units) control wiring
0.75 mm
Use shielded wiring*Use shielded wiringUse shielded wiring
2
(AWG #18)
Max. 1,000 m
(D) Remote control wiring(E) Control wiring for group control
2
0.75 mm
(AWG #18)
Max. 500 m
NOTE
0.75 mm
2
(AWG #18)
Max. 500 m (Total)
1
1 - 78
● Wiring System Diagrams
(1) Refer to the section “Recommended Wire Length
and Wire Diameter for Power Supply System” for
the explanation of “A,” “B,” “C,” “D,” and “E,” in the
above diagram.
(2) The basic connection diagram of the indoor unit at
right shows the 7P terminal board, so the terminal
board in your equipment may differ from the diagram.
(3) The refrigerant Circuit (R.C.) address should be
set before turning the power on.
Power supply
220-240V 50Hz
Remote
controller
1
WHT
BLK
Power supply
220-240V 50Hz
Power supply
220-240V 50Hz
1
2
2
Group control:
L
N
Ground
L
N
Ground
L
N
Ground
Indoor
unit (No. 1)
L
N
B
U1
Indoor
unit (No. 2)
B
U2
1
2
C
L
N
U1
U2
1
2
D
C
Indoor
unit (No. 3)
L
N
B
U1
E
U2
1
2
C
C
Ground
Ground
Ground
Ground
Outdoor unit
INV unit
L
N
1
2
A
Power supply
L
200-240V 50Hz
N
Indoor
Power supply
220-240V 50Hz
L
N
Ground
unit (No. n)
B
L
N
U1
U2
1
2
NOTE
7P terminal board
1(L) 2(N)
Power
supply
8P terminal board
U1
Inter-unit
control wiring
ACS Type
U2
R1
Remote
controller
5P terminal board
R2
1 2U1 U2 R1 R2
1(L)2(N)
Power
supply
U1
U2
Inter-unit
control wiring
ADS Type
R1 R2
Remote
controller
12345
1(L)2(N)
Power
supply
control wiring
AWS Type
U1 U2
Inter-unit
1
1 - 79
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the
short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor
units except any one of the outdoor units.
(When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop.
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-
address setting.
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 1 m are not included in the total branch number.)
CAUTION
Outdoor unitOutdoor unitOutdoor unit
Prohibited
Indoor unitIndoor unitIndoor unitIndoor unit
NO
Outdoor unitIndoor unitIndoor unitIndoor unit
NO
Indoor unitIndoor unitIndoor unit
Branch point
Prohibited
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unitIndoor unitIndoor unitIndoor unit
Branch
point
16 or fewer
Indoor unit
more than 1 m
Indoor unit
less than 1 m
Indoor unit
Outdoor unit
more than 1 m
Indoor unitIndoor unitIndoor unit
Outdoor unit
1
1 - 80
(5) Use shielded wires for inter-unit control wiring
(C) and ground the shield on both sides, otherwise misoperation from noise may occur.
Connect wiring as shown in the section
“Wiring System Diagrams.”
Loose wiring may cause
the terminal to overheat or
result in unit malfunction.
A fire hazard may also
exist. Therefore, ensure
that all wiring is tightly
connected.
When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the
terminal” and fasten the wire securely with the fixing
screw of the terminal plate.
How to connect wiring to the terminal
■ For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10
mm and tightly twist the wire ends.
(2) Using a Phillips head screwdriver, remove the ter-
minal screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal.
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screwdriver.
Opening of the electronic control valve is controlled
so that the appropriate operating conditions are maintained, based on the signal from each sensor (discharge temperature [TD], intake temperature [TS],
outdoor heat exchanger temperature [C1], and indoor
heat exchanger temperature [E1, E2]).
Discharge temperature release control
(1) This control lowers the operating frequency of the
compressor when electronic control valve control
is unable to maintain the appropriate operating
conditions because the discharge temperature
fails to decline or because there is a sudden
increase in the discharge temperature.
(2) If the discharge temperature exceeds 111°C, the
compressor is stopped and then restarted. (Error
count = 1)
(3) The error count is cleared when operation has
continued for 10 minutes after the compressor
was restarted.
(4) If (2) repeats 4 times without the error count being
cleared (error count = 4), alarm “P03” occurs.
Current release control
The compressor operating frequency is controlled so
that the current that is input to the inverter compressor
does not exceed the designated value (control value).
Outdoor unit fan control
1. Cooling fan control
(1) The outdoor unit fan minimum speed and maxi-
mum speed are determined according to the outdoor air temperature and the operating frequency.
