Appleton Sealing Fittings, 500395001 Instruction Sheet

500395-1
DAMMING AND POURING :
AFTER POURING SEALING CEMENT
DRAIN
HOLE
CORE
WASHER
(PROVIDED)
FIBER FILLER
FIBER FILLER
ECDB DRAIN/ BREATHER
SEALING
COMPOUND
READY FOR USE
EYD AND EYDM SERIES 1/2" TO 1"
INSTRUCTION SHEET
INSTRUCTION FOR UNILET SEALING FITTINGS APPROVED FOR USE
®
WITH: APPLETON Kwiko
®
CROUSE-HINDS Chico
Appleton sealing unilets are UL listed for use in hazardous locations with Appleton Kwiko A compound or Crouse Hinds Chico A compound only. These compounds, when properly mixed and poured, hardens into a dense and strong mass which is insoluble in water, is not attacked by petroleum products and is not softened by heat.
The following sealing fitting series are UL listed for use with Appleton Kwiko A or Chico A sealing compounds: EYF, EYF-AL, EYM, EYM-AL, EYDM, EYDM-AL, EYD, EYS, EYSF, EYSF-AL, EYSM, EYSM-AL, ESUF, ESUM
A SEALING CEMENT
A AND
WARNING:
Fai lure to follo w saf ety instr ucti o ns may caus e i g n ition of haza r d o us atmosphe re resulting in serious personal injury and / or property damage.
STEP 1.
Install unilet and pull conductors through.
Remove plug(s) from sealing fitting and use fiber filler to make dam (s) in hub(s).
STEP 2.
Mi ner al Fib er Filler "Asbestos Free"
"A s b e s t o s Fr e e " S eali n g C e m e n t . B e sure to read the mi xi ng ins tr uc­tions on Sealing cement can.
DAMMING: Separate each conductor and pack fiber filler tightly into hub(s) behind conductors and around each conductor.
These conductors must not touch each other nor the sealing fitting wall.
Clean fiber shreds away from walls or conductors to prevent them from causing flame and / or leakage of gases. Finished dam must be flush with conduit hub bushing.
CAUTION Refer to Table 1 to determine the maximum number and size of con­ductors allowed in a seal. (Page 4)
STEP 3.
MIxing: Prepare sealing compound using a completely
clean mixing vessel in each batch. Shake the sealing cement thoroughly in all directions. Mix sealing cement with correct proportion of clean water as noted below.
APPLETON Kwiko A and CROUSE -HINDS Chico A CEMENT. Add one (1) part water to two (2) parts cement
by volume. Use cold water, warm water increases setting speed. Add water and stir immediately and thoroughly.
• DO NOT mix more than can be poured in 15 minutes after adding water.
These cements are NOT INSULATING COMPOUNDS and MUST NOT be used for such purposes.
EGS Electrical Group  •  www.appletonelec.com  •  800.621.1506
CAUTION: TEMPERATURE/CURE TIME
APPLETON Kwiko A and CROUSE-HINDS Chico A CEMENT
FOR GROUPS C AND D APPLICATIONS: Sealing com-
pound to be mixed ONLY at temperatures above 35º F (1.7º C) and ONLY poured into fittings that have been brought to a temperature above 35º F (1.7º C). Seals must NOT be
exposed to temperatures below 35º F (1.7º C) for a least 8  hours.   Compound  must be  allowed  8  hours  to cure  to  full 
strength before energizing system.
FOR GROUPS A AND B APPLICATIONS: Sealing com­pound to be mixed ONLY at temperatures above 40º F (4.4º C) and ONLY poured into fittings that have been brought to a temperature above 40º F (4.4º C). Seals must NOT be exposed to temperatures below 40º F (4.4º C) for a least 72 hours. Compound must be allowed 72 hours to cure to full strength before energizing system.
STEP 4
VERTICAL CONDUIT RUN. Pour sealing cement mixture into
the small pipe opening until the cement is level with the last thread of the opening. Replace and tighten small pipe plug.
HORIZONTAL CONDUIT RUN. Pour sealing cement mixture into the unilet through the large opening until two (2) to three (3) threads are covered with the cement.
Replace and tighten in sequence the large pipe plug or cover the small pipe plug into the unilet and the small pipe plug into the cover.
