Appleton Intraground™ N1 Series Control Stations Catalog Page

Page 1
Intraground™ N1 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Amp, 600 Vac Max. for Heavy Duty Use.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
• Listed for use in Class I, Division 1 and 2, Group C and D atmospheres such as:
— Diethyl ether — Methyl ethyl keytone — Acetone — Toluene — No. 3 fuel oil — Ammonium hydroxide (20%) — Benzene — Regular unleaded gas — Ethyl acetate — Hexane — Methanol
• Not suitable for: — Ethylene dichloride — Partially halogenated hydrocarbons
• Sealing ttings must be eld installed adjacent to enclosure on
all conduit runs.
• Explosionproof, with sealing ttings installed at each conduit
entrance, the N1 Series enclosures withstood a hydrostatic test of four times the maximum internal explosion pressure that could be developed from a gas or vapor explosion.
• Push buttons and selector switches are used in conjunction with contactors or magnetic starters for remote control of motors in hazardous locations. They provide circuit control and/ or selection.
• Pilot lights provide visual assurance that an electrical function is being performed at a remote or local hazardous location.
Features
• Nonmetallic construction with metal imbedded grounding grid. No need to install special wires and parts for grounding. Feed-thru or dead-end grounded 1/2” or 3/4” conduit openings for threaded conduit.
• Special grounding wire furnished with each box provides safe grounding when cover is removed.
• Ideal for use in corrosive environments. Nonmetallic enclosures
with corrosion resistant parts coated with epoxy, Teon®
®
Mylar chemicals.
• Unique labyrinth-path construction assures ame-tight joint
between body and cover.
• Silicone gasket, specially designed for the labyrinth-path joint, prevents entrance of moisture without interfering with the venting of cooled hazardous gases and vapors.
• Typical mechanical properties of 24,500 psi tensile strength,
3% elongation at break, 33,000 psi exural strength, and 1,200,000 psi exural modulus.
• Electrical properties of sample specimens: dielectric strength (in air) of 769 at 1/16”.
• High strength thermoplastic polyetherimide, together with thick walls (5/16”) and sound structural design (rounded corners) provides superior resistance to impact and crushing.
• Excellent resistance to ultraviolet light and water.
• Excellent conduit connection strength.
• Excellent resistance to attack by fungi and mold.
• Superior ammability resistance.
, these control stations offer unsurpassed resistance to
or
Push Button Pilot Light
Selector Switch Combination Push Button
and Pilot Light
Combination Selector Switch
and Pilot Light
Related Products
• Sealing tting must be installed at each conduit entrance
of the N1 enclosure to be explosionproof. See Hazardous Location Fittings Section.
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs. Teflon and Mylar are registered trademarks of E. I. du Pont de Nemours and Company.
107
Page 2
Intraground™ N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use.
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
• Listed for use in Class I, Division 2, Group B, C and D atmospheres such as:
— Diethyl ether — Methyl ethyl keytone — Acetone — Toluene — No. 3 fuel oil — Ammonium hydroxide (20%) — Benzene — Regular unleaded gas — Ethyl acetate — Hexane — Methanol.
• Listed for use in Class II, Division 1 and 2, Groups E, F and G.
• Dust-tight construction. After 32 hour UL test, no magnesium dust entered the enclosure.
• Push buttons and selector switches are used in conjunction with contactors or magnetic starters for remote control of motors in hazardous locations. They provide circuit control and/or selection.
• Pilot lights provide visual assurance that an electrical function is being performed at a remote or local hazardous location.
Features
• Factory sealed — no external seals required.
• Nonmetallic construction with metal imbedded grounding grid. No need to install special wires and parts for grounding. Feed­thru or dead-end grounded 1/2” or 3/4” conduit openings for threaded conduit.
• Special grounding wire furnished with each box provides safe grounding when cover is removed.
• Ideal for use in corrosive environments. Nonmetallic enclosures with corrosion resistant parts coated with epoxy, Teon®  or
®
Mylar chemicals.
• Silicone gasket, specially designed for the labryinth-path point between cover and body, prevents entrance of moisture and dust.
• Molded of high-tensile 30% glass reinforced thermoplastic polyethermide. Enclosure walls are 5/16” thick.
