Appleton Viamaster™ LED Series Emergency Battery Backup Luminaires Data Sheet

VIAMASTER™ LED SERIES EMERGENCY BATTERY BACKUP LUMINAIRES
Appleton® Linear LED luminaires provide over 1,000 lumens of illumination for 90 minutes of emergency lighting.
Compact and easy to install, they t the same footprint as their uorescent counterparts with all the benets LED
has to offer — year after year
• Provides up to 1250 lumens illumination for 90
minutes of emergency lighting.
after initial start up.
• Duration test is automatically performed once per
year.
• Green and Red LED lamps indicate charging status and provide fault warning.
• Positive safety switch disconnects power to LEDs and LED driver to allow maintenance in hazardous
locations.
• 60,000+ hour LED life, for years of maintenance free
operation.
• Universal, high efciency, driver covers voltage requirements for 120-277 Vac, 50/60 Hz +/- 10%.
• Standard 2KV surge suppression.
• Hinged cover with captive screws, and terminal block wiring for easy installation and maintenance.
• Standard screw-type terminal block can accept UL/ CSA 26 to 10 AWG wire.
• Contemporary, low prole design suitable for tight
spaces.
• Field replaceable LED driver, battery management module (BMM), battery pack, and lens.
• 5 Cell NiMH battery pack for longer emergency capability.
• Plug in connectors on battery pack for easy
maintenance.
• Industry-leading thermal management for safe, reliable operation over a wide temperature range.
• Easy retrot in same mounting footprint as Appleton’s FV Series uorescent xtures.
• Full range of lumen outputs, with light distribution equivalent to Appleton’s FV Series uorescent xtures.
Fusing option not available with Marine Outside Type (Salt Water) rating. Fusing option not permitted for cUL.
• 2 opposing 3/4” NPT hubs with adjacent terminal blocks for thru wiring. (1) 3/4” NPT close up plug provided.
SUITABLE LOCATIONS
• For use in locations where:
— Flammable gases, vapors and dusts are
present
— A high degree of corrosion resistance is
required
— Protection against dirt, water and
moisture is necessary
• Typical applications include:
— Oil reneries — Petrochemical facilities — Pulp and paper mills — Food processing plants — Waste and sewer treatment — Underground tunnels — General manufacturing facilities
STANDARD MATERIALS
• Housing: copperfree (4/10 of 1% max.)
aluminum
• Lens: thermal shock- and impact-resistant polycarbonate lens
• Gasket: silicone rubber, mechanically
secured
• Bolts: stainless steel
• Close up plugs: nickel plated brass
— Mounting hardware: See ordering
informations
STANDARD FINISHES
• Housing/Reector: gray polyester
NEC/CEC RATINGS
• Class I, Division 2, Groups A, B, C, D
• Class I, Zone 2, Group IIC
• Class II, Division 2, Groups F, G
• Class III
• Zone 22, Group IIIB
• Type 3R, 4, 4X
• Marine Outside Type- For USA Only
• IP66/67
• Suitable for Use in Wet Locations
NEC/CEC CERTIFICATIONS AND COMPLIANCES
• UL Standard: UL 1598, UL 8750, UL 844
• cULus Certied: E165014
• Ambient Temperature:
120-277 Volts:
-20 °C up to +55 °C (-4 °F up to +131 °F)
Appleton Grp LLC d/b/a Appleton Group. The Appleton and Emerson logos are registered in the U.S. Patent and Trademark Ofce. All other product or service names are the property of their registered owners. © 2017, Appleton Grp LLC. All rights reserved.
VIAMASTER™ LED SERIES EMERGENCY BATTERY BACKUP LUMINAIRES
Automatic Testing System (ATS)
Functional Full Duration
Starts within 24 to 45 hours after the initial powerup of the module Starts within 14 to 35 days after the initial power of the module
Occurs every 14 days after the initial aforementioned functional test Occurs every 364 days after the initial aforementioned functional test
Lasts for 5 minutes Lasts for the full duration of the rated emergency period
At the completion of functional and full duration tests, LED indicator will display the status of the emergency luminaire when AC is present
LED Indicator LED Array
Standard Catalog Numbers LLEDA12LU2H LLEDA15LU2H LLEDA17LU2H
Voltage Range LU 120 – 277 Vac, 50/60 Hz
LED Lumens
Standard Operation
LED Lumens
Emergency Operation
Clear 2,200 4,400 7,800
Diffused 1,800 3,800 6,400
Clear 1,250
Diffused 1,000
Input Power (W) 24 45 83
Efficacy (LPW) 92 98 94
Ambient Temperature
-20 °C up to +55 °C
(-4 °F up to +131 °F)
T-Rating T3C @ +65 °C (+149 °F) T4 @ +65 °C (+149 °F)
Correlated Color Temperature (CCT) 5650
Color Rendering Index (CRI) 70
Fixture Length .843 m (33.2 in) .843 m (33.2 in) 1.2 m (47.2 in)
Fixture Weight 8.75 kg (19.3 lbs) 8.89 kg (19.6 lbs) 9.07 kg (20.0 lbs)
Housing: copperfree aluminum
Standard Materials
Finish: gray polyester
Lens: thermal shock- and impact-resistant polycarbonate lens
Lifetime 60,000+ hours
For optional safety cable, add the suffix C to the end of the catalog number; example: LLEDA12LU2C.
For optional fuse, add the suffix F to the end of the catalog number; example: LLEDA12LU2F
Loading...