Damming and Pouring:
SEALING
VERTICAL CONDUIT
SEALING COMPOUND
FIBER FILLER
FIBER FILLER
HORIZONTAL CONDUIT
COMPOUND
Rev. "H " 07/01/09
SEALING UNILETS, EXPLOSION-PROOF, DUST-IGNITION-PROOF
FIBER FILLER
HORIZONTAL CONDUIT
SEALING COMPOUND
AFTER POURING SEALING CEMENT
DRAIN
HOLE
CORE
WASHER
(PROVIDED)
FIBER FILLER
FIBER FILLER
ECDB DRAIN/ BREATHER
SEALING
COMPOUND
EYSF AND EYSM SERIES 1/2" TO 4"
EYS 1/2" TO 1"
EYD SERIES 1-1/4" TO 4"
EYDM SERIES 1-1/4" TO 4"
READY FOR USE
EYD AND EYDM SERIES 1/2" TO 1"
SEALING COMPOUND
DRAIN TUBE
FIBER FILLER
FIBER FILLER
ECDB DRAIN/ BREATHER
SEALING
COMPOUND
EYD SERIES 1-1/4" TO 4"
EYDM SERIES 1-1/4" TO 4"
READY FOR USE
SEALING COMPOUND
FIBER FILLER
DRAIN TUBE
FOR USE IN VERTICAL CONDUIT RUNS.
EYSF AND EYSM SERIES 1/2" TO 4"
EYS 1/2" TO 1
1. Install Unilet and pull conductors through.
2. Remove the large pipe plug. Tighten the small pipe plug on
side of 3" and 4" Unilet sizes.
3. Dam the lower hub opening with Fiber Filler. (Page 1, Steps 1 & 2)
4. Mix sealing cement with the correct proportion of water per instructions provided with the cement. (Page 1, Step 3).
5. Pour Sealing Cement mixture into the Unilet opening until the cement is level with the last thread.
6. Replace and tighten pipe plug.
"
SEALING COMPOUND
FIBER FILLER
EYD SERIES 1-1/4" TO 4"
EYDM SERIES 1-1/4" TO 4"
1. Install Unilet and pull conductors through.
2. Remove the large threaded cover from the Unilet.
3. Dam the lower hub opening with fiber filler. (Page 1, Step 2).
4. Replace the large threaded cover so that the threaded hole
is facing downward.
5. Insert the tube and wire drain core into the opening of the large threaded cover so that the end being inserted will be above the compound in a completed seal. (See illustration above).
6. Be sure that the tube and wire drain core do not touch any of the conductors, Otherwise, this will expose the conductors in the completed and hardened seal. (See illustration above).
7. Mix Sealing Cement with the correct proportion of water per instructions provided with the cement. (Page 1, Step 3).
8. Pour Sealing Cement mixture into the Unilet through the opening located above the large cover until the last thread
is covered with cement.
9. After cement has cured, (See page 1, "Caution: Temperature
/ Cure Time") pull out the old tube and wire drain core and discard.
10. Thread the small pipe plug into this opening and tighten .
11. Thread ECDB drain-breather fitting into large cover
threaded hole and tighten secure.
Page 2 500395-1 Rev. "H " 07/01/09 EGS Electrical Group  •  www.appletonelec.com  •  800.621.1506
SEALING COMPOUND
FIBER FILLER
FIBER FILLER
VERTICAL CONDUIT
DAMMING AND POURING :
HORIZONTAL CONDUIT
SEALING COMPOUND
AFTER POURING SEALING CEMENT
DRAIN
HOLE
CORE
WASHER
(PROVIDED)
HORIZONTAL CONDUIT
VERTICAL CONDUIT
EYSF AND EYSM SERIES 1/2" TO 4"
EYS 1/2" TO 1"
EYD SERIES 1-1/4" TO 4"
EYDM SERIES 1-1/4" TO 4"
EYS, EYF AND EYM SERIES 1/2" TO 6"
EYD AND EYDM SERIES 1/2" TO 1"
SEALING COMPOUND
FIBER FILLER
FIBER FILLER
SEALING COMPOUND
SEALING UNILETS EXPLOSION PROOF, DUST IGNITION PROOF FOR USE IN
SEALING COMPOUND
FIBER FILLER
FIBER FILLER
VERTICAL CONDUIT
DAMMING AND POURING :
HORIZONTAL CONDUIT
SEALING COMPOUND
AFTER POURING SEALING CEMENT
DRAIN
HOLE
CORE
WASHER
(PROVIDED)
FIBER FILLER
FIBER FILLER
ECDB DRAIN/ BREATHER
SEALING
COMPOUND
HORIZONTAL CONDUIT
VERTICAL CONDUIT
READY FOR USE
EYD AND EYDM SERIES 1/2" TO 1"
SEALING COMPOUND
FIBER FILLER
VERTICAL AND/OR HORIZONTAL CONDUIT RUNS
EYS, EYF AND EYM SERIES 1/2" TO 6"
VERTICAL CONDUIT
NOTE: On  sizes  3-1/2" and  6"  the  cover  should  be tightened    down  with 
the small pipe plug removed from it. This will allow excess cement or air to escape out rather than seeping through or pushing the dam into the conduit. When the large cover has been tightened fully, replace pipe plug.