• Typical mechanical properties of 17,000 psi tensile strength,
3% elongation at break, 27,000 psi exural strength, and 1,100,000 psi exural modulus (UL tests showed 18,918 psi tensile strength and 30,675 psi exural strength).
• Electrical properties of sample specimens: dielectric strength of 490 at 1/8” and a comparative track index of 185V/0.058”.
• Superior impact resistance.
• Extremely low water absorption. This important quality assures dimensional stability.
• Excellent resistance to ultraviolet light and water.
• UL Temperature Index (continuous use temperature): +130 °C (+266 °F) electrical properties, +130 °C (+266 °F) mechanical properties with impact, and +140 °C (+284 °F) mechanical properties without impact.
• Superior ammability resistance.
• Excellent pull-out resistance.
, these control stations offer unsurpassed resistance to
Push Button Pilot Light
Selector Switch Combination Push Button
and Pilot Light
Combination Selector Switch
and Pilot Light
Teflon and Mylar are registered trademarks of E. I. du Pont de Nemours and Company.
108
Page 3
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
Features
• Heavy duty push button, 10 Amp 600 Vac rated.
• Dozens of possible combinations of push buttons, pilot lights and selector switches.
• Smooth, rounded integral bushing in each conduit opening protects conduct or insulation.
• Accurately tapped, tapered conduit openings for tight, rigid joints and ground continuity.
• Push Buttons, Selector Switches, and Pilot Lights — Stainless steel push button shaft operates within stainless
steel bushing, assuring long, maintenance-free operation.
— Push button and selector switch contacts are silver cadmium
oxide which are ”sealed” in lower phenolic chamber isolated from corrosive elements. Assures positive contact and long, trouble-free operation.
— Enclosed stainless steel helper spring prevents accidental
operation of push button in severe vibration installations.
— Corrosion resistant stainless steel Teon
cap screws hold covers to body.
— Push buttons are supplied with lockout type guards as
standard. Hole in guard will accept locks with up to 1/4” hasp. Permits locking of push button to prevent unauthorized operation.
— Clearly marked terminals with brass screws assure quick, easy
wiring.
— Pilot light supplied with jewel/guard assembly and 120 Vac,
6 Watt type 6S6 lamp, 120 Vac/Vdc, 50/60 Hz, 6 Watt.
®
coated hex head
Standard Materials
• Body and cover: 30% glass-reinforced thermoplastic polyetherimide
• SPBB push button: aluminum upper barrel and phenolic lower barrel with nylon plastic button. Glass reinforced polypropylene guard. Silicone weather boot. Aluminum nameplate
• SPLS pilot light: aluminum guard and body assembly; steel clamping ring; and tempered glass jewel
• SSBA selector switch: aluminum housing, nylon knobs and cams, and sealed phenolic contact block
• NBN rectangular button with weather boot: Nylon plastic button with neoprene weather boot. Aluminum nameplate
• NMRB mushroom button with weather boot: anodized aluminum buttons with neoprene weather boot
• Selector switch locking devices and push button securing rods: stainless steel
• Cover bolts: stainless steel
• Nameplates: copperfree (4/10 of 1% max.) aluminum
• Receptacles: copperfree (4/10 of 1% max.) aluminum
Standard Finishes
• Cover bolts: Teon® 
• Nameplates: Mylar® 
• Pilot light guard and clamping ring: epoxy
Options
• Three position selector switches with modied operation. For
description and switch diagram, refer to switch operators. — Momentary contact right position, spring return to center,
maintained contact left position. Add sufx –SRC.
— Momentary contact left position, spring return to center,
maintained contact right position. Add sufx –SLC.
• Alternate contacts add sufx –ALT .
• Selector switch Lockout: locks 2- or 3-position handle in any position. Sufx –LD.
• Push button front operated mushroom head (momentary contact):
— Red –NMRBRE — Green –NMRBGR — Black, add sufx –NMRBBL.
• Pilot light jewel/guard assembly. Order by sufxes if color
desired is other than red, as follows:
— Amber –JGBA — Blue –JGBB — Clear –JGBC — Green –JGBG
Opal –JGBO
For colored LED jewel/guard assembly, order by sufxes:
— Red –LEDR — Green –LEDG — Amber –LEDA
• Pilot light transformers for single pilot light per gang.