The speed is controlled in stages between the
minimum speed and maximum speed, based on
the outdoor heat exchanger temperature (C2) at
that time.
(2) For 60 seconds after start, the outdoor unit fan
operates at maximum speed, as determined by
the outdoor air temperature and operating frequency at that time.
Subsequently, the fan operates at low speed until
the outdoor heat exchanger temperature (C2) rises.
(3) If the discharge temperature (TD) sensor is abnor-
mal or has become disconnected, the fan will not
operate and a protective device is activated.
2. Heating fan control
(1) The outdoor unit fan minimum speed and maxi-
mum speed are determined according to the outdoor air temperature and operating frequency. The
speed is controlled in stages between the minimum
speed and maximum speed, based on the outdoor
heat exchanger temperature (C1) at that time.
(2) If the outdoor heat exchanger temperature (C2) is
24°C or higher continuously for 5 minutes, fan
operation may stop (same conditions as when the
thermostat is OFF). In this case, the fan will
restart after 3 minutes.
(3) This control is not performed during the 3 minutes
after start, for 1 minute after defrost ends, and
while defrost is in progress.
Coil heating control
(1) This control applies current to the coil of the
stopped compressor to heat the compressor in
place of the crank case heater.
(2) When the discharge temperature (TD) is less
than 25°C, the current application judgment is
made based on the outdoor air temperature (TO).
• Current application starts when the outdoor air
temperature drops to 15°C or below.
• Current application stops when the outdoor air
temperature rises above 18°C.
Control for prevention of short intermittent
operation
In order to protect the compressor, this control does
not allow the compressor to be stopped for 10 minutes after operation starts, even if the thermostat OFF
signal is received from the indoor unit.
Control for prevention of high cooling loads
(1) This control reduces abnormal high-pressure
increases during cooling operation.
(2) If the outdoor heat exchanger temperature (C2)
reaches 64°C or above, the compressor is
stopped. (Error count = 1)
(3) 3 minutes after the compressor stops, if the out-
door heat exchanger temperature (C2) is less
than 55°C the compressor is restarted. If operation subsequently continues for 10 minutes, the
error count is cleared.
(4) If the outdoor heat exchanger temperature (C2)
again reaches 64°C or higher within 10 minutes
after the compressor restarts, the compressor is
stopped again. (Error count = 2)
(5) If the above start/stop of the compressor is repeat-
ed 10 times (error count = 10), alarm “P20” occurs.
At this time, operation stops and does not restart.
(6) If the compressor has stopped because the out-
door heat exchanger temperature (C2) reached
64°C or higher, and the temperature remains at
64°C or higher for 30 seconds, alarm “P20”
occurs even when the error count is less than 10.
At this time, operation stops and does not restart.
(7) For 30 minutes or longer after the compressor
restarts, the control value for “current release
control” is reduced to 70 – 90%.
2
2 - 3
Overcurrent protection control
(1) If the overcurrent protection circuit detects abnor-
mal current, the compressor is stopped. (Error
count = 1.) The compressor then restarts after 3
minutes.
(2) If compressor start/stop is repeated 4 times (error
count = 4), alarm “P26,” “P29,” or “H01” (count =
2 in this case only) occurs. Operation stops and
does not restart.
Current release value shift control
(1) This control is intended to improve compressor
reliability by preventing continuous high-frequency operation under overload conditions when the
outdoor air temperature is high, and by preventing intermittent operation through “control for prevention of high cooling loads.”
(2) The control value for “current release control” is
corrected according to the outdoor air temperature (TO).
Depending on the temperature, the control value
is lowered to 55 – 90% for cooling operation, and
to 85 – 98% for heating operation.
Freeze prevention (low-temperature release)
control
The below control is performed during cooling operation (including dehumidifying operation), using
whichever of the indoor heat exchanger temperatures
(E1 or E2) is lower. (See the figure below.)
(1) If a temperature in the “J” area (operating fre-
quency reduction and thermostat OFF area) is
detected for 6 minutes, the compressor operating
frequency is reduced.
The compressor operating frequency is reduced
every 30 seconds as long as the temperature
remains within this area.
(2) If the temperature is in the “K” area (operating
frequency increase-prohibit area), the compressor operating frequency is maintained.
(3) If the temperature is in the “H” area (operating
frequency control area), and the outdoor air temperature is less than 32°C, the compressor maximum operating frequency is limited according to
the indoor unit fan speed.
(4) If the temperature is in the “I” area (normal oper-
ating area), the compressors operate normally.