Vertical conduit
1. Install Unilet and pull conductors through.
2. Remove the pipe plug where the cement will be poured
through and the large pipe plug or cover with the small pipe
plug for size 3-1/2"-6" at the center of the Unilet.
3. Dam the lower hub with fiber filler. (Page 1, Steps 1 & 2.)
4. Replace the large pipe plug or cover with the small pipe
plug for 3-1/2" thru 6" and tighten all threaded joints securely.
5. Mix Sealing Cement with the correct proportion of water per instructions provided with the cement. (Page 1, Step 3).
6. Pour Sealing Cement mixture into the small pipe plug opening until the cement is level with the last thread of the opening.
7. Replace and tighten small pipe plug.
Horizontal conduit
1. Install Unilet and pull conductors through.
2. Remove all pipe plugs and / or cover from the Unilet.
3. Dam both hubs with fiber filler. (Page 1, Steps 1 & 2)
4. Mix Sealing Cement with the correct proportion of water
per instructions provided with the cement. (Page 1, Step 3).
5. Pour Sealing Cement mixture into the Unilet through the large opening until 2-3 threads are covered with the cement. Fill hole must be oriented in the upright position.
6. Replace and tighten in sequence the large pipe plug or cover, the small pipe plug into the Unilet and the small pipe plug into the cover.
ESUF AND ESUM SERIES 1/2" TO 1"
EGS Electrical Group  •  www.appletonelec.com  •  800.621.1506 500395-1 Rev. "H " 07/01/09 Page 3
SEALING COMPOUND
FIBER FILLER
HORIZONTAL CONDUIT
SEALING COMPOUND
FIBER FILLER
Vertical Conduit
1. Install Unilet and pull conduc-
tors through.
2. Remove flanged cover and the pipe plug from the Unilet.
3. Dam the lower hub opening with fiber filler (Page 1, Steps 1 & 2).
4. Replace the flanged cover.
5. Mix Sealing Cement with the
correct proportion of water per instr uctions provided with the cement (Page 1, Step 3).
6. P
our Sealing Cement mixture into the flanged cove opening until the cement level is equal to the last thread of the opening
7. Replace and tighten the small pipe plug.
Horizontal Conduit
1. Install Unilet and pull conductors through.
2. Remove the flanged cover.
3. Dam both hub openings with fiber filler (Page 1, Steps 1 & 2).
4. Mix Sealing Cement with the correct proportion of water
--
per instructions provided with the cement. (Page 1, Step 3).
5. Pour Sealing Cement mixture into the Unilet opening until the cement level is equal to the bottom of the cover mount­ing flange. Fill hole must be oriented in the upright position.
6. Replace the flanged cover, tighten the small pipe plug.
EYD AND EYDM SERIES 1/2" TO 1" DRAIN AND SEALING UNILETS EXPLOSION-PROOF, DUST-IGNITION-PROOF FOR USE IN VERTICAL CONDUIT RUNS
SEALING
COMPOUND
WASHER
DRAIN
HOLE
CORE
AFTER POURING
SEALING CEMENT
1. Install Unilet and pull conductors through.
2. Remove the pipe plug.
3. Dam the lower hub opening with fiber filler (See page 1,
Steps 1 and 2).
4. Insert rubber drain-hole core through drain opening and washer (provided) high enough so inner end of core will-be above sealing compound in completed seal.
Note: Washer (provided) must be inserted to last thread to form dam for sealing compound.
5. Be sure that the rubber drain - hole - core does not touch any of the conductors.
6. Mix Sealing Cement with the correct proportion of water per instructions provided with the cement (Page, 1 Step 3.).
7. Pour Sealing Cement mixture into the Unilet opening until the cement is level with the last thread of the opening.
8. Replace and tighten pipe plug.
9. Wh e n ce m e nt ha s cu r e d (s e e pa g e 1, " Caution:
Temperature / Cure Time") remove drain - hole - core.