Order by sufx:
Primary Voltage Lamp Voltage Suffix
220 120 TR-2 277 120 TR-3 440 120 TR-4 550 120 TR-5
• Securing rod for push button lockout guard. Add sufx –SR.
NPBRKT nameplate mounting bracket to make circuit
description/identication easy.
— Pre-drilled holes in bottom of bracket allow direct mounting
to control stations with existing cover bolts.
— Pre-drilled holes in middle of bracket allow mounting of
customer’s circuit identication nameplate; epoxy glue may
also be used for mounting (phenolic nameplate not included).
— Bracket eliminates costly eld installation of drilling and
tapping to accommodate circuit identication nameplate.
— Brackets t side-by-side on 2-, 3- and 4-gang boxes and
3-devices.
NEC Certifications and Compliances
• UL Standards: UL 508, UL 698, UL 1203
• UL Listed: E10449, E81751
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs. Teflon and Mylar are registered trademarks of E. I. du Pont de Nemours and Company.
109
Page 4
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
Illustrated Features
Aluminum grounding grid, imbedded into the nonmetallic
enclosure during molding, provides complete grounding system.
No field work. No extra grounding wires or parts required.
SPBB Design Features
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
110
Page 5
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
Catalog Numbering Guide
N2D C 75 102 SRC SLNPFORQ
NEC Certified Backbox/Hub Arrangement:
N1D – Cover and Box N2D – Cover and Box N1K – Cover Only N2K – Cover Only
Hub Arrangement:
Blank - Dead-End or Cover
Only
C - Feed-Thru
Full Catalog # N2DC75-102-SRC-SLNPFORQ
Feed-Thru N2D Box with 3/4” Hubs: With A 2-Circuit, 3 Position Spring Return from the Right Selector Switch and ”Forward-Off-Reverse” Nameplate
Options
Options Description Suffix
Momentary Push Button Securing Rod SR
Selector Switch Lockout LD
Spring Return From Right Selector Switch (3 Positions Only) SRC
Spring Return From Left Selector Switch (3 Positions Only) SLC
Alternate Contacts Selector Switch ALT
Change One Red Lens to Green Lens JGBG
Change One Red Lens to Opal Lens JGBO
Change One Red Lens to Amber Lens JGBA
Change One Red Lens to Blue Lens JGBB
Change One Red Lens to Clear Lens JGBC
Add 220/120 Vac Transformer (J1 Device Only) TR2
Add 277/120 Vac Transformer (J1 Device Only) TR3
Add 440/120 Vac Transformer (J1 Device Only) TR4
Add 550/120 Vac Transformer (J1 Device Only) TR5
Change One Red Pilot to Red LED LEDR
Change One Red Lens to Green LED LEDG
Change One Red Lens to Amber LED LEDA
Add Red Mushroom Head to Momentary Push Button NMRBRE
Add Black Mushroom Head to Momentary Push Button NMRBBL
Add Green Mushroom Head to Momentary Push Button NMRBGR
Locking Guard for Maintained Push Button SMPBLG
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
Hub Size: 75 - 3/4” Blank - Cover Only
Device:
See Devices
Options:
See Options
Special Nameplates:
See Accessories
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
111
Page 6
Intraground™ N1 and N2 Series Control Stations Devices
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
Devices
Device Description Suffix
