by
by
Water Analytics
Aqua
Metrix
Metrix
Description
The model 2200D Dissolved Oxygen analyzer/controller is a rugged and dependable industrial grade microprocessor-based
instrument that is extremely easy to use.
Its large, bright LED digital display is clearly
visible even in direct sunlight. It’s speedy calibration and simple operator interface makes
this analyzer/controller a favorite with instrumentation departments in a wide variety of demanding industrial and municipal application.
Frequently used functions are accessed through
an intuitive step-through menu which is printed
directly on the front panel for ease of navigation. By pressing the MENU key the operator
scrolls through the menu, illuminating an LED
beside the selected item and displaying the
stored value. Arrow keys are used to change the
value. Seldom used or set-once adjustments,
such as password activation are located on DIP
switches on the back of the swing-out front panel.
INPUTS
The 2200D accepts a sensor input from the P91
sensor. The P91 sensor consists of a probe that
is tted with a cartridge (P91D) containing a pre cisely stretched permeable membrane, electrodes
and electrolyte. The inexpensive and easy to
change cartridge will provide continuous service
for years and is then easily replaced in minutes.
The cartridge is hermetically sealed for long shelf
life. Optional mounting hardware include submersion, ow through and “ball oat” assemblies.
Aquametrix Model 2200D
Dissolved Oxygen Anayzer / Controller
Features
• Dissolved Oxygen
level displayed in PPM
or Percent Saturation
• Intuitive step-through menu
design for quick and easy setup
• Bidirectional control
through two control relays
with independent setpoints
for Relay On and Relay Off
• High/low alarm relay
• ALARM LED on front panel
• Membrane perforation alarm
• Output signal is eld-scalable
meter; in a clean water sample to a lab meter;
in a saturated process; in saturated clean water and in air. To Calibrate, press the MENU key
until the CALIBRATION LED illuminates. Use
the arrow keys to set the value determined using a calibration method described above. Press
The Enter key twice. The unit is now calibrated.
OUTPUTS
The 2200D provides three analog outputs, including a 4-20 mA, 0-5 VDC and 0-1 mA. The instrument also provides control of external devices using its two independent control relays. An alarm
relay has both high and low set points with a xed
dead band. When this relay is energized, the Alarm
LED on the front panel also illuminates to clearly
indicate an alarm condition. Factory set for bidirectional control, both control relays can be set to
control either a rising or falling process, with easily
programmed Relay On and Relay Off set points.
DIAGNOSTICS
A self-diagnostics program clearly indicates any
system errors or faults by turning the STATUS LED
on the front panel from green to red. The operator
then scrolls through the menu to STATUS to determine the fault code. The Operator’s Manual indicates the source and likely remedy for the fault.
When the status fault is corrected the STATUS
LED will turn back to green.
for maximum resolution
• Altitude compensation
for maximum accuracy
• STATUS errors illumi-
nate LED on front panel
• Test feature allows simula-
tion of DO readings to test relay
setpoints and analog settings
• Password protection
and watchdog timer
Applications
• Industrial and Municipal
Waste Treatment
• Aeration basin monitoring
• Aquariums
• Fish Hatcheries
CALIBRATION
Calibration can be accomplished by using one
of seven different calibration techniques: in the
process to a portable meter; in clean water to
a portable meter; in a process sample to a lab
ENCLOSURE
Model 2200D is packaged in a rugged NEMA 4X
berglass reinforced polyester enclosure. It is ideally suited for heavy-duty outdoor applications
such as municipal and industrial wastewater applications.
100 School Street
Andover, MA 01810
978-749-9949
Toll free - 855-747-7623
www.WaterAnalytics.net
Model 2200D Dissolved Oxygen Analyzer / Controller
Technical Data
Display 4 x 7 segment 1/2” LED Display
Indicator Lights 4 LED indicators: Status, Alarm, Relay A,
Relay B
Measuring Range
D.O. 0 to 20.00 ppm
Temperature 0 to 400C (32 to 1040 F)
Power Requirements
Standard 98-132 VAC 50/60 Hz, (less than 10 VA)
Optional 196-26 4 VAC 50/60 Hz (less than 10 VA)
23-26 VDC (nominal current: 150 mA)
Ambient Conditions
Temperature -30 to 50°C (-22 to 122°F)
Humidity 0 to 90% RH non-condensing
Control Relays
Number Two Control Relays: Relay A, Relay B
Rating 5A 115/230Vac, 5A 30Vdc, SPDT
Bidirectional Relays factory preset for bidirectional con-
trol, can be individually eld set for rising or
falling process
On/ Off Setpoints Field selectable full scale
Fail-safe Normal or fail safe operation
Relay Indicators Three individual LED’s indicate status of
two control relays and alarm relay.
Analog Outputs
Non-isolated 0-1 mA, 100 W maximum load
Non-isolated 0-5 VDC, 1000 W minimum load
Isolated 4-20 mA, 800 W maximum load Output
is isolated from the input, the ground, line
power and all other outputs.
Range Expand Outputs can be scaled to represent any
segment of the instrument scale to a minimum of 10% of full scale.
Output Holds The analog outputs are automatically
placed on hold when the instrument is
placed in the menu mode
Temperature The 0-1 mA and 0- 5 V dc output can be se-
lected to track either the dissolved oxygen
level of the process or the temperature of
the process.
Temperature Compensation
Automatic 0-40°C (32 to 104°F)
Diagnostics
Invalid Entries Identied by ashing LEDs.
System Error Two color STATUS LED indicates system sta-
tus: Green no fault, Red system fault. Status
menu value indicates system problem and
likely solution.
Alarm LED Illuminates red when Alarm Relay is energized,
indicating high/low process value or memory
loss.
Test Display value and analog outputs can be man-
ually set to any value for testing and diagnostic
purposes.
Safety & Security
Operator Password protected (activated by DIP switch)
Memory Nonvolatile memory (EPROM)
Microprocessor Watchdog timer monitors microprocessor. In-
strument automatically returns to online operation if left in menu mode for more than 10 minutes and no key is pressed.
Sensitivity 0.1% of span
Stability 0.1% of span per 24 hours non-cumulative
Temperature Drift Zero - 0.01% of span per °C
Span - 0.01% of span per °C
Response Time 0.5 second to 90% of value upon step change
Enclosure NEMA 4X molded berglass reinforced polyes-
ter enclosure with four 1/2” conduit holes and
mounting feet for surface mount. A NEMA 4X
plug is provided for one hole.
Mounting
Standard Surface Mount
Optional Panel Mount kit P/N C35 -68
Pipe Mount kit P/N C35-69
Weight 3.5 lbs. (1.6 kg)
Related Products
P91 Dissolved Oxygen probe, for use with P91D cartridge
P91D Replaceable cartridge for P91 probe; thick membrane
MHDS Submersion Mounting Hardware
MHBF Ball Float Hardware
FTA2 Inline Mounting Hardware
Ordering Information
2200D Dissolved Oxygen Analyzer/Controller
1 120 Vac, 50/60 Hz Powe
2 240 Vac, 50/60 Hz Power
A Surface Mount
B Panel Mount
C Pipe Mount
1 Reserved
2200D
www.WaterAnalytics.net 978-749-9949 Toll free - 855-747-7623 (855-pHProbe)