(5) If the temperature is continuously in the “J” area
and the compressor operating frequency reaches
0, then temperature A (temperature for changing
from “J” area to “H” area) is raised from 5°C to
12°C, and operation continues with the thermostat
OFF until the temperature reaches the “H” area.
Heating high-load control
The below control is performed during heating operation, based on the indoor heat exchanger temperature
(E2).
(1) If the temperature is in the “M” area (operating
frequency reduction and thermostat OFF area),
the compressor operating frequency is reduced.
The compressor operating frequency is reduced
every 30 seconds as long as the temperature
remains within this area.
(2) If the temperature is continuously in the “M” area,
the thermostat turns OFF.
(3) If the temperature is in the “N” area, operating
frequency increases are prohibited.
(4) If the temperature is in the “L” area, the operating
frequency is raised to the original frequency (the
frequency prior to frequency reduction) by 6 Hz
every 60 seconds.
* When the compressor turns ON and the E2 tem-
perature rises, the temperature at which the “M”
area is first entered is 54°C (36, 48 types) or higher
than 51°C (25 type).
If the E1, E2 temperature subsequently falls to the
“L” area, the temperature for entering the “M” area
is raised to 56°C (36, 48 types) or 52°C (25 type).
However if the E1, E2 temperature falls to the “L”
area and falls below 30°C, then the temperature for
entering the “M” area is changed back to 54°C (36,
48 types) or 51°C (25 type).
E1 (or E2) (°C)
I
22
17
5
2
H
A
(operating frequency
K
increase-prohibit area)
J
E1, E2 (°C)
(25 type) (36, 48 types)
58
65
Thermostat OFF
M
52 (51)
46
56 (54)*
52
(operating frequency
N
increase-prohibit area)
L
30*
2
2 - 4
Defrost control
(1) Frost detection
1. Outdoor heat exchanger temperature (C1) method
(15-minute mask after operation start)
2. Outdoor air temperature is –13°C or above and outdoor heat
exchanger temperature (C1) of –18°C or below is detected continuously for 20 seconds.
3. Outdoor air temperature is below –13°C and outdoor heat exchanger temperature (C1) of below (outdoor air temperature – 5)°C is
detected continuously for 20 seconds.
(2) Defrost cancel
• Defrost end conditions
1. Outdoor heat exchanger temperature (C1) rises to 12°C or higher.
2. Outdoor heat exchanger temperature is 7°C or higher continuously
for 1 minute.
3. Defrost time of 10 minutes has elapsed.
(3) Startup operation
After defrost ends, the compressors and outdoor unit fan stop for approximately 40 seconds, then operation begins in heating mode.
Defrost control
Defrost sequence
Heating operation
(25-minute mask)
1
Frost detection
Defrost start
(reverse cycle defrost)
2
Defrost cancel
Defrost in progress
Operating frequency: 61.8 Hz
•
Outdoor unit fan: OFF
•
Electronic control valve: step 300
•
4-way valve: OFF
•
Indoor unit fan: OFF
•
3
Start-up operation
Outdoor heat exchanger temperature (C1) (°C)
Outdoor air
–13.7010
–3
–8
–18
Temperature in defrost condition area is detected
continuously for 3 minutes or for 60 minutes in total.
temperature (TO) (°C)
X
Defrost condition area
2
2 - 5
2-2. Outdoor Unit Control PCB
(1) Layout Diagram (AES71PIH)
Heat exchanger temperature (C1) sensor
Heat exchanger temperature (C2) sensor
Intake temperature (TS) sensor
Outdoor air temperature (TO) sensor
Compressor temperature (TD) sensor
Refrigerant recovery switch
(S005)
Quiet mode plug (CN028)
MDC
EEPROM IC
System address switch
(S002)
EXCT plug (CN026)
Automatic address
setting switch (S001)
Snowfall sensor
System address switch
(S003)
Cooling test
Heating test
Test pin (CN036)
Operation circuit fuse
(F002)
LED 1, 2
Serial 1 plug
Terminal plug (CN015)
Serial 2 plug
If the operation circuit fuse
(F002) has blown,
determine and correct the
cause for the blown fuse,
then change the socket
from the serial 1 plug to
the serial 2 plug.