10. Thread ECDB drain - breather fitting into threaded hole and tighten securely.
FIBER FILLER
ECDB DRAIN/ BREATHER
READY FOR USE
r
FIBER FILLER
Trade Conductor Type Max. No. Max. No. Permitted
Example On How To Use Table 1
  Size   Size  Permitted   For 40% Fill/Trade
For 25% Fill   Size Sealing
Fitting Needed
  1-1/2"  No.4  THHN (Col.B)  6   (9/2") 
103 132
/2”) 3 3 3 3 (4/ 5”) 5 5 (7/ 6”) 8 8
/2”) 3 3 (4/ 5”) 3 3 (5/ 5”) 6 6 (8/ 6”) 8 8
/2”) 3 3 (4/ 4”) 4 4 (5/ 5”) 6 6 (9/ 6”) 9 9
/2”) 4 4 (5/ 4”) 5 5 (7/ 5”) 8 8 (11/ 6”) 11 11
/2”) 5 5 (7/ 5”) 6 6 (9/ 5”) 10 10 (15/ 6”) 15 15
1
35 (57/ 4”) 32 47 (76/ 5”) 41 61 (98/ 6”) 64 96 93 139
/2”)
In our example, use an EYM / EYF200 for 2" size EYSF / ESUM, EYD, EYDM,
64 100 (160/ 4”) 86 134 110 172 173
76
(77/3-1/2”)
/2”)
/2”)
1
1
(164/ 3
(104/ 3
1
23
18 21 (35/ 4”) 24 29 (47/ 5”) 31 37 (60/ 6”) 49 (50/ 6”) 59 72 85
16 18 (29/ 4”) 21 (22/ 4”) 24 (39/ 5”) 28 31 (51/ 6”) 44 50 63 72
(24/ 3
/2”)
/2”)
1
1
(37/ 3
(22/ 3
11 (18/ 4”) 14 15 (25/ 5”) 18 20 (32/ 6”) 29 31 42 45
14 15 (25/ 4”) 1/9 20 (33/ 5”) 24 26 (43/ 6”) 38 42 55 61
(11/3-1/2”)
/2”) 10
/2”) 9 9 (15/ 4”) 12 13 (21/ 5”) 16 16 (27/ 6”) 25 26 37 38
1
/2”)
1
(19/ 3
1
/2”)
1
(16/ 3
1
1
1
1
1 1 1 1 1 1 1 1 3 3
1 1 1 1 1 1 2 2 4 4
1 1 1 1 1 1 3 3 4 4
22 37 (51/ 3”) 35 58 (79/ 4”) 47 78 (106/ 5”) 60 100 (136/ 5”) 94 157 137
/2”) 3 3 4/ 3”) 5 5 (7/ 4”) 6 6 (10/ 5”) 8 8 (12/ 5”) 13 13 19 19
/2”) 3 3 (4/ 3”) 4 4 (6/ 4”) 5 5 (8/ 5”) 7 7 (11/ 5”) 11 11 16 16
/2”)
1
(36/ 2
71 (114/ 3”) 50 102
/2”)
1
(35/ 2
16 (26/ 3”) 15 23
/2”)
1
/2”) 5 (8/ 3”) 7 7 (12/ 3
1
(11/ 2
9 16 (22/ 2”) 16 26
/2”) 3 3 (5/ 2”) 4 (5/ 2
/2”)
1
/2”) 1 2 (3/ 2”) 3 3 (6/ 3”) 5 5 (8/ 3”) 8 8 (13/ 4”) 11 11 (17/ 5”) 14 14 (22/ 5”) 22 22 32 32
1
1
/2”) 1 (2/ 3”) 2 (3/ 3”) 3 (4/3-1/2”) 3 (5/ 3
1
1
1
1 1 1 1 1 1 2 (3/ 3
1 1 1 1 1 1 (2/3-1/2”) 2 (3/ 3
(16/ 1
/2”) 7 (11/ 2”) 6 9 (15/ 2”) 10
18 43 (69/ 2”) 25 58 (94/ 2”) 41 96 (154/ 3”) 58 137 90 121 155
THE MAXIMUM NUMBER OF CONDUCTORS THAT CAN BE SEALED IN A SEALING FITING
13 20 (32/ 2”) 17 (18/ 2”) 27 (44/ 2”) 29 45 (73/ 3”) 41 65
15 32 (51/ 2”) 21 43 (70/ 2”) 34
/4”)
/4”)
1
1
(29/ 1
(39/ 1
/4”) 18
1
1
/4”) 7 11
/4”) 4 (5/ 1
/4”)
1
1
/4”) 3 4 (7/ 2”) 5 6 (9/ 2”) 8 9 (16/ 3”) 12 14
1
1
/4”) 3 3 (5/ 2”) 3 (4/ 2”) 4 (7/ 2”) 6 7 (11/ 3”) 9 10
1
(16/ 1
1 1 1 1 (2/ 1
