Aqua-Pure SS20 EPE-316L User Manual

INSTR3010 0406
Installation and Operating Instructions
Installation Instructions for SS EPE-316L Series
Congratulations on your purchase of this Aqua-Pure® high fl ow, single housing fi ltration system. This system is ideal for large homes, restaurants, schools, clubs, farms, camps, and institutions of all types. This system is ideal for locations where fl ow rates range up to 288 gallons per minute (1,090 lpm).
The all-metal housing is available with AP110, AP117, AP017 or without cartridges and features a single clamp for easy cover removal. An internal center rod with a tightening knob provides quick cartridge changes. All housing internal and external parts are stainless steel with the exception of the gasket which is Nitrile rubber and the Tightening Knob which is Polypropylene.
Design Features:
• Durable corrosion resistant 316L stainless steel construction
• Shouldered seal plates fi t solidly into the cartridge core to ensure a positive cartridge seal.
• V-band clamp for quick and easy opening and closing.
• Removable cartridge posts lift out for easy cleaning.
• Housing drains; both sludge and clean chambers have drain couplings for easy draining.
• Air vent allows venting before start-up or draining.
• High fl ow design accommodates up to 288 gpm (1,090 lpm) fl ow rate.
• High temperature capacity (up to 250°F [121°C], dependent of fi lter cartridge used).*
• Manufactured from FDA CFR-21 and/or NSF compliant materials.
*Not tested or certifi ed by NSF International
Specifi cations
Model No. Pipe Size
SS4 EPE-316L 1 1/2” NPT 19 1/2 8” 4 32 gpm 32gpm 32 gpm 12 gpm 12 gpm 32 gpm Series Male (49.5 cm) (20.3 cm) (121.1 lpm) (121.1 lpm) (121.1 lpm) (45.4 lpm) (45.4 lpm) (121.1 lpm)
SS8 EPE-316L 2” NPT 29 1/2 8” 8 64 gpm 64 gpm 64 gpm 24 gpm 24 gpm 64 gpm Series Male (74.9 cm) (20.3 cm) (242.3 lpm) (242.3 lpm) (242.3 lpm) (90.8 lpm) (90.8 lpm) (242.3 lpm)
SS12 EPE-316L 2” NPT 39 1/2 8” 12 96 gpm 96 gpm 96 gpm 36 gpm 36 gpm 96 gpm Series Male (100.3 cm) (20.3 cm) (363.4 lpm) (363.4 lpm) (363.4 lpm) (136.3 lpm) (136.3 lpm) (363.4 lpm)
SS20 EPE-316L 2” NPT 49 1/2 8” 20 160 gpm 160 gpm 160 gpm Series Male (125.7 cm) (20.3 cm) (605.7 lpm) (605.7 lpm) (605.7 lpm)
SS24 EPE-316L 3” - 150 # 40 9/16 12” 24 192 gpm 192 gpm 192 gpm Series Flange (103.0 cm) (30.5 cm) (726.8 lpm) (726.8 lpm) (726.8 lpm)
SS36 EPE-316L 3” - 150 # 50 7/16 12” 36 288 gpm 288 gpm 288 gpm Series Flange (128.1 cm) (30.5 cm) (1,090 lpm) (1,090 lpm) (1,090 lpm)
Dimensions
Height Diameter
Maximum
Pressure
150 psi
(1,034 kPa)
Replacement
CTG No.
AP110 AP111 AP124 AP117
APS117
AP420
AP017 AP110 AP111 AP124
Replacement
CTG Qty
Maximum Flow Rate
AP110* AP111 AP124 AP117 APS117
—— —
——
——
AP420*
CAUTION: To reduce the risks associated with water leakage, which, if not avoided, may result in property damage — check with your plumbing professional to verify that water pressure is less than 150 psi.
Flow rate is based on a maximum velocity of 8 ft/sec as required by National Standard Plumbing Code for water piping systems. At velocity of 10 ft/sec these values can be increased by 25%. Filter life will be greater with the 25 and 50 micron cartridges. Note: Filter housing with more cartridges at a given fl ow rate can greatly extend cartridge life. Note: Aqua-Pure fi lter housings may be used with various fi lter cartridges.
IMPORTANT: Activated carbon fi lters should not be used on water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system.
2
HOUSING
IN OUT
WALL
2 VALVES (EACH DRAIN REQUIRES A VALVE)
DRAINS
HOUSING
VALVEVALVE
MAIN DRAIN
WALL
IN OUT
DRAIN