Uninterruptible Power Supplies
S4K2U-C and S4K2U-5C Industrial On-Line UPS
The SolaHD S4KC Series is a single phase, on-line (doubleconversion) UPS system available in 700-3000 VA, 120 V and 230 V. On-Line design means zero transfer time from external to internal power. When utility power fails, your
critical load remains supported by a seamless ow of power. Rack or tower congurable, the S4KC Series UPS offers
customers a higher power factor, longer battery life, higher reliability and reduced cost of ownership. Housed in a slim 2U package, the SolaHD S4KC protects equipment from virtually all power disturbances due to blackouts, brownouts, sags, surges or noise interference. The UPS includes internal batteries. Optional, matching external battery cabinets, also
in a slim 2U (3.5") size, offer extended battery runtime.
The LED display indicates battery capacity, percentage of UPS load, battery operation, bypass operation and UPS fault condition.
The rack-tower models are also supplied with securing
anges and rack slide mounting hardware is available
separately, if required. Units can be easily hardwired by removing the attached line cord and receptacle plate. All units include a conduit knockout cover in the box.
Applications
• Industrial Automation Systems
• Critical Microprocessors and PC Based Systems
• Robotics and Process Control
• Programmable Logic Controllers (PLC)
• Mission Critical and High Speed Networks
• Enterprise Telecommunication Systems
• Pharmaceutical and Medical Diagnosis Equipment
• Printing and Publishing Machinery
Features
Certifications and Compliances
• ABS Type Approved
• RoHS Compliant
ISTA Procedure 1A
• Hardwire capability for permanent installation
• Small 2U height maximizes available space
• Input and output noise suppression
• Higher output power factor of 0.90
• PWM (pulse-width modulation) inverter reduces output
voltage distortion
• Add on batteries for extended back-ups
• Integral sealed non-spillable batteries
• Hot swappable user replaceable battery
• Automatic restart
Note: The securing anges do not support the weight of the UPS. Rack slides or shelves are required (sold separately).
EAC applies only to certain CE models.
E179213
• Automatic and manual battery test
• Rack-mount or stand-alone tower mounting
• Units are eld congurable with a PC as a frequency con-
verter (bypass will be disabled)
• Select S4KC models use an average of 35% less energy
than their standard counterparts
• Select S4KC models provide continuous uptime for the
connected equipment, with capacity and battery back-up delivered in cabinets that use 2U of rack space
• Integral dynamic bypass reduces shutdowns
• Compatible with most standby generators
• Two year limited warranty
All Models
S4K2U-C, S4K2U3000-5C:
Listed, UPS Equipment
- UL 1778
- CSA C22.2 No. 107.3
S4K2U-C:
• ENERGY STAR certied:
- 700, 1000, 1500, 2000, 3000 VA 120 V input
S4K2U-5C:
: EC/EN/AS 62040-1-1:2008
• EAC: TR CU 004/2011 - Technical Regulation of Custom Union "On the safety of low-voltage equipment”
ENPC
© December 2018
73
Uninterruptible Power Supplies
Selection Table - S4K2U-C & S4K2U-5C Tower/Rack-Mount Models
Capacity
(VA/W)
120 Vac, 50/60 Hz Models
700/630
1000/900
1500/1350
2000/1800
3000/2700
230 Vac, 50/60 Hz International Models
1000/900
2000/1800
3000/2700
* Full/Half Load (in minutes) at rated wattage.
