• Sealing ttings must be eld installed adjacent to enclosure on
all conduit runs.
• Explosionproof, with sealing ttings installed at each conduit
entrance, the N1 Series enclosures withstood a hydrostatic
test of four times the maximum internal explosion pressure that
could be developed from a gas or vapor explosion.
• Push buttons and selector switches are used in conjunction
with contactors or magnetic starters for remote control of
motors in hazardous locations. They provide circuit control and/
or selection.
• Pilot lights provide visual assurance that an electrical function is
being performed at a remote or local hazardous location.
Features
• Nonmetallic construction with metal imbedded grounding grid.
No need to install special wires and parts for grounding.
Feed-thru or dead-end grounded 1/2” or 3/4” conduit openings
for threaded conduit.
• Special grounding wire furnished with each box provides safe
grounding when cover is removed.
• Ideal for use in corrosive environments. Nonmetallic enclosures
with corrosion resistant parts coated with epoxy, Teon®
®
Mylar
chemicals.
• Unique labyrinth-path construction assures ame-tight joint
between body and cover.
• Silicone gasket, specially designed for the labyrinth-path joint,
prevents entrance of moisture without interfering with the
venting of cooled hazardous gases and vapors.
• Typical mechanical properties of 24,500 psi tensile strength,
3% elongation at break, 33,000 psi exural strength, and
1,200,000 psi exural modulus.
• Electrical properties of sample specimens: dielectric strength
(in air) of 769 at 1/16”.
• High strength thermoplastic polyetherimide, together with thick
walls (5/16”) and sound structural design (rounded corners)
provides superior resistance to impact and crushing.
• Excellent resistance to ultraviolet light and water.
• Excellent conduit connection strength.
• Excellent resistance to attack by fungi and mold.
• Superior ammability resistance.
, these control stations offer unsurpassed resistance to
or
Push ButtonPilot Light
Selector SwitchCombination Push Button
and Pilot Light
Combination Selector Switch
and Pilot Light
Related Products
• Sealing tting must be installed at each conduit entrance
of the N1 enclosure to be explosionproof. See Hazardous
Location Fittings Section.
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
Teflon and Mylar are registered trademarks of E. I. du Pont de Nemours and Company.
107
Page 2
Intraground™ N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
• Listed for use in Class II, Division 1 and 2, Groups E, F and G.
• Dust-tight construction. After 32 hour UL test, no magnesium
dust entered the enclosure.
• Push buttons and selector switches are used in conjunction
with contactors or magnetic starters for remote control of
motors in hazardous locations. They provide circuit control
and/or selection.
• Pilot lights provide visual assurance that an electrical function
is being performed at a remote or local hazardous location.
Features
• Factory sealed — no external seals required.
• Nonmetallic construction with metal imbedded grounding grid.
No need to install special wires and parts for grounding. Feedthru or dead-end grounded 1/2” or 3/4” conduit openings for
threaded conduit.
• Special grounding wire furnished with each box provides safe
grounding when cover is removed.
• Ideal for use in corrosive environments. Nonmetallic enclosures
with corrosion resistant parts coated with epoxy, Teon® or
®
Mylar
chemicals.
• Silicone gasket, specially designed for the labryinth-path point
between cover and body, prevents entrance of moisture and dust.
• Molded of high-tensile 30% glass reinforced thermoplastic
polyethermide. Enclosure walls are 5/16” thick.
• Typical mechanical properties of 17,000 psi tensile strength,
3% elongation at break, 27,000 psi exural strength, and
1,100,000 psi exural modulus (UL tests showed 18,918 psi
tensile strength and 30,675 psi exural strength).
• Electrical properties of sample specimens: dielectric strength of
490 at 1/8” and a comparative track index of 185V/0.058”.
• Superior impact resistance.
• Extremely low water absorption. This important quality assures
dimensional stability.
• Excellent resistance to ultraviolet light and water.
• UL Temperature Index (continuous use temperature): +130 °C
(+266 °F) electrical properties, +130 °C (+266 °F) mechanical
properties with impact, and +140 °C (+284 °F) mechanical
properties without impact.
• Superior ammability resistance.
• Excellent pull-out resistance.
, these control stations offer unsurpassed resistance to
Push ButtonPilot Light
Selector SwitchCombination Push Button
and Pilot Light
Combination Selector Switch
and Pilot Light
Teflon and Mylar are registered trademarks of E. I. du Pont de Nemours and Company.
108
Page 3
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
• Nameplates: copperfree (4/10 of 1% max.) aluminum
• Receptacles: copperfree (4/10 of 1% max.) aluminum
Standard Finishes
• Cover bolts: Teon®
• Nameplates: Mylar®
• Pilot light guard and clamping ring: epoxy
Options
• Three position selector switches with modied operation. For
description and switch diagram, refer to switch operators.
— Momentary contact right position, spring return to center,
maintained contact left position. Add sufx –SRC.
— Momentary contact left position, spring return to center,
maintained contact right position. Add sufx –SLC.
• Alternate contacts add sufx –ALT .
• Selector switch Lockout: locks 2- or 3-position handle in any
position. Sufx –LD.
• Push button front operated mushroom head (momentary
contact):
— Red –NMRBRE
— Green –NMRBGR
— Black, add sufx –NMRBBL.
