S4K2U-C and S4K2U-5C Industrial On-Line UPS
The SolaHD S4KC Series is a single phase, on-line
(doubleconversion) UPS system available in 700-3000 VA,
120 V and 230 V. On-Line design means zero transfer time
from external to internal power. When utility power fails, your
critical load remains supported by a seamless ow of power.
Rack or tower congurable, the S4KC Series UPS offers
customers a higher power factor, longer battery life, higher
reliability and reduced cost of ownership. Housed in a slim
2U package, the SolaHD S4KC protects equipment from
virtually all power disturbances due to blackouts, brownouts,
sags, surges or noise interference. The UPS includes internal
batteries. Optional, matching external battery cabinets, also
in a slim 2U (3.5") size, offer extended battery runtime.
The LED display indicates battery capacity, percentage of
UPS load, battery operation, bypass operation and UPS
fault condition.
The rack-tower models are also supplied with securing
anges and rack slide mounting hardware is available
separately, if required. Units can be easily hardwired by
removing the attached line cord and receptacle plate. All
units include a conduit knockout cover in the box.
Applications
• Industrial Automation Systems
• Critical Microprocessors and PC Based Systems
• Robotics and Process Control
• Programmable Logic Controllers (PLC)
• Mission Critical and High Speed Networks
• Enterprise Telecommunication Systems
• Pharmaceutical and Medical Diagnosis Equipment
• Printing and Publishing Machinery
Features
Certifications and Compliances
• ABS Type Approved
• RoHS Compliant
• ISTA Procedure 1A
• Hardwire capability for permanent installation
• Small 2U height maximizes available space
• Input and output noise suppression
• Higher output power factor of 0.90
• PWM (pulse-width modulation) inverter reduces output
voltage distortion
• Add on batteries for extended back-ups
• Integral sealed non-spillable batteries
• Hot swappable user replaceable battery
• Automatic restart
Note: The securing anges do not support the weight of the UPS. Rack slides or shelves are required (sold separately).
EAC applies only to certain CE models.
E179213
• Automatic and manual battery test
• Rack-mount or stand-alone tower mounting
• Units are eld congurable with a PC as a frequency con-
verter (bypass will be disabled)
• Select S4KC models use an average of 35% less energy
than their standard counterparts
• Select S4KC models provide continuous uptime for the
connected equipment, with capacity and battery back-up
delivered in cabinets that use 2U of rack space
• Integral dynamic bypass reduces shutdowns
• Compatible with most standby generators
• Two year limited warranty
All Models
S4K2U-C, S4K2U3000-5C:
•
Listed, UPS Equipment
- UL 1778
- CSA C22.2 No. 107.3
S4K2U-C:
• ENERGY STAR certied:
- 700, 1000, 1500, 2000, 3000 VA 120 V input
S4K2U-5C:
•
: EC/EN/AS 62040-1-1:2008
• EAC: TR CU 004/2011 - Technical Regulation of
Custom Union "On the safety of low-voltage equipment”
ENPC
© December 2018
73
Uninterruptible Power Supplies
Selection Table - S4K2U-C & S4K2U-5C Tower/Rack-Mount Models
Capacity
(VA/W)
120 Vac, 50/60 Hz Models
700/630
1000/900
1500/1350
2000/1800
3000/2700
230 Vac, 50/60 Hz International Models
1000/900
2000/1800
3000/2700
* Full/Half Load (in minutes) at rated wattage.