Catalog Number
S4K2U700C
S4K2U1000C
S4K2U1500C
S4K2U2000C
S4K2U3000C
S4K2U10005C
S4K2U20005C
S4K2U30005C
Typical Back-up Times *
(minutes)
11/27 5-15P / (6) 5-15R
7/17 5-15P / (6) 5-15R
4/11 5-15P / (6) 5-15R 57.3 (26.00)
3/11 5-20P / (6)5-20R (15/20 amp type) 61.7 (28.00)
3/11 L5-30P / (5)5-20R (15/20 amp type): (1) L5-30R 70.5 (32.00)
6/17 IEC 320-C14 / (6) IEC 320/C13 44.0 (20.00)
3/11 IEC 320-C20 / (6) IEC 320-C13 61.7 (28.00)
3/11 IEC 320-C20 / (6) IEC 320-C13 (1) IEC 320-C19 70.5 (32.00)
Input Plug/Output
Receptacle
Approx. Ship
Weight - lbs (kg)
52.9 (24.00)
74
© December 2018
Uninterruptible Power Supplies
S4K2U-C, 120 Vac, 50/60 Hz Tower/Rack-Mount Models Specifications
Catalog Number S4K2U700C S4K2U1000C S4K2U1500C S4K2U2000C S4K2U3000C
Dimensions - D x W x H, in. (mm)
Unit
Shipping
Unit
Shipping
Voltage Range (typical)
90% to 100% Loading
70% to 90% Loading
30% to 70% Loading
0% to 30% Loading
Power Factor
Frequency
Input Power Cord
Output Receptacles
Voltage
Waveform
Utility (Vac) Mode Overload
Power Factor
Type
Qty x V x Rating
Battery Mfr./Part Number
Recharge Time
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Storage Elevation
*
*
19.70 x 16.90 x 3.40 (500.4 x 430.0 x 86.4)
25.50 x 23.90 x 10.60 (648.0 x 607.1 x 270.0)
Weight - lbs. (kg)
37.0 (16.80) 51.1 (23.20) 51.1 (23.20) 71.4 (32.40)
44.1 (20.00) 57.3 (26.00) 57.3 (26.00) 79.4 (36.00)
Input AC Parameters
120 Vac nominal; variable based on output load
90 Vac/140 Vac 102 Vac/140 Vac
86 Vac/140 Vac 96 Vac/140 Vac
77 Vac/140 Vac 84 Vac/140 Vac
60 Vac/140 Vac 60 Vac/140 Vac
0.99
40 Hz to 70 Hz; auto sensing
10 ft. attached with NEMA 5-15P plug
Output AC Parameters
5-15R x 6 5-20R x 6 L5-30R x 1 + 5-20R x 6
110/115/120/127 Vac (user-congurable) ±3%
Sine wave
200% for 2 seconds; 150% for 50 seconds with transfer to bypass
0.90
Battery
Valve-regulated, non-spillable, lead acid
4 x 12 V x 5.0 Ah 4 x 12 V x 7.2 Ah 4 x 12 V x 9.0 Ah 6 x 12 V x 9.0 Ah
YUASA/NPH5-12; CSB/HR 1221W
3 hours to 90% capacity after full discharge with 100% load until UPS auto shutdown (internal batteries only)
Environmental Requirements
0°C to +40°C; See Operating Temperature Parameters
Panasonic/UP- RW1245;
CSB/UPS12460F2
-15°C to +50°C
0% to 95%, non-condensing
Up to 10,000 ft. (3,000 m)
50,000 ft. (15,000 m) max.
10 ft. attached with
NEMA 5-20P plug
Panasonic/UP-RW1245; CSB/UPS12460F2
23.70 x 16.90 x 3.40
(602.0 x 430.0 x 86.4)
29.40 x 23.40 x 10.60
(747.0 x 594.4 x 270.0)
10 ft. attached with NEMA L5-30P plug
Notes: * Input power cord and output receptacles can be removed for hardwired applications.
© December 2018
75
Uninterruptible Power Supplies
S4K2U-C, 120 Vac, 50/60 Hz Tower/Rack-Mount Models Specifications - continued
Catalog Number S4K2U700C S4K2U1000C S4K2U1500C S4K2U2000C S4K2U3000C
Audible Noise
EMC
Ambient Temperature
<43 dBA max. @ 3 ft. (1 m) front &
sides; <46 dBA max.
@ 3 ft. (1 m) rear
<45 dBA max. @ 3 ft. (1 m) front & sides; <50 dBA max. @ 3 ft.