One Pilot Light (Red Standard) J1 Two Pilot Lights J2 One Pilot Light and One Momentary Push Button J1U1 One Pilot Light and Two Momentary Push Buttons J1U2 One Pilot Light and One Maintained Push Button J1UM1 One Pilot Light and One Dust-Cap Push Button J1DU1 One Pilot Light and One 12 Selector Switch (2 Position, 2 Circuit) J112 One Pilot Light and One 35 Selector Switch (2 Position, 4 Circuit ) J135 One Pilot Light and One 102 Selector Switch (3 Position, 2 Circuit) J1102 One Pilot Light and One 345 Selector Switch (3 Position, 4 Circuit) J1345 One Monetary Push Button U1 Two Monetary Push Buttons U2 Two Side-By-Side Momentary Push Buttons U2DBL Three Monetary Push Buttons U3 One Momentary Push Button and One Maintained Push Button U1UM1 One Momentary Push Button and One Dust-Cap Push Button U1DU1 One Momentary Push Button and One 12 Selector Switch (2 Position, 2 Circuit) U112 One Momentary Push Button and One 35 Selector Switch (2 Position, 4 Circuit ) U135 One Momentary Push Button and One 102 Selector Switch (3 Position, 2 Circuit) U1102 One Momentary Push Button and One 345 Selector Switch (3 Position, 4 Circuit) U1345 One Maintained Push Button (Mushroom Head - Red) UM1 Two Maintained Push Button UM2 One Maintained and One Dust-Cap Push Button UM1DU1 One Maintained Push Button and One 12 Selector Switch (2 Position, 2 Circuit) UM112 One Maintained Push Button and One 35 Selector Switch (2 Position, 4 Circuit ) UM135 One Maintained Push Button and One 102 Selector Switch (3 Position, 2 Circuit) UM1102 One Maintained Push Button and One 345 Selector Switch (3 Position, 4 Circuit) UM1345 One Dust Cap Push Button DU1 Two Dust Cap Push Buttons DU2 One Dust Cap and One 12 Selector Switch (2 Position, 2 Circuit) DU112 One Dust Cap and One 35 Selector Switch (2 Position, 4 Circuit ) DU135 One Dust Cap and One 102 Selector Switch (3 Position, 2 Circuit) DU1102 One Dust Cap and One 345 Selector Switch (3 Position, 4 Circuit) DU1345 One 12 Selector Switch (2 Position, 2 Circuit) 12 One 35 Selector Switch (2 Position, 4 Circuit ) 35 One 102 Selector Switch (3 Position, 2 Circuit) 102 One 345 Selector Switch (3 Position, 4 Circuit) 345
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
112
Page 7
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC — N1 Series (Non-Factory Sealed) :
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
Nameplates
Description Suffix
Mushroom Head Push Buttons (Maintained and Momentary)
Start MNPSTQ
Stop MNPSPQ
Emergency Stop MNPESTPQ
Blank MNPBQ
Pilot Light Nameplates
Blank LNPBQ
Forward LNPFWDQ
Jog LNPJOGQ
Run LNPRUNQ
Stop LNPSPQ
Start LNPSTQ
Down LNPDOWNQ
Fast LNPFASTQ
Slow LNPSLOWQ
Raise LNPRAISEQ
Lower LNPLOWERQ
Reset LNPRESETQ
Off LNPOFFQ
On LNPONQ
Reverse LNPREVQ
Close LNPCLOSEQ
Open LNPOPENQ
Up LNPUPQ
Test LNPTESTQ
Low LNPLOWQ
High LNPHIGHQ
Two Position Selection Switch Nameplates
Forward—Reverse SLNPFRQ
Hand—Auto
On—Off SLNPOO
Start—Stop SLNPSS
Blank SLNPBQ
Up—Down SLNPUDQ
Run—Jog SLNPRJQ
Auto—Hand SLNPAHQ
Off—Remote SLNPORQ
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
SLNPHAQ
Description Suffix
Three Position Selection Switch Nameplates
Forward—Off—Reverse SLNPFORQ
Hand—Off—Auto
Run—Off—Jog SLNPROJQ
Blank SLNPB3
Reverse—Off—Forward SLNPROFQ
Auto—Off—Hand SLNPAOHQ
Hand—Off—Remote SLNPHORQ
1—Off—2 SLNP102Q
Jog—Off—Run SLNPJORQ
Stop—Run—Start SLNPSRSQ
Local—Off—Remote SLNPLORQ
Momentary Push Buttons
For Rectangular Weatherboot Style Only (Not for round weatherboot style)
Blank
Forward SNPFWDQ
Jog SNPJOGQ
Run SNPRUNQ
Stop
Start
Down SNPDOWNQ
Fast SNPFASTQ
Slow SNPSLOWQ
Raise SNPRAISEQ
Lower SNPLOWERQ
Reset SNPRESETQ
Off SNPOFFQ
On SNPONQ
Reverse SNPREVQ
Close SNPCLOSEQ
Open SNPOPENQ
Up SNPUPQ
Test SNPTESTQ
Low SNPLOWQ
High SNPHIGHQ
SLNPHOAQ
SNPBQ
SNPSPQ
SNPSTQ
Custom nameplates are not available. Included as standard (no need to use suffix). For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
113
Page 8
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Push Button and Push Button/Pilot Light. Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
1-Gang Push Buttons — Momentary Contact
