Appleton SD Series Static Discharge Grounding Reelites™ Catalog Page

SD Series Static Discharge Grounding Reelites
CONTROLS: NEC/CEC HAZARDOUS INDICATORS AND GROUNDING DEVICES
NEC/CEC:
Rated for (Unclassied) Locations
Applications
• SD Static Discharge Reelites are used for grounding portable machines or equipment operating in hazardous atmospheres. These Reelites safely dissipate static electrical buildup and reduce the chance of a spark and resulting explosion.
• SD Series Reelites are spring-driven and carry various lengths of wire cable with grounding clamps. They are applied to: — Fuel-transfer trucks — Barges — Dock side loading facilities — Grain elevators — Hazardous maintenance areas
—Whereverammableliquidsorcombustibledustispresent
• Maximum Vdc resistance through Reelite and cable is approximately one ohm for each 15.2 meters (50 feet) of 2.38 mm (3/32”) steel aviation control cable. On Reelites carrying 14 gauge, stranded, rubber-covered, copper cable, maximum Vdc resistance is approximately 0.15 ohms per 15.2 meters (50 feet) of cable.
• SD11 Series — Lightweight, compact, enclosed, all-steel construction. — 15.2 meter (50 foot) single or Y-type cable lengths in 3/32”
galvanized steel aviation control cable with or without nylon
jacket. — 100 Amp universal jaw type grounding clamp. — Gravity type ratchet. — Mounts on ceiling, wall or with base down to a clean,
unpainted conductive surface to assure positive electrical
continuity through frame.
• SD50A thru SD100A Series — Lightweight and compact. Rugged open drum design with all
steel construction.
— Available with cable lengths from 15.2 meters (50 feet) to
30.5 meters (100 feet), single and Y-type construction.
Standard Materials
• SD11, SD50A thru SD100A: all steel construction
Standard Finishes
• SD11 series: red epoxy powder coat
• SD50A thru SD100A Series: yellow epoxy/polyester powder coat
Options
• An SDG grounding stud and SDP grounding plug, required by some state regulations, provides positive grounding and prevents accidental cable severing.
• Stainlesssteelcableisavailable,addsufx-SS
• Withoutratchet,addsufx-LR
SD11 Series
SD50A thru SD100A Series
SDG
Permanent grounding stud
for 2.38 mm (13/32”) hole. Thread 3/8 — 16 UNC-2B.
SDP
Positive grounding plug.
Without cord.
Note: An SDG grounding stud and SDP grounding plug, required by some state regulations, provides positive grounding and prevents accidental cable severing. See
next page for part numbers.
344
SD Series Static Discharge Grounding Reelites
CONTROLS: NEC/CEC HAZARDOUS INDICATORS AND GROUNDING DEVICES
NEC/CEC:
Rated for (Unclassied) Locations
Description Catalog Number
15.2 meters (50 feet) of 2.38 mm (3/32”) galvanized steel aviation control cable. 1 ohm D.C. resistance.
15.2 meters (50 feet) of 2.38 mm (3/32”) nylon covered galvanized steel aviation control cable. 1 ohm D.C. resistance.
15.2 meters (50 feet) total cable length consisting of 10.7 meters (35 feet) of 2.38 mm (3/32”) galvanized steel aviation control cable branching out to two 4.6 meters (15 feet) lengths with grounding clamps. 1 ohm D.C. resistance.
15.2 meters (50 feet) of 2.38 mm (3/32”) galvanized steel aviation control cable. 1 ohm D.C. resistance.
15.2 meters (50 feet) of 2.38 mm (3/32”) galvanized-steel cable with 1/64” nylon jacket. 1 ohm D.C. resistance.
30.5 meters (100 feet ) of 2.38 mm (3/32”) galvanized steel cable with 0.40 mm (1/64”) nylon jacket. 1.5 ohm D.C. resistance.
30.5 meters (100 feet ) of 2.38 mm (3/32”) galvanized steel aviation control cable. 2 ohms D.C. resistance.
22.9 meters (75 feet) total cable length consisting of 15.2 meters (50 feet) of 2.38 mm (3/32”) galvanized steel aviation control cable branching out to two 7.6 meters (25 feet) lengths with grounding clamps. 1.5 ohms D.C. resistance.
SD11
SD11N
SD11Y
SD50A
SD50AN
SD100AN
SD100A
SD75AY
30.5 meters (100 feet) total cable length consisting of 22.9 meters (75 feet) of 2.38 mm (3/32”) galvanized steel aviation control cable branching out to two 7.6 meters (25 feet) lengths with grounding clamps. 2.0 ohms D.C. resistance.
Permanent Grounding Stud for 2.38 mm (3/32”) hole. Thread 3/8-16 UNC-2B. SDG
Positive Grounding Plug. Without cord. #14 Type ”S” 0.265 max. SDP
SD100AY