Aquametrix 2200R User Manual

OPERATING INSTRUCTION MANUAL
MODEL 2200R
ORP ANALYZER
Water Analytics, Inc. 100 School Street Andover, MA 01810
Tel: (978) 749-9949
(888) 749-9099
Fax: (978) 749-9961
www.WaterAnalytics.net
TABLE OF CONTENTS
SECTION DESCRIPTION PAGE
1 GENERAL INFORMATION 1
2 SPECIFICATIONS 2
3 INSTALLATION 3
4 DESCRIPTION OF FUNCTIONS 8
5 START-UP AND OPERATION 14
6 OPERATING HINTS 20
7 UTILITY MENU 21
8 DIAGNOSTICS 23
9 TROUBLESHOOTING AND SERVICE 24
Model 2200R Page 1
MODEL 2200R ORP CONTROLLER
INSTRUCTION MANUAL
1.0 GENERAL INFORMATION
The AquaMetrix Model 2200R ORP analyzer is a versatile industrial microprocessor based instrument. Setpoints and outputs are programmed through the menu with push buttons on the face of the instrument. Calibration is achieved from the front panel menu.
The instrument may be used in conjunction with AquaMetrix 5-wire differential probes or with conventional combination probes. However, the differential probes are highly recommended for most processes.
The instrument provides non-isolated 0-5 Vdc, 0-1 mA and isolated 4-20 mA analog outputs. The 4­20 mA output may be programmed to represent any segment of the measuring scale. Two control relays may be individually programmed to activate on either rising or falling ORP, thus permitting bi­directional control. In addition, the instrument has a high / low alarm relay.
The integrity of the system is ensured with a watch-dog timer and system alarm. A user-enabled password feature protects all stored values.
The instrument is housed in a NEMA 4X enclosure. The standard unit is provided with mounting hardware for surface mount applications. Both panel and pipe mount kits can be ordered separately.
Model 2200R Page 2
2.0 SPECIFICATIONS
DISPLAY:
4 x 7 segment ½” LED Display
MEASURING RANGES:
ORP: 0 to 1000mV or -1000mV to +1000mV
POWER REQUIREMENTS: Standard: 98-132 Vac, 50/60 Hz (less than 5 VA) Optional: 196-264 Vac, 50/60 Hz (less than 5 VA)
23-26Vdc (nominal current 150mA)
AMBIENT CONDITIONS:
-30 to 50°C (-22 to 122°F) 0 to 90% R.H. non-condensing
CONTROL RELAY:
5A 115/230 Vac, 5A 30 Vdc SPDT
Selectable to activate in response to rising or falling
process Fully adjustable setpoint and deadband Manual Override Auto / Off / On for Relay A Cycling Feature: On time 0-600sec Off time 0-600sec Normal or Fail Safe operation
ALARM RELAY:
5A 115/230 Vac, 5A 30 Vdc SPDT
Programmable to activate at high and low alarm
setpoints Deadband fixed at 2% of Full Scale
Normal or Fail Safe Operation
RELAY INDICATORS:
Three individual LEDs indicate status of the two
control relays and the alarm relay.
ANALOG OUTPUTS:
Non Isolated 0-1mA, 100 ohms maximum load Non Isolated 0-5Vdc, 1000 ohms minimum load Isolated 4-20mA, 800 ohms maximum load
Range Expand: The analog outputs can be scaled to
represent any segment of the full scale of the
instrument. Minimum segment is 10% of Full Scale.
Output Hold: The analog outputs are automatically
placed on hold when the unit is placed in any menu
mode.
SENSOR-TO-ANALYZER DISTANCE:
Differential Probe (R60) 3000 feet maximum
Conventional combination probe 25 feet (an
AquaMetrix Series 101 preamplifier is required for
distances greater than 25 feet)
CALIBRATION:
Two point
TEMPERATURE READOUT:
Automatic 0°C to 100°C (32°F to 212°F) If probe has temperature compensation
SYSTEM ERROR:
A LED indicates a system alarm. The alarm relay can be programmed to activate upon system memory loss.
DIAGNOSTICS: Invalid entries are identified by respective flashing
LEDs. When a status error occurs, press CALL to obtain the status error number, which corresponds to a fault as described in the Status Fault Table.
TEST: Display value and analog outputs can be set manually
to any value for testing and diagnostic purposes. This feature allows the operation of the control relays, alarm relay, and outputs to be tested independently of process value.
SAFETY AND SECURITY: Non-volatile memory (EEPROM) Password protected if enabled Watch-dog timer monitors microprocessor
Instrument automatically returns to on line operation if accidentally left in menu mode. (This feature may be field disabled if desired.)
SENSITIVITY: 0.1% of span
STABILITY: 0.1% of span per 24 hrs. non-cumulative.
NON-LINEARITY: 0.1% of span
REPEATABILITY: 0.1% of span or better
TEMPERATURE DRIFT:
Zero: 0.01% of span per °C Span: 0.01% of span per °C
RESPONSE TIME:
0.5 second to 90% of value upon step change
ENCLOSURE:
NEMA 4X molded fiberglass reinforced polyester enclosure with four 1/2" conduit holes and mounting feet for surface mount. A NEMA 4 plug is provided for one hole.