(1 m) rear
Operating Temperature Parameters
+25°C to +30°C +30°C to +35°C +35°C to +40°C
<46 dBA max. @ 3 ft. (1
m) front & sides; <45 dBA
max. @ 3 ft. (1 m) rear
Standards
FCC Part 15, Class A
<48 dBA max. @ 3 ft. (1 m) front & sides;
<48 dBA max. @ 3 ft. (1 m) rear
Maximum output power factor derating at maximum load
100% to 93% 93% to 86% 86% to 79%
76
© December 2018
Uninterruptible Power Supplies
S4K2U-5C, 230 Vac, 50/60 Hz Tower/Rack-Mount Models Specifications
Catalog Number S4K2U1000-5C S4K2U2000-5C S4K2U3000-5C
Dimensions - D x W x H, in. (mm)
Unit
Shipping
Unit
Shipping
Voltage Range (typical)
90% to 100% Loading
70% to 90% Loading
30% to 70% Loading
0% to 30% Loading
Power Factor
Frequency
Input Power Receptacle
Output Receptacles
Voltage
Frequency
Waveform
Overload
Power Factor
Type
Qty x V x Rating
Battery Mfr./Part Number
Recharge Time
Operating Temperature
Storage Temperatures
Relative Humidity
Operating Elevation
Storage Elevation
*
*
200% for 2 seconds; 150% for
1 minute with transfer to bypass
YUASA/NPH5-12; CSB/HR 1221W Panasonic/UP-RW1245; CSB/UPS12460F2
3 hours to 90% capacity after full discharge with 100% load until UPS auto shutdown (internal batteries only)
19.60 x 16.90 x 3.30 (497.0 x 430.0 x 85.0)
28.20 x 22.40 x 10.30 (717.0 x 570.0 x 262.0)
Weight - lbs. (kg)
37.0 (16.80) 51.1 (23.20) 71.4 (32.40)
44.1 (20.00) 57.3 (26.00) 79.4 (36.00)
Input AC Parameters
230 Vac nominal; variable based on output load
177 Vac/280 Vac 196 Vac/280 Vac
168 Vac/280 Vac 184 Vac/280 Vac
150 Vac/280 Vac 161 Vac/280 Vac
115 Vac/280 Vac 115 Vac/280 Vac
IEC 320 C14 IEC 320 C20
Output AC Parameters
IEC 320 C13 x 6 IEC 320 C13 x 6; IEC 320 C19 x 1
208/220/230/240 Vac (user-congurable**) ±3%
Battery
Valve-regulated, non-spillable, lead acid
4 x 12 V x 5.0 Ah 4 x 12 V x 9.0 Ah 6 x 12 V x 9.0 Ah
Environmental Requirements
0°C to +40°C; See Operating Temperature Parameters
0.99
40 Hz to 70 Hz; auto sensing
50 Hz or 60 Hz
Sine wave
200% for 2 seconds; 150% for
50 seconds with transfer to bypass
0.90
-15°C to +50°C
0% to 95%, non-condensing
Up to 3,000 m (10,000 ft.)
15,000 m (50,000 ft.) max.
23.70 x 16.90 x 3.30
(602.0 x 430.0 x 85.0)
28.20 x 22.40 x 10.30
(717.0 x 570.0 x 262.0)
200% for 2 seconds; 150% for
55 seconds with transfer to bypass
Notes: * Input power cord and output receptacles can be removed for hardwired applications. **Contact Technical Support on any derating.
