Unicode™ 2 Series Illuminated Push Buttons
CONTROLS CONTROLS: NEC/CEC, ATEX/IECEX INCREASED SAFETY CONTROL STATIONS
© June 2017
Components for Increased Safety Enclosures
NEC/CEC:
Class I, Division 2, Groups A, B, B, C, D
Class I, Zone 1, AEx de IIC
Class I, Zone1, AEx e IIC
NEC/CEC:
Class II, Division 2, Groups F, G
Class III
Type 4X/IP66
Features
• Can be equipped with up to two Unicode 2 Series Contact
Blocks (UCB) contact blocks.
• Globally certied.
• Available in TS35 rail mounted or panel mounted.
• Long lifetime, high intensity single LED light.
• Rated operating voltage (Ue): 12 Vac to 254 Vac, 50/60 Hz and
12 Vdc to 60 Vdc.
• Terminal connection: 2.5 mm2 (0.004 in2)
• Operational life: 100,000 hours.
Standard Materials
• Body: polyamide
• Lens: polycarbonate
• Seal: ethylene propylene diene Monomer (M-class) rubber
(EPDM)
NEC/CEC Certifications and Compliances
• Certication Type TCe
— Operating Temperature: -40 °C to +60 °C (-40 °F to +140 °F)
— Ingress Protection (solid and liquid): IP66 and Type 4X
— CAN/CSA Standards: C22.2 No. 0-M91, No. 14-05,
No. 94-M91, No. 213-M1987, No. 60079-0:07,
No. 60079-1:07, No. 60529:05, E60079-7-03, E61241-1-1:02
— UL Standards: UL 508, UL 50E, UL 60079-0, UL 60079-1,
UL 60079-7
— Other Standards: ANSI/ISA 12.12.01-2011, ANSI/ISA
61241-0 (12.10.02)-2006, ANSI/ISA 61241-1(12.10.03)-2006
— CSA Certicate: 2358701
ATEX/IECEx Certifications and Compliances
• Certication Type TCe (Actuator and Lens).
— Gas: Zone 1 and 2
– Conforming to ATEX 94/9/CE: II 2 G
– Type of Protection: Ex e IIC Gb
— Dust: Zone 21 and 22
– Conforming to ATEX 94/9/CE: II2 D
– Type of Protection: Ex tb IIIC Db
— Surface Temperature: -40 °C to +60 °C (-40 °F to +140 °F)
— CE Declaration of Conformity: 5C242
— ATEX Certicate: LCIE 09 ATEX 3010U
— IECEx Certicate: IECEx LCI 09.0011U
— Index of Protection according EN/IEC 60529: IP66
— Impact Resistance (shock): IK10
• Certication Type CVe (Contact Block and Pilot Light)
— Gas: Zone 1 and 2
– Conforming to ATEX 94/9/CE: II 2 G
– Type of Protection: Ex e IIC
— Dust: Zone 21 and 22
– Conforming to ATEX 94/9/CE: II2 D
– Type of Protection: Ex tD A21
— Surface Temperature: -40 °C to +75 °C (-40 °F to +167 °F)
— CE Declaration of Conformity: 5C243
— ATEX Certicate: LCIE 09 ATEX 3001U
— IECEx Certicate: IECEx LCI 09.0002U
ATEX/IECEx:
Zone 1 and 2 – 21 and 22
II 2 GD
IP66 – IK10
ULG0H
(rail mounted contacts)
UCB
Contact Block
(panel mounted contacts)
ULG0P
UIL08
EURASEC Certification
• Certication Type TCe (Actuator and Lens)
— EURASEC RU C-FR. ГБ05.B00909
• Certication Type CVe (Contact Block and Pilot Light)
— EURASEC RU C-FR. ГБ05.B00909
Other Certification
• Certication Type TCe (Actuator and Lens)
— INMETRO Certicate: BVC 10.0044-U
• Certication Type CVe (Contact Block and Pilot Light)
— INMETRO Certicate: BVC 10.0047-U
Overall hazardous location and ingress protection rating depends on the rating of the optional certified components used.