1 Circuit 2 Circuit
1-Gang Push Buttons — Maintained Contact Red Mushroom Head — Emergency Stop Nameplate
3-Device Push Buttons — Momentary Contact
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
Hub Size
(Inches) Description Diagram
Dead-End
1/2 or 3/4 1 Circuit Universal
1/2 or 3/4 2 Circuits Universal
Feed-Thru
1/2 or 3/4 1 Circuit Universal
1/2 or 3/4 2 Circuits Universal
Dead-End
1/2 or 3/4 1 Circuit Universal
Feed-Thru
1/2 or 3/4 1 Circuit Universal
Dead-End
1/2 or 3/4 3 Circuits Universal
Nameplate
Marking
Start/Stop N1D75-U1 N2D75-U1
Start/Stop N1D75-U2 N2D75-U2
Start/Stop N1DC75-U1 N2DC75-U1
Start/Stop N1DC75-U2 N2DC75-U2
Emergency Stop N1D75-UM1 N2D75-UM1
Emergency Stop N1DC75-UM1 N2DC75-UM1
Start/Stop N1D75-U3 N2D75-U3
Catalog Number
N1 Series N2 Series
Feed-Thru
1/2 or 3/4 3 Circuit Universal
1-Gang Push Button/Pilot Light — Momentary Contact
Dead-End
1/2 or 3/4
1/2 or 3/4
Feed-Thru
1/2 or 3/4
1 Circuit
1 Pilot Light
1-Gang Pilot Lights
1 Pilot Light 2 Pilot Lights
2 Circuit
1 Pilot Lights
1/2 or 3/4
Dead-End
1/2 or 3/4 1 Pilot Light
1/2 or 3/4 2 Pilot Lights
Feed-Thru
1/2 or 3/4 1 Pilot Light
1/2 or 3/4 2 Pilot Lights
1 Circuit Universal
and 1 Pilot Light
2 Circuits Universal
and 1 Pilot Light
1 Circuit Universal
and 1 Pilot Light
2 Circuits Universal
and 1 Pilot Light
Start/Stop N1DC75-U3 N2DC75-U3
Specify N1D75-J1U1 N2D75-J1U1
Specify N1D75-J1U2 N2D75-J1U2
Specify N1DC75-J1U1 N2DC75-J1U1
Specify N1DC75-J1U2 N2DC75-J1U2
Specify N1D75-J1 N2D75-J1
Specify N1D75-J2 N2D75-J2
Specify N1DC75-J1 N2DC75-J1
Specify N1DC75-J2 N2DC75-J2
Furnished with 3/4” to 1/2” NPT reducer. For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
114
Page 9
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Selector Switch Control Stations and Fire Alarm Station. Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
Pilot Light and Selector Switch
Selector Switch
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
Pilot
Hub Size (Inches)
Dead-End
1/2 or 3/4 — Pilot Light and
2-Pos., 2-Cir. Selector Switch
1/2 or 3/4 — Pilot Light and
2-Pos., 4-Cir. Selector Switch
Note: Standard legend plate reads Hand/Auto
1/2 or 3/4 — Pilot Light and
3-Pos., 2-Cir. Selector Switch
1/2 or 3/4 — Pilot Light and
3-Pos., 4-Cir. Selector Switch
Note: Standard legend plate reads Hand/Off/Auto
Feed-Thru
1/2 or 3/4 — Pilot Light and
2-Pos., 2-Cir. Selector Switch
1/2 or 3/4 — Pilot Light and
2-Pos., 4-Cir. Selector Switch
Note: Standard legend plate reads Hand/Auto
1/2 or 3/4 — Pilot Light and
3Pos., 2-Cir. Selector Switch
1/2 or 3/4 — Pilot Light and
3-Pos., 4-Cir. Selector Switch
Note: Standard legend plate reads Hand/Off/Auto
Light
Diagram
Switch Diagram Catalog Number
Left Center Right
None
None
None
None
With
Pilot Light
N1D75-J112 N1D75-12
N2D75-J112 N2D75-12
N1D75-J135 N1D75-35
N2D75-J135 N2D75-35
N1D75-J1102 N1D75-102
N2D75-J1102 N2D75-102
N1D75-J1345 N1D75-345
N2D75-J1345 N2D75-345
N1DC75-J112 N1DC75-12
N2DC75-J112 N2DC75-12
N1DC75-J135 N1DC75-35
N2DC75-J135 N2DC75-35
N1DC75-J1102 N1DC75-102
N2DC75-J1102 N2DC75-102
N1DC75-J1345 N1DC75-345
N2DC75-J1345 N2DC75-345
With Out
Pilot Light
Fire Alarm Station, Factory Sealed — Universal Contacts, with hammer on chain
Catalog Number
Hub Size
(Inches) Description
Dead-End
1/2 or 3/4 Universal 2 Position, 1 Circuit
Feed-Thru
1/2 or 3/4 Universal 2 Position, 1 Circuit
Replacement Glass
(For N1 or N2) NFA-G
Furnished with a 3/4” to 1/2” NPT reducer. For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs. Do not use in atmospheres containing
electrically conductive dusts (most coal dusts are not electrically conductive).