Position detection plug
(CN003)
Fan motor plug (CN004)
2
2 - 6
2-2. Outdoor Unit Control PCB
(2) Layout Diagram (AES125PIH)
Heat exchanger temperature (C1) sensor
Heat exchanger temperature (C2) sensor
Intake temperature (TS) sensor
Outdoor air temperature (TO) sensor
Compressor temperature (TD) sensor
Refrigerant recovery switch
(S005)
Quiet mode plug (CN028)
MDC
EEPROM IC
System address switch
(S002)
EXCT plug (CN026)
Automatic address
setting switch (S001)
Snowfall sensor
System address switch
(S003)
Cooling test
Heating test
Test pin (CN036)
Operation circuit fuse
(F002)
LED 1, 2
Serial 1 plug
Terminal plug (CN015)
Serial 2 plug
If the operation circuit fuse
(F002) has blown,
determine and correct the
cause for the blown fuse,
then change the socket
from the serial 1 plug to
the serial 2 plug.
• If the system address switch (S002: set to 0 at time of shipment) setting is other than “0”
(central control), press this switch once to automatically set the addresses at all indoor units
which are in the same system, and are connected to that outdoor unit.
During automatic address setting, the 2 LEDs (red) on the outdoor unit control PCB blink
alternately.
(Pressing this switch again stops automatic address setting.)
• If automatic address setting is currently in progress at another system that is subject to central control, only LED 1 on the outdoor unit control PCB blinks to indicate that automatic
address setting is in progress at another unit. If automatic address setting is in progress at
another unit, automatic address setting cannot be started at this unit, even if S001 is
pressed.
S002Rotary switch (10 positions, black): System address setting switch
• This switch is set to 0 (1 system control) at the time of shipment. However the address for
each system must be set when multiple systems are controlled or when central control is
used. (Figure 1)
• If the system address is set to 0, automatic address setting is started when the power is
turned ON. Therefore it is not necessary to use switch SW01 and perform automatic address
setting in the case of single or simultaneous-operation multi control of a single system.
• When using central control for multiple systems, a maximum of 30 systems (maximum 64
units) can be connected. In the case of group control or central control, set the system
address to a setting other than 0 (1 or above).
• If the number of systems is greater than 9, this switch can be used in combination with DIP
switch S003 to set up to 30 systems. The setting can be made as high as 39, however all
settings above 30 are handled as 30 for control. (For details, refer to Table 1.)
• If system addresses are duplicated (the same address exists more than once), LED 1 on
the outdoor unit control PCB lights up, and alarm “L04” is displayed on the remote controller.
S003DIP switch (2P, blue): System address 10s-digit and 20s-digit place setting switch
• When setting 10 systems or more, set this switch in combination with S002.
• For 10 – 19 systems, set 1P (10s-digit place) to ON.
• For 20 – 29 systems, set 2P (20s-digit place) to ON, and set 1P (10s-digit place) to OFF.
• For 30 systems, set both 1P (10s-digit place) and 2P (20s-digit place) to ON.
• Press this switch to perform refrigerant recovery control using cooling operation. The indoor
unit fan will operate at HIGH and 55 Hz for a maximum of 10 minutes. When refrigerant
recovery is completed, close the valves and press this switch to stop the operation.
Test (CN036)2P plug (red): Pin used for PCB inspection at the factory
EXCT (CN026)3P plug (red): Can be used for demand control
• The operating ranges are shown in the table.
Short-circuited
2P and 3P 1P and 3P
0
0
1
1
0
1
0
1
Operating
range
100%
75%
50%
0%
Terminal plug 3P plug (black): Terminal plug for the communications line
(CN015)• At the time of shipment from the factory, the short-circuiting socket (2P, black) is installed
between pins 1 and 2 on the terminal plug (terminal = yes).
• When central control is used for multiple systems, leave the short-circuiting socket in place
only on the outdoor unit with a system address of 1. At all other outdoor units (other than
unit No. 1), move the short-circuiting socket to between 2 and 3 (terminal = no).
If multiple short-circuiting sockets remain in place during central control, a communications
failure will occur.
• In the case of a single system only (system address = 0), do not remove the short-circuiting
socket. (Alarm “E04” will occur.)
Quiet mode 2P plug (white): Enables operation in quiet mode.
(CN028)• The outdoor unit fan and compressor frequencies are subject to limits during operation.
• Low-noise operation is enabled when the relay is turned ON.
● Example of wiring
Outdoor unit control PCB
Note 1: The maximum length of the wiring between the outdoor unit PCB and the relay is 2 m.
• Lead wire with 2P plug (special-order part: WIRE K/ 623-161-2098)
• Relay, field supply, contact input specifications: DC 5 V, 0.5 mA
(Recommended relay: Fuji Electric HH62SW, compatible with micro contacts)
• Use a commercially available timer (such as the Omron H5 daily time switch).