INMETRO certification available on special request only. Contact your local sales representative for more information.
214

Unicode™ 2 Series Illuminated Push Buttons
(1.36”)
Ø 39 mm (1.54”)
13 mm
CONTROLSCONTROLS: NEC/CEC, ATEX/IECEX INCREASED SAFETY CONTROL STATIONS
© June 2017
Components for Increased Safety Enclosures
NEC/CEC:
Class I, Division 2, Groups A, B, B, C, D
Class I, Zone 1, AEx de IIC
Class I, Zone1, AEx e IIC
Weight kg (lb) Volume dm3 (in3)
NEC/CEC:
Class II, Division 2, Groups F, G
Class III
Type 4X/IP66
ATEX/IECEx:
Zone 1 and 2 – 21 and 22
II 2 GD
IP66 – IK10
Catalog Number
Rail Mounted Panel MountedRail Mounted Panel Mounted Rail Mounted Panel Mounted Pack
Spring Return Illuminated Push Button (contact block to be ordered separately)
For legend plates, guards and blanking plugs see accessories page.
Green 0.062 (0.137) 0.075 (0.165) 0.26 (15.87) 0.28 (17.09) 1 ULG0R ULG0P
Red 0.062 (0.137) 0.075 (0.165) 0.26 (15.87) 0.28 (17.09) 1 ULR0R ULR0P
White 0.062 (0.137) 0.075 (0.165) 0.26 (15.87) 0.28 (17.09) 1 ULW0R ULW0P
Blue 0.062 (0.137) 0.075 (0.165) 0.26 (15.87) 0.28 (17.09) 1 ULB0R ULB0P
Yellow 0.062 (0.137) 0.075 (0.165) 0.26 (15.87) 0.28 (17.09) 1 ULY0R ULY0P
1-Pole Contact Blocks
1 x NO
1 x NC UCB9R UCB9P
0.032 (0.071) 0.06 (3.66) 1
UCB5R UCB5P
Spare Parts
Rail to
panel
mounted
0.02 (0.04) 0.08 (4.88) 1 — UPMA
conversion
adaptor
Marking Color
Weight
kg (lb)
Volume
3
dm
(in3)
Pack
Catalog Number
Set of Five Spare Inserts
(unmarked) Green 0.01 (0.02) 0.01 (0.61) 1 UIAG
(unmarked) Red 0.01 (0.02) 0.01 (0.61) 1 UIAR
(unmarked) Yellow 0.01 (0.02) 0.01 (0.61) 1 UIAY
(unmarked) White 0.01 (0.02) 0.01 (0.61) 1 UIAW
(unmarked) Blue 0.01 (0.02) 0.01 (0.61) 1 UIAB
(unmarked) Black 0.01 (0.02) 0.01 (0.61) 1 UIAN
ON Green 0.01 (0.02) 0.01 (0.61) 1 UIA01
OFF Red 0.01 (0.02) 0.01 (0.61) 1 UIA02
START Green 0.01 (0.02) 0.01 (0.61) 1 UIA03
STOP Red 0.01 (0.02) 0.01 (0.61) 1 UIA04
MARCHE Green 0.01 (0.02) 0.01 (0.61) 1 UIA05
ARRET Red 0.01 (0.02) 0.01 (0.61) 1 UIA06
I Green 0.01 (0.02) 0.01 (0.61) 1 UIA07
O Red 0.01 (0.02) 0.01 (0.61) 1 UIA08
Dimensions in Millimeters (Inches) Wiring Diagram
52.5 mm (2.06”)
64 mm (2.52”)
58.5 mm (2.30”)
35 mm
(1.38”)
30 mm
(1.18”)
(0.51”)
34.5 mm
Ø 39 mm (1.54”)
(0.51”)
M30 x 1.5 (0.25”)
32 mm
(0.44”)
12.5 mm
(0.49”)
Rail Mounted Contacts Panel Mounted Contacts
Overall hazardous location and ingress protection rating depends on the rating of the optional certified components used.