MOUNTING CONFIGURATIONS:
Standard is surface mount Optional panel mount hardware Part No. C35-68 Optional pipe mount hardware Part No. C35-69
NET WEIGHT: 3 1/2 lb. (1.6 kg)
Approvals: CSA
Model 2200R Page 3
3.0 INSTALLATION
3.1 Location
3.1.1 Install the instrument within 3000 feet of where the AquaMetrix differential probe (R60 Series) is installed. If a conventional combination probe (R500 Series) is used the instrument must be within 25 feet of the probe for direct connection. An AquaMetrix 101 Series preamplifier may be used to extend this distance to 3000 feet.
3.1.2 Select an installation site which is:
• free of mechanical vibrations
• reasonably clean and dry
• protected from falling corrosive fluids within the ambient temperature and humidity
specifications
• remote from high voltage relay and power switches
3.2 Type of Mounting
3.2.1 If the instrument is to be pipe or panel mounted a special hardware kit will be required. For panel mount order part number C35-68. For pipe mount order part number C35-69. Instructions for both types of mounting will be included with the kits.
3.2.2 For surface mounting, four feet brackets, together with fastening screws, are provided with the instrument. These should be fastened to the back of the instrument and then it may be screwed or bolted in the selected location.
3.3 Conduit Connections
3.3.1 Four 1/2" conduit holes are provided in the bottom of the enclosure. One of these is fitted with an approved water tight plug. To maintain NEMA 4X integrity, approved conduit hubs must be used to connect conduit. The hubs must be connected to the conduit before being connected to the enclosure. Any unused conduit holes must be closed with water tight plugs or connectors.
3.3.2 For convenience of internal connections the right conduit hole (viewed from the front) should be used for power connection; the next hole to the left for relay outputs; the next hole to the left for analog outputs and finally the fourth hole for sensor input.
Model 2200R Page 4
3.4 Electrical Connections
The 2200P is available in 3 different power options, 120Vac, 240Vac, and 24Vdc. Refer to following sections for connecting the input power.
120Vac and 240Vac
3.4.1 To access the terminal strips open the door of the instrument and then unscrew the captive retaining screw near the upper right hand corner of the panel. Now swing open the panel to reveal the terminal strip on the power supply circuit board and the smaller terminal strip on the back of the main circuit board.
CAUTION: The instrument operates from line voltage. This constitutes a
possible shock hazard. Ensure that line power is removed before attempting connections. Note: A separate source of line power may have been connected to the floating relay contacts.
3.4.2 The terminal strip on the power supply board at the back of the instrument is labeled for line power, relay outputs and analog outputs. Connect the wiring in accordance with this labeling. (Refer to Fig.1A)
Terminals 4 and 5 are wired directly to the input line voltage. These terminals can be used to supply power to the relays. Use the common ground of Terminal 1as the ground for the auxiliary devices. A separate source of power can also be used to provide power to the relays. Ensure that the circuit breaker supplying the instrument is able to supply enough current to the auxiliary devices, to ensure proper operation of the instrument.
CAUTION: Connecting the line voltage to incorrect terminals may cause serious damage.
Model 2200R Page 5
24Vdc
3.4.3 To access the terminal strips open the door of the instrument and then unscrew the captive retaining screw near the upper right hand corner of the panel. Now swing open the panel to reveal the terminal strip on the power supply circuit board and the smaller terminal strip on the back of the main circuit board.
3.4.4 The terminal strip on the power supply board at the back of the instrument is labeled for input power, relay outputs and analog outputs. Connect the wiring in accordance with this labeling. (Refer to Fig.1B)
Model 2200R Page 6
3.5 Sensor Connections
3.5.1 Jumpers J42 are used to select which type of probe is being used. If a differential probe (R60) is used, ensure that both J42 jumpers are in the up position. If a combinational probe is used, ensure that both jumpers are in the down position. (Refer to Fig. 2)
3.5 Probe Connections: DIFFERENTIAL PROBE (R60 SERIES)
3.5.1 Ensure that both J42 jumpers are in the up position, leaving the pins nearest to the bottom exposed. Connect the 6 wires from the probe to the TB2 terminal strip on the main circuit board. Match the colors of the probe wires to the terminals marked on the circuit board. (Refer to Fig. 3)
Model 2200R Page 7
3.6 Sensor Connections; Combination Probe (P500 Series) Without Temperature Compensation
3.6.1 a) Both J42 jumpers located on the swing-out board must be in the down position leaving the pin nearest to the top exposed. (Refer to Fig. 4)
b) Connect the active electrode (ring terminal) to the terminal post on the swing-
out board and connect the shield to the SH terminal of the terminal strip TB2.
c) Connect a 300 ohm resistor to the YL and BL terminals on TB2.
3.7 Combination Probe with Preamplifier
3.7.1 If the analyzer is mounted in such a position that the 10 ft. cable on the combinational probe cannot be directly connected to the 2200R. An AquaMetrix 101 Series preamplifier is required. The pre-amplifier converts the signal so that it can be transmitted up to 3000 feet, the same as the differential (R60) probe. When the pre-amplifier is used the controller must be configured, as if you were using a differential (R60) probe. (Refer to FIG. 5)
Loading...
+ 21 hidden pages