N1 Series
(Neutral Color)
N1D75FA-U1 N2D75FA-U1
N1DC75FA-U1 N2DC75FA-U1
N2 Series
(Red Color)
115
Page 10
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Selector Switch Operators and Cover Assemblies. Nonmetallic
For use with N1 and N2 Series Bodies Only. 10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
2 Circuit (2 or 3 Position) Momentary contact right position. Spring return to center. Maintained contact left position.
4 Circuit (2 or 3 Position)
Nameplates
Two Position
Three Position
Selector Switch Locking Devices
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
Thread Size
(Inches,
NPSM) Description
Maintained Contact
2 Position, 2
1/2
1/2
Note: Standard legend plate reads Hand/Auto
1/2
1/2
Note: Standard legend plate reads Hand/Off/Auto
Modified Operations
1/2
1/2
Note: Standard legend plate reads Hand/Off/Auto
1/2
1/2
Note: Standard legend plate reads Auto/Off/Hand
1/2
Note: Standard legend plate reads Stop/Run/Start
Forward—Reverse SLNP-FRQ Forward—Off—Reverse SLNP-FORQ Hand—Auto
On—Off SLNP-OO Run—Off—Jog SLNP-ROJQ
Start—Stop SLNP-SS Blank SLNP-B3
Blank SLNP-BQ Reverse—Off—Forward SLNP-ROFQ
Up—Down SLNP-UDQ Auto—Off—Hand SLNP-AOHQ
Run—Jog SLNP-RJQ Hand—Off—Remote SLNP-HORQ
Auto—Hand SLNP-AHQ 1—Off—2 SLNP-1O2Q
Off—Remote SLNP-ORQ Jog—Off—Start SLNP-JORQ
Circuit
2 Position, 4
Circuit
3 Position, 2
Circuit
3 Position, 4
Circuit
3 Position, 2
Circuit
3 Position, 4
Circuit
Momentary contact left position. Spring return to center. Maintained contact right position.
3 Position, 2
Circuit
3 Position, 4
Circuit
Momentary contact right position. Spring return to center. Maintained contact left position.
3 Position, 4
Circuit
Two Position Nameplates Three Position Nameplates
Two or Three Positions — Permit locking in any position. SBL-3-Q
Left Center Right N1 Switch N2 Switch
Diagram
SLNP-HAQ
N1/N2 Switch
Assembly Only
SSBA1-2Q N1K-12 N2K-12
SSBA2-2Q N1K-35 N2K-35
SSBA1-3Q N1K-102 N2K-102
SSBA2-3Q N1K-345 N2K-345
SSBAS-1-3 N1K-102SRC N2K-102SRC
SSBAS-2-3 N1K-345SRC N2K-345SRC
SSBASL-1-3 N1K-102SLC N2K-102SLC
SSBASL-2-3 N1K-345SLC N2K-345SLC
SSBASRA-2-3 N1K-637SRC N2K-637SRC
Hand—Off—Auto
Stop—Run—Start SLNP-SRSQ Local—Off—Remote SLNP-LORQ
Assembly with Cover
SLNP-HOAQ
Supplied as standard with Maintained Contact Selector Switches. For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
116
Page 11
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic.