1 1 1 1 1 1 (3/ 2
1 1 1 1 1 1 2 (3/ 3”) 3 3 (5/ 4”) 4 4 (6/ 4”) 6 6 (8/ 5”) 9 9 (13/ 6”) 13 13
1 1 1 1 1 1 (2/ 2
1 1 1 1 1 2 (3/ 2
1 1 1 1 1 1 (3/ 2") 3 3 (5/ 3”) 4 4 (7/ 3) 7 7 (11/ 4”) 9 9 (14/ 5”) 12 12 (18/ 5”) 19 19 27 27
1 1 1 1 1 (2/ 2”) 2 2 (4/ 3”) 3 (4/ 3”) 3 (6/ 3”) 6 6 (9/ 4”) 8 8 (12/ 5”) 10 10 (15/ 5”) 16 16 23 23
1 1 1 1 1 1 1 (2/ 3”) 3 3 (4/ 3
1 1 1 1 1 1 1 2 3 3 5 5
NOTE: For all other conductor sizes and types, wire fill is based on maximum 40% fill or 
less depending on conduit size and conductor type per the NEC Code.
• For all other conductor sizes and types, wire fill is based on maximum 25% fill or less.
1 1 1 1 1 1 1 1 3 3 4 4 6 6
1 1 1 1 1 1 1 2 3 3 4 4 7 7
1 1 1 1 1 1 2 2 3 3 5 5 7 7
1 1 1 1 1 1 (2/ 3
TABLE 1
• The maximum number of No. 4 Type THHN Conductors (Column B) in a 1-1/2" size sealing fitting is 6.                                                                                          
• The six (6) No. 4 THHN conductors represent the maximum wire fill of 25% or less for sealing fittings.                                                                                                    
nine (9) No. 4 conductors.
•  Increasing the sealing fitting to a 2" trade size will provide space for the 40% wire fill, or 
1/2” Seal 3/4” Seal 1” Seal 1-1/4” Seal 1-1/2” Seal 2” Seal 2-1/2” Seal 3” Seal 3-1/2” Seal 4” Seal 5” Seal 6” Seal
The Maximum number of wires that can be sealed in a fitting are as follows:
Size
1 1 1 1 (3/ 1
1 1 1 2 (3/1-1/4”) 3 3 (6/2”) 4 5 (5/ 2”) 7 8 (13/ 3”) 10 12
/4”) 6 15 (24/ 1”) 10 24
/4”) 5 11 (18/ 1”) 8 (9/ 1
/4”) 4 7 (11/ 1”) 7 11
3
3
(Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size) (Qty/NPT Size)
3 8 (13
6 9 10 16 17 27 30 47 41 64 68 106 98 151 150
7 11 12 20 20 33 35 58 49 80 80 131 115 187 176
A B A B A B A B A B A B A B A B A B A B A B A B
3 6 (10
/4”) 2 4 (5/ 1”) 4 6 (9/ 1
3
3
1 2 (3
1 1 1 1 (2/ 1”) 1 2 (4/ 1
1 1 1 2 (4/ 1”) 2 4 (6/ 1
1 1 1 1 2 (3/ 2”) 2 2 (4/ 2”) 4 4 (7/ 3”) 6 6 (10/ 3
1 1 1 1 1 2 (3/ 1
1 (2-3/4”) 4 (6
14
16
18
Kcmil
AWG or
12
8
10
4
6
2
3
1
1/0
2/0
3/0
4/0
300
250
600
400
350
500
900
800
750
700
1000
2000
1750
1500
1250
* COL. A = Wire Types: RFH-2, RH, RHH, THW, TH, XHHW (AWG 14-6).
COL. B = FEP, THHN, THWN, TFN, PF, PGFF, XHHW (AWG4-2000 MCM), FEPBV
(AWG 14-8).