2
2 - 8
Table 1. Method of System Address Setting
[S002 (rotary, black), S003 (2P DIP switch, green or blue)]
Fig. 1
• Example of wiring
Quiet mode
CN40
Relay (field supply)
1
1
2
2
Powe r
External contact
(timer input, etc.: field supply)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1P (10s-digit place)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
System
controller
Outdoor
In-
door
Outdoor
In-
door
Outdoor
In-
door
Outdoor
In-
door
2
2 - 9
2-3. Indoor Unit Control PCB Switches and Functions
■ For AC fan motor (CR-TRP50A)
VARISTOR (VA041)
FAN DRIVE (CN032)
OPTION
T10 (CN061)
JP1
EXCT (CN073)
FILTER (CN070)
EEPROM (IC010)
EMG (CN044)
OC (CN040)
DISP (CN072)
CHK (CN071)
GRL (C020)
POWER LED
VARISTOR (SG41)
FAN DRIVE (CN32)
OPTION
T10 (CN61)
JP1 (J01)
EXCT (CN73)
FILTER (CN70)
EEPROM (IC10)
EMG (CN44)
OC (CN40)
DISP (CN72)
CHK (CN71)
GRL (C20)
POWER LED
■ For DC fan motor (CR-SRP50A-1)
2
2 - 10
VARISTOR (VA002)
FAN DRIVE (CN017)
OPTION (CN014)
T10 (CN015)
JP001
EXCT (CN009)
FILTER (CN012)
EEPROM (IC002)
EMG (CN018)
OC (CN019)
DISP (CN010)
CHK (CN011)
■ For DC fan motor (CR-KRP50A)
VARISTOR (VA002)
FAN DRIVE (CN017)
OPTION (CN014)
T10 (CN015)
JP001
EXCT (CN009)
FILTER (CN012)
EEPROM (IC002)
EMG (CN018)
OC (CN019)
DISP (CN010)
CHK (CN011)
■ For DC fan motor (CR-KRP80A)
2
2 - 11
PCB Settings Section
1. Indoor Unit Control PCB Switches and Functions
[Indoor unit control PCB]
T10 (CN61-15):6P plug (YEL) / Used for remote control operation. (Refer to the Remote Control Section.)
Control items:(1) Start/stop input(2) Remote controller prohibit input
(3) Start signal output(4) Alarm signal output
EXCT (CN73-9):2P plug (RED) / Can be used for demand control. When input is present, forces the unit to
operate with the thermostat OFF.
DISP (CN72-10):2P plug (WHT) / Short-circuiting this plug allows operation to be controlled by the remote con-
troller even when an outdoor unit is not connected. (In this case, alarm “E04,” which indicates
trouble in the serial communication between the indoor and outdoor unit, does not occur.)
CHK (CN71-11):2P plug (WHT) / Test pin. Short-circuiting this pin allows the indoor FM (H fan speed), drain
pump, flap motor (F1 position), and electronic expansion valve full-open position to be
checked.
However this function turns OFF if the indoor unit protection mechanism is activated.
The components will operate even if the remote controller and outdoor unit are not connected, however the remote control cannot be used for control even if it is connected. This plug
can be used for short-term tests.
JP1 (J01):Jumper wire / Allows selection of the T10 terminal start/stop signal. (Refer to the Remote
Control Section.)
Setting at time of shipment: Pulse signal
Jumper wire cut: Static signal (continuous signal)
Fan drive (CN32-17): 2P plug (WHT) / This terminal sends the signal to the ventilation fan when a commercially
available ventilation fan is operated by the FAN button on the wired remote controller.
(Refer to the Remote Control Section.)
Use a ventilation fan which can accept the no-voltage contact A signal as the external input
signal.
Filter (CN70-12):2P (WHT) / This terminal is used to connect contact input from the differential-pressure
switch, used to detect filter clogging. When the contact is ON, “FILTER” appears on the display of the wired remote controller.
Power LED:LED (RED) / Illuminates when the power is ON. Flashes when there is trouble with the
EEPROM (IC10, IC010: nonvolatile memory).
EEPROM (IC10-02): Nonvolatile memory / Used to store model information and other data. When replacing the
PCB, remove the EEPROM from the old PCB and install it onto the new PCB. If there is IC
trouble, replace with a new IC (provided with the servicing PCB), and set the necessary
information using the wired remote controller. (For the setting procedure, refer to the servicing technical materials.)
GRL (CN20):
● For AC fan motor (CR-TRP50A) – 3P (YEL)
● For DC fan motor (CR-SRP50A) – 5P (BLU)
● There are 5P, 7P and 8P control PCB types for indoor units.