© December 2018
77
Uninterruptible Power Supplies
S4K2U-5C, 230 Vac, 50/60 Hz Tower/Rack-Mount Models Specifications
Catalog Number S4K2U1000-5C S4K2U2000-5C S4K2U3000-5C
Audible Noise
EMC
Ambient temperature
Maximum output power factor derating at maximum load
<43 dBA max. @ 1 m (3 ft.) front &
sides; <46 dBA max. @ 1 m (3 ft.) rear
Standards
IEC/EN/AS 62040-2 2
+25°C to +30°C +30°C to +35°C +35°C to +40°C
100% to 93% 93% to 86% 86% to 79%
nd
Edition = CISPR22 Class A; IEC62040-2 2nd Edition
Operating Temperature Parameters
<48 dBA max. @ 1 m (3 ft.) front & sides;
<48 dBA max. @ 1 m (3 ft.) rear
78
© December 2018
Uninterruptible Power Supplies
External Battery Cabinets Specifications
Catalog Numbers S4K2U48BATC S4K2U96BATC
Used with UPS models
Unit
Shipping
Unit
Shipping
Type
Qty x V x Rating
Battery Mfr./Part Number
Back-up Time
Operating Temperature
Storage Temperatures
Relative Humidity
Operating Elevation
Storage Elevation
S4K2U700C, S4K2U1000C (-5),
S4K2U1500C, S4K2U2000C (-5)
Dimensions - D x W x H, in. (mm)
19.70 x 16.90 x 3.40 (500.4 x 430.0 x 86.4) 23.70 x 16.90 x 3.40 (602.0 x 430.0 x 86.4)
24.30 x 22.40 x 10.30 (617.2 x 570.0 x 262.0) 28.20 x 22.40 x 10.30 (717.0 x 570.0 x 262.0)
Weight - lbs. (kg)
70.5 (32.00) 93.5 (42.40)
77.2 (35.00) 101.4 (46.00)
Battery
Valve-regulated, non-spillable, lead acid
2 x 4 x 12 V x 9.0 Ah 2 x 6 x 12 V x 9.0 Ah
Panasonic/UP-RW1245; CSB/UPS12460F2
Battery Back-up Times Chart
Environmental Requirements
0°C to +40°C
-15°C to +50°C; High ambient temperatures will reduce battery life
0% to 95%, non-condensing
Up to 10,000 ft. (3,000 m)
50,000 ft. (15,000 m) max.
S4K2U3000C (-5)
© December 2018
79
Uninterruptible Power Supplies
S4K2U-C Battery Back-up Times
Number of Batteries/Cabinets
Internal battery
Internal battery + 1 external battery cabinet
Internal battery + 2 external battery cabinets
Internal battery + 3 external battery cabinets
Model Rating
Load % of
Capacity
10% 105 90 123 92 82 20% 61 37 52 38 38 30% 37 30 34 23 23 40% 32 23 23 16 16 50% 27 17 18 12 12 60% 22 14 14 9 9 70% 18 11 11 7 7 80% 15 9 9 5 5 90% 13 8 7 4 4
100% 11 7 6 3 3
10% 426 332 335 303 224 20% 302 165 162 140 137 30% 163 137 129 96 95 40% 144 108 96 66 66 50% 125 92 72 49 49 60% 106 74 54 38 41 70% 94 61 46 33 34 80% 78 49 38 28 27 90% 69 40 34 23 23
100% 60 38 31 20 21
10% 480 456 451 431 427 20% 433 331 318 207 202 30% 327 222 187 150 149 40% 265 166 151 124 124 50% 201 152 131 97 98 60% 164 137 107 75 76 70% 153 122 91 61 62 80% 142 105 74 50 50 90% 131 95 64 41 45
100% 120 79 53 38 41
10% 480 480 480 455 452 20% 461 441 426 326 323 30% 438 336 312 197 196 40% 344 305 198 155 155 50% 322 209 160 136 136 60% 300 167 145 111 112 70% 213 157 130 96 98 80% 189 146 111 78 79 90% 163 135 99 68 70
100% 155 124 83 56 60
700 VA 1000 VA 1500 VA 2000 VA 3000 VA
Back-up Time in Minutes
Note: Run times in this table are approximate. They are based upon new, fully charged standard battery modules at a temperature of 25°C (77°F) with
100% resistive UPS loading. Run times listed above can vary by +/-5% due to manufacturing variances of the individual batteries
80
© December 2018
Uninterruptible Power Supplies
S4K2U-C Battery Back-up Times - continued
Number of Batteries/Cabinets
Internal battery + 4 external battery cabinets
Internal battery + 5 external battery cabinets
Internal battery + 6 external battery cabinets
Model Rating
Load % of
Capacity
