Appleton Intraground™ N1 Series Nonmetallic Tumbler Switches Catalog Page

Intraground™ N1 Series Nonmetallic Tumbler Switches
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Explosionproof
Enclosures and Covers Have Neutral Color. Non-Factory Sealed.
NEC:
Class I, Division 1 and 2, Groups C, D NEMA 3, 4X, 7CD, 12
Applications
• Listed for use in Class I, Group C and D, Division 1 and 2 atmospheres such as: — Diethyl ether — Methyl ethyl keytone — Acetone — Toluene — No. 3 fuel oil — Ammonium hydroxide (20%) — Benzene — Regular unleaded gas — Ethyl acetate — Hexane and methanol
• Not suitable for: — Ethylene dichloride — Partially halogenated hydrocarbons.
• Sealing ttings must be eld installed adjacent to enclosure on
all conduit runs.
• Explosionproof. With sealing ttings installed at each conduit
entrance, the N1 Series enclosures withstood a hydrostatic test of four times the maximum internal explosion pressure that could be developed from a gas or vapor explosion in actual use.
Features
• Nonmetallic construction with metal imbedded grounding grid. No need to install special wires and parts for grounding. Feed­thru or dead-end grounded 1/2” or 3/4” conduit openings for threaded conduit.
• Special grounding wire furnished with each box provides safe grounding when cover is removed.
• Ideal for use in corrosive environments. Nonmetallic enclosures with corrosion resistant parts coated with epoxy, Teon®  or Mylar® , these switches offer unsurpassed resistance to a wide variety of corrosive chemicals.
• Unique labyrinth-path construction assures ame-tight joint
between body and cover.
• Silicone gasket, specially designed for the labyrinth-path joint, prevents entrance of moisture without interfering with the venting of cooled hazardous gases and vapors.
• Typical mechanical properties of 24,500 psi tensile strength,
3% elongation at break, 33,000 psi exural strength, and 1,200,000 psi exural modulus.
• Electrical properties of sample specimens: dielectric strength (in air) of 769 at 1/16”.
• High strength thermoplastic polyetherimide, together with thick walls (5/16”) and sound structural design (rounded corners) provides superior resistance to impact and crushing.
• Excellent resistance to ultraviolet light and water.
• Excellent conduit connection strength.
• Excellent resistance to attack by fungi and mold.
• Excellent heat deection temperature: sample specimens rated
at +210 °C (+410 °F).
• UL Temperature Index (continuous use temperature): +170 °C (+338 °F) electrical properties, +170 °C (+338 °F) mechanical properties with impact.
• Superior ammability resistance.
• Enclosures have external mounting lugs for ease of mounting.
• Smooth, rounded integral bushing in each hub protects conductor insulation.
• 20 Amp and 30 Amp units available for use with 120-277 Vac.
• Corrosion resistant, strong stainless steel Teon head cap screws attach cover and body for approved ame-
tight construction.
• Operating handle has close-tolerance threaded stainless steel shaft to meet explosionproof requirements. Provides positive corrosion resistant operation.
• Handle may be locked in ON or OFF position.
Standard Materials
• Body and cover: 30% glass-reinforced thermoplastic polyetherimide — neutral color
• Handle: nylon 6/6
• Cover bolts: stainless steel
• Nameplates: aluminum
Standard Finishes
• Cover bolts: Teon® 
• Nameplates: Mylar® 
NEC Certifications and Compliances
• UL Standards: UL 894, UL 1203
• UL Listed: E10523
Related Products
• For classied-location push button, pilot light and selector
switch control stations, see Non-Hazardous Control Stations Section.
• For sealing ttings, See Hazardous Location Fittings Section.
®
coated hex
Sealing fittings not furnished. Sealing fittings must be field-installed adjacent to enclosure on all conduit runs. See Hazardous Location Fittings Section. Teflon and Mylar are registered trademarks of E. I. du Pont de Nemours and Company.
122
Intraground™ N1 Series Nonmetallic Tumbler Switches
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Explosionproof
Enclosures and Covers Have Neutral Color. Non-Factory Sealed.
NEC:
Class I, Division 1 and 2, Groups C, D NEMA 3, 4X, 7CD, 12
Aluminum grounding grid, imbedded into the nonmetallic enclosure during molding, provides complete grounding system.
Switch
1-Gang Tumbler Switches
1-Pole 1/2 or 3/4 N1D75-F1 N1DC75-F1 N1D75-F13 N1DC75-F13
2-Pole 1/2 or 3/4 N1D75-F2 N1DC75-F2 N1D75-F23 N1DC75-F23
3-Way 1/2 or 3/4 N1D75-F3W N1DC75-F3W N1D75-F3W3 N1DC75-F3W3
4-Way 1/2 or 3/4 N1D75-F4W N1DC75-F4W
Switch
1-Gang Covers and Switches
All covers furnished with four bolts and blank nameplate.
1-Pole N1K-F12 EFSFR1Q N1K-F12 EFSFR13Q
2-Pole N1K-F12 EFSFR2Q N1K-F12 EFSFR23Q
3-Way N1K-F34W EFSFR3WQ N1K-F34W EFSFR3W3Q
4-Way N1K-F34W EFSFR4WQ
Cover Only Switch Only
1-Gang Nonmetallic Mounting Bodies
For use with covers above.
No field work. No extra grounding wires or parts required.
Hub Size
(Inches)
Hub Size
(Inches)
20 Ampere - 120-277 Vac 30 Ampere – 120-277 Vac
Dead-End Feed-Thru Dead-End Feed-Thru
20 Ampere - 120-277 Vac 30 Ampere – 120-277 Vac
Cover Switch Cover Switch
Catalog Number
Catalog Number
Catalog Number
Dead-End Feed-Thru
1/2 or 3/4 N1D75Q N1DC75Q
Sealing fittings must be field-installed adjacent to enclosure on all conduit runs. Furnished with a 3/4” to 1/2” NPT reducer. 20 Amp — 1 HP at 120 Vac and 2 HP at 240 Vac. 30 Amp — 2 HP at 120 Vac or 240 Vac.