For use with N1 and N2 Series Bodies Only. All Covers Supplied with Four Bolts and Blank Nameplate. N1 Series– Neutral Color; N2 Series– Blue Color.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
Covers Only — for Use with Nonmetallic Mounting Bodies Below
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
Description
Pilot Light or Push Button Covers
3/4” tapped openings
One opening: one pilot light or one push button
Two openings: two pilot lights; two push buttons — one pilot light and one push button
Push Button or Selector Switch Covers
1/2” tapped openings
Two openings: selector switch or two push buttons N1K-2SP N2K-2SP
Push Button, Pilot light or Selector Switch Covers
One 3/4” top and two 1/2” bottom tapped openings
One top and two bottom openings — one pilot light, two push buttons; one pilot light, one selector switch; or three push buttons
Catalog Number
N1 Series N2 Series
N1K-1PL N2K-1PL
N1K-2PL N2K-2PL
N1K-3JPB N2K-3JPB
1-Gang Nonmetallic Mounting Bodies — for use with Covers Above
Description Hub Size (Inches)
Dead-End 1/2 or 3/4 N1D75Q N2D75Q
Feed-Thru 1/2 or 3/4 N1DC75Q N2DC75Q
Nameplate Mounting Bracket
Description Catalog Number
Bracket for N1, N2 Series NPBRKT-N1N2
To order bracket with control station, add suffix –NPBRKT to end of catalog number.
Note: Secure mount bracket using cover nameplate screws.
Furnished with 3/4” to 1/2” NPSM reducer. Furnished with a 3/4” to 1/2” NPT reducer. For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
Catalog Number
N1 Series N2 Series
117
Page 12
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC:
Class I, Division 1 and 2, Groups B,C, D Class II, Division 1 and 2, Groups E, F, G Class III
Description Diagram Catalog Number
Push Button — Factory Sealed — Momentary Contact
10 Amp 600 Vac Heavy Duty 1/2” thread size (NPSM). Furnished with 1/2” to 3/4” enlarger, Weather Boot, Guard, Start, Stop and Blank Nameplates.
SPBB-U1-Q
SPBB-U2DBL
Push Button — Red Mushroom Head — Factory Sealed — Maintained Contact
Rectangular Button with Weather Boot
Nameplates for Rectangular Push Buttons
SNP-OFF-Q
SNP-ON-Q
Single Push Button Universal SPBB-U1-Q
Double Push Button Universal
10 Amp 600 Vac Heavy Duty 1/2” thread size (NPSM). Furnished with 1/2” to 3/4” enlarger and Emergency Stop Nameplate (guard not furnished).
Single Push Button Universal SMPB-U1-Q
Furnished with Start, Stop and Blank Nameplates NBN-WB
Blank SNP-B-Q Off SNP-OFF-Q
Forward SNP-FWD-Q On SNP-ON-Q
Jog SNP-JOG-Q Reverse SNP-REV-Q
Run SNP-RUN-Q Open SNP-OPEN-Q
Stop SNP-SP-Q Close SNP-CLOSE-Q
Start SNP-ST-Q Up SNP-UP-Q
Down SNP-DOWN-Q Test SNP-TEST-Q
Fast SNP-FAST-Q Low SNP-LOW-Q
Slow SNP-SLOW-Q High SNP-HIGH-Q
Raise SNP-RAISE-Q
Lower SNP-LOWER-Q
Reset SNP-RESET-Q
SPBB-U2DBL
Push Button Replacement Locking Guards — Glass Reinforced Polypropylene — Gasketed
Maintained Mushroom Head
Single Guard
Suitable for Class I, Group B when installed in an enclosure rated for Class I, Group B.
Switch Guard
Double Guard
Has hole for 1/4” hasp.