10% 480 480 480 480 466 20% 480 459 446 424 421 30% 457 435 341 308 307 40% 441 339 309 192 192 50% 424 316 204 157 158 60% 336 221 164 142 143 70% 318 199 153 126 128 80% 301 166 141 107 109 90% 213 158 130 95 97
100% 197 149 112 79 81
10% 480 480 480 480 480 20% 480 466 458 441 439 30% 464 446 432 333 332 40% 451 427 333 225 225 50% 438 341 306 188 190 60% 424 322 207 158 159 70% 343 303 167 145 147 80% 329 212 158 133 135 90% 315 193 148 120 122
100% 300 166 139 104 107
10% 480 480 480 480 480 20% 480 480 467 452 450 30% 480 458 445 422 421 40% 462 442 422 319 319 50% 451 426 327 216 218 60% 440 342 304 185 188 70% 428 326 208 159 160 80% 370 309 184 148 149 90% 336 221 161 137 139
100% 324 204 153 126 129
700 VA 1000 VA 1500 VA 2000 VA 3000 VA
Back-up Time in Minutes
Note: Run times in this table are approximate. They are based upon new, fully charged standard battery modules at a temperature of 25°C (77°F) with
100% resistive UPS loading. Run times listed above can vary by +/-5% due to manufacturing variances of the individual batteries
© December 2018
81
Uninterruptible Power Supplies
S4K2U-5C Battery Back-up Times
Number of Batteries/Cabinets
Internal battery
Internal battery + 1 external battery cabinet
Internal battery + 2 external battery cabinets
Internal battery + 3 external battery cabinets
Model Rating
Load % of
Capacity
10% 91 81 91 20% 38 37 39 30% 31 23 23 40% 23 16 16 50% 17 12 12 60% 14 9 9 70% 11 7 7 80% 9 5 5 90% 8 4 4
100% 6 3 3
10% 334 222 302 20% 166 137 139 30% 138 94 95 40% 108 66 66 50% 92 49 48 60% 72 39 41 70% 56 34 34 80% 48 28 27 90% 40 23 23
100% 37 20 21
10% 457 426 431 20% 333 201 205 30% 224 149 150 40% 166 124 124 50% 151 97 97 60% 135 75 76 70% 113 61 63 80% 103 50 50 90% 92 41 45
100% 78 38 41
10% 480 451 455 20% 442 322 325 30% 337 195 196 40% 305 154 155 50% 208 136 136 60% 166 111 112 70% 155 96 98 80% 144 78 79 90% 132 68 70
100% 122 56 60
1000 VA 2000 VA 3000 VA
Back-up Time in Minutes
Note: S4K2U-5C models are not available in 700 VA or 1500 VA.
Run times in this table are approximate. They are based upon new, fully charged standard battery modules at a temperature of 25°C (77°F) with
100% resistive UPS loading. Run times listed above can vary by +/-5% due to manufacturing variances of the individual batteries
82
© December 2018
Uninterruptible Power Supplies
S4K2U-5C Battery Back-up Times - continued
Number of Batteries/Cabinets
Internal battery + 4 external battery cabinets
Internal battery + 5 external battery cabinets
Internal battery + 6 external battery cabinets
Model Rating
Load % of
Capacity
10% 480 466 480 20% 460 421 423 30% 436 306 307 40% 340 192 192 50% 315 157 157 60% 218 142 143 70% 195 127 128 80% 165 107 109 90% 156 95 97
100% 147 80 81
10% 480 480 480 20% 467 438 440 30% 447 331 332 40% 428 224 225 50% 341 189 189 60% 320 158 159 70% 227 146 147 80% 208 133 135 90% 189 120 122
100% 164 104 106
10% 480 480 480 20% 480 450 452 30% 458 420 421 40% 442 319 319 50% 426 217 217 60% 341 186 187 70% 323 159 160 80% 306 148 150 90% 217 137 139
100% 201 126 128
1000 VA 2000 VA 3000 VA
Back-up Time in Minutes
Note: S4K2U-5C models are not available in 700 VA or 1500 VA.
Run times in this table are approximate. They are based upon new, fully charged standard battery modules at a temperature of 25°C (77°F) with
100% resistive UPS loading. Run times listed above can vary by +/-5% due to manufacturing variances of the individual batteries
© December 2018
83