Catalog
Number
S4K2U700C
S4K2U1000C
S4K2U1500C
S4K2U2000C
S4K2U3000C
S4K2U10005C
S4K2U20005C
S4K2U30005C
Typical Back-up Times *
(minutes)
11/27 5-15P / (6) 5-15R
7/17 5-15P / (6) 5-15R
4/11 5-15P / (6) 5-15R 57.3 (26.00)
3/11 5-20P / (6)5-20R (15/20 amp type) 61.7 (28.00)
3/11 L5-30P / (5)5-20R (15/20 amp type): (1) L5-30R 70.5 (32.00)
6/17 IEC 320-C14 / (6) IEC 320/C13 44.0 (20.00)
3/11 IEC 320-C20 / (6) IEC 320-C13 61.7 (28.00)
3/11 IEC 320-C20 / (6) IEC 320-C13 (1) IEC 320-C19 70.5 (32.00)
Input Plug/Output
Receptacle
Approx. Ship
Weight - lbs (kg)
52.9 (24.00)
74
© December 2018
Uninterruptible Power Supplies
S4K2U-C, 120 Vac, 50/60 Hz Tower/Rack-Mount Models Specifications
Catalog Number S4K2U700C S4K2U1000C S4K2U1500C S4K2U2000C S4K2U3000C
Dimensions - D x W x H, in. (mm)
Unit
Shipping
Unit
Shipping
Voltage Range (typical)
90% to 100% Loading
70% to 90% Loading
30% to 70% Loading
0% to 30% Loading
Power Factor
Frequency
Input Power Cord
Output Receptacles
Voltage
Waveform
Utility (Vac) Mode Overload
Power Factor
Type
Qty x V x Rating
Battery Mfr./Part Number
Recharge Time
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Storage Elevation
*
*
19.70 x 16.90 x 3.40 (500.4 x 430.0 x 86.4)
25.50 x 23.90 x 10.60 (648.0 x 607.1 x 270.0)
Weight - lbs. (kg)
37.0 (16.80) 51.1 (23.20) 51.1 (23.20) 71.4 (32.40)
44.1 (20.00) 57.3 (26.00) 57.3 (26.00) 79.4 (36.00)
Input AC Parameters
120 Vac nominal; variable based on output load
90 Vac/140 Vac 102 Vac/140 Vac
86 Vac/140 Vac 96 Vac/140 Vac
77 Vac/140 Vac 84 Vac/140 Vac
60 Vac/140 Vac 60 Vac/140 Vac
0.99
40 Hz to 70 Hz; auto sensing
10 ft. attached with NEMA 5-15P plug
Output AC Parameters
5-15R x 6 5-20R x 6 L5-30R x 1 + 5-20R x 6
110/115/120/127 Vac (user-congurable) ±3%
Sine wave
200% for 2 seconds; 150% for 50 seconds with transfer to bypass
0.90
Battery
Valve-regulated, non-spillable, lead acid
4 x 12 V x 5.0 Ah 4 x 12 V x 7.2 Ah 4 x 12 V x 9.0 Ah 6 x 12 V x 9.0 Ah
YUASA/NPH5-12; CSB/HR 1221W
3 hours to 90% capacity after full discharge with 100% load until UPS auto shutdown (internal batteries only)
Environmental Requirements
0°C to +40°C; See Operating Temperature Parameters
Panasonic/UP- RW1245;
CSB/UPS12460F2
-15°C to +50°C
0% to 95%, non-condensing
Up to 10,000 ft. (3,000 m)
50,000 ft. (15,000 m) max.
10 ft. attached with
NEMA 5-20P plug
Panasonic/UP-RW1245; CSB/UPS12460F2
23.70 x 16.90 x 3.40
(602.0 x 430.0 x 86.4)
29.40 x 23.40 x 10.60
(747.0 x 594.4 x 270.0)
10 ft. attached with
NEMA L5-30P plug
Notes:
* Input power cord and output receptacles can be removed for hardwired applications.
© December 2018
75
Uninterruptible Power Supplies
S4K2U-C, 120 Vac, 50/60 Hz Tower/Rack-Mount Models Specifications - continued
Catalog Number S4K2U700C S4K2U1000C S4K2U1500C S4K2U2000C S4K2U3000C
Audible Noise
EMC
Ambient Temperature
<43 dBA max. @
3 ft. (1 m) front &
sides; <46 dBA max.
@ 3 ft. (1 m) rear
<45 dBA max. @ 3
ft. (1 m) front & sides;
<50 dBA max. @ 3 ft.
(1 m) rear
Operating Temperature Parameters
+25°C to +30°C +30°C to +35°C +35°C to +40°C
<46 dBA max. @ 3 ft. (1
m) front & sides; <45 dBA
max. @ 3 ft. (1 m) rear
Standards
FCC Part 15, Class A
<48 dBA max. @ 3 ft. (1 m) front & sides;
<48 dBA max. @ 3 ft. (1 m) rear
Maximum output power factor derating at maximum load
100% to 93% 93% to 86% 86% to 79%
76