Single Guard (Maintained Switch) SMPB-LG
Single Guard NPB-LG1
Double Guard NPB-LG2
Single Guard (No Lockout Holes) NPB-LG1-LL
Double Guard (No Lockout Holes) NPB-LG2-LL
118
Page 13
Intraground™ N1 and N2 Series Control Station
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC:
Class I, Division 1 and 2, Groups B,C, D Class II, Division 1 and 2, Groups E, F, G Class III
Push Button Accessories and Parts
Description Catalog Number
Push Button Securing Rod with Chain — Stainless Steel
For use with Single Guard Only NBL-SR
Mushroom Head Button with Weather Boot for Use with Momentary Contact — Gasketed
Black NMRB-BL
Green NMRB-GR
Red NMRB-RE
Mushroom Head Push Button
For Use with Mushroom Head Push Button — Maintained Contact — Solid-Colored Nonmetallic
Red NMRBM-RE
MNPESTPQ
Pilot Light, Factory Sealed
Pilot Light Chamber Only
Nameplates — Mushroom Head Push Button For Momentary and Maintained
Start MNPSTQ
Stop MNPSPQ
Emergency Stop MNPESTPQ
Blank MNPBQ
Incandescent
Furnished with 6S6 120 Vac incandescent lamp, jewel and guard. Has 457 mm (18”) long, type SFF-2 pigtail leads; +150 °C (+302 °F). Body has 3/4” straight thread (NPSM).
With Red Jewel SPLSREB
With Green Jewel SPLSGRB
With Amber Jewel SPLSAMB
With Blue Jewel SPLSBLB
With Clear Jewel SPLSCLB
With Opal Jewel SPLSOPB
LED
Furnished with candelabra base 120 Vac LED, jewel and guard. Has 457 mm (18”) long, type SFF-2 pigtail leads; +150 °C (+302 °F). Body has 3/4” straight thread (NPSM).
With Red LED, Clear Jewel SPLNSREB
With Green LED, Clear Jewel SPLNSGRB
With Amber LED, Clear Jewel SPLNSAMB
Chamber Only
(Same as above, less jewel, guard and lamp) SPLSSCB
Suitable for Class I, Group B when installed in an enclosure rated for Class I, Group B.
119
Page 14
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC:
Class I, Division 1 and 2, Groups B,C, D Class II, Division 1 and 2, Groups E, F, G Class III
Push Button Accessories and Parts
Description Catalog Number
Pilot Light Jewel/Guard Assembly
The below catalog numbers indicate an assembly of the Pilot Light Jewels and Guards. Jewels and Guards are not available as separate items.
Amber Jewel/Guard JGBNA
Blue Jewel/Guard JGBNB
Clear Jewel/Guard JGBNC
Green Jewel/Guard JGBNG
Opal Jewel/Guard JGBNO
Red Jewel/Guard JGBNR
Replacement Bulbs
Clear Bulbs
Furnished with candelabra base. 6 Watt, 120 Vac, Type 6S6 EPL-B6W
LED Replacements
Furnished with candelabra base. 120 Vac, 10 mA.
Red LED EPLLEDR
Green LED EPLLEDG
EPL-B6W EPLLEDR
Amber LED EPLLEDA
Transformer
Nameplates for Pilot Light
LNPRUNQ
Add Suffix as listed below. Transformer clamps directly to pilot light barrel.
Only one pilot light transformer assembly per one gang body.
Primary Vac Lamp Vac Suffix
220 120 TR2
277 120 TR3
440 120 TR4
550 120 TR5
Description Catalog Number Description Catalog Number
Blank LNPBQ Reset LNPRESETQ
Forward LNPFWDQ Off LNPOFFQ
Jog LNPJOGQ On LNPONQ
Run LNPRUNQ Reverse LNPREVQ
Stop LNPSPQ Close LNPCLOSEQ
Start LNPSTQ Open LNPOPENQ
Down LNPDOWNQ Up LNPUPQ
Fast LNPFASTQ Test LNPTESTQ
Slow LNPSLOWQ Low LNPLOWQ
Raise LNPRAISEQ High LNPHIGHQ
Lower LNPLOWERQ
Suitable for Class I, Group B when installed in an enclosure rated for Class I, Group B.
120
Page 15
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
© June 2017
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D NEMA 3R, 4X, 7CD, 12
Dimensions in Millimeters (Inches)
Push Button/Pilot Light
Selector Switch
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 3R, 4X, 9EFG, 12
NPBRKT Nameplate Mounting Bracket
Secure bracket using
cover nameplate
screws.
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
121