• Pilot light jewel/guard assembly. Order by sufxes if color
desired is other than red, as follows:
— Amber –JGBA
— Blue –JGBB
— Clear –JGBC
— Green –JGBG
— Opal –JGBO
• For colored LED jewel/guard assembly, order by sufxes:
— Red –LEDR
— Green –LEDG
— Amber –LEDA
• Pilot light transformers for single pilot light per gang.
Order by sufx:
Primary VoltageLamp VoltageSuffix
220120TR-2
277120TR-3
440120TR-4
550120TR-5
• Securing rod for push button lockout guard. Add sufx –SR.
• NPBRKT nameplate mounting bracket to make circuit
description/identication easy.
— Pre-drilled holes in bottom of bracket allow direct mounting
to control stations with existing cover bolts.
— Pre-drilled holes in middle of bracket allow mounting of
customer’s circuit identication nameplate; epoxy glue may
also be used for mounting (phenolic nameplate not included).
— Bracket eliminates costly eld installation of drilling and
tapping to accommodate circuit identication nameplate.
— Brackets t side-by-side on 2-, 3- and 4-gang boxes and
3-devices.
NEC Certifications and Compliances
• UL Standards: UL 508, UL 698, UL 1203
• UL Listed: E10449, E81751
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
Teflon and Mylar are registered trademarks of E. I. du Pont de Nemours and Company.
109
Page 4
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
Class I, Division 1 and 2, Groups C, D
NEMA 3R, 4X, 7CD, 12
Devices
Device DescriptionSuffix
One Pilot Light (Red Standard)J1
Two Pilot LightsJ2
One Pilot Light and One Momentary Push ButtonJ1U1
One Pilot Light and Two Momentary Push ButtonsJ1U2
One Pilot Light and One Maintained Push ButtonJ1UM1
One Pilot Light and One Dust-Cap Push ButtonJ1DU1
One Pilot Light and One 12 Selector Switch (2 Position, 2 Circuit)J112
One Pilot Light and One 35 Selector Switch (2 Position, 4 Circuit )J135
One Pilot Light and One 102 Selector Switch (3 Position, 2 Circuit)J1102
One Pilot Light and One 345 Selector Switch (3 Position, 4 Circuit)J1345
One Monetary Push Button U1
Two Monetary Push Buttons U2
Two Side-By-Side Momentary Push ButtonsU2DBL
Three Monetary Push Buttons U3
One Momentary Push Button and One Maintained Push ButtonU1UM1
One Momentary Push Button and One Dust-Cap Push ButtonU1DU1
One Momentary Push Button and One 12 Selector Switch (2 Position, 2 Circuit)U112
One Momentary Push Button and One 35 Selector Switch (2 Position, 4 Circuit )U135
One Momentary Push Button and One 102 Selector Switch (3 Position, 2 Circuit)U1102
One Momentary Push Button and One 345 Selector Switch (3 Position, 4 Circuit)U1345
One Maintained Push Button (Mushroom Head - Red)UM1
Two Maintained Push ButtonUM2
One Maintained and One Dust-Cap Push ButtonUM1DU1
One Maintained Push Button and One 12 Selector Switch (2 Position, 2 Circuit)UM112
One Maintained Push Button and One 35 Selector Switch (2 Position, 4 Circuit )UM135
One Maintained Push Button and One 102 Selector Switch (3 Position, 2 Circuit)UM1102
One Maintained Push Button and One 345 Selector Switch (3 Position, 4 Circuit)UM1345
One Dust Cap Push ButtonDU1
Two Dust Cap Push Buttons DU2
One Dust Cap and One 12 Selector Switch (2 Position, 2 Circuit)DU112
One Dust Cap and One 35 Selector Switch (2 Position, 4 Circuit )DU135
One Dust Cap and One 102 Selector Switch (3 Position, 2 Circuit)DU1102
One Dust Cap and One 345 Selector Switch (3 Position, 4 Circuit)DU1345
One 12 Selector Switch (2 Position, 2 Circuit)12
One 35 Selector Switch (2 Position, 4 Circuit )35
One 102 Selector Switch (3 Position, 2 Circuit)102
One 345 Selector Switch (3 Position, 4 Circuit)345
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3R, 4X, 9EFG, 12
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
112
Page 7
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC — N1 Series (Non-Factory Sealed) :
Class I, Division 1 and 2, Groups C, D
NEMA 3R, 4X, 7CD, 12
Nameplates
DescriptionSuffix
Mushroom Head Push Buttons (Maintained and Momentary)
StartMNPSTQ
StopMNPSPQ
Emergency StopMNPESTPQ
BlankMNPBQ
Pilot Light Nameplates
BlankLNPBQ
ForwardLNPFWDQ
JogLNPJOGQ
RunLNPRUNQ
StopLNPSPQ
StartLNPSTQ
DownLNPDOWNQ
FastLNPFASTQ
SlowLNPSLOWQ
RaiseLNPRAISEQ
LowerLNPLOWERQ
ResetLNPRESETQ
OffLNPOFFQ
OnLNPONQ
ReverseLNPREVQ
CloseLNPCLOSEQ
OpenLNPOPENQ
UpLNPUPQ
TestLNPTESTQ
LowLNPLOWQ
HighLNPHIGHQ
Two Position Selection Switch Nameplates
Forward—ReverseSLNPFRQ
Hand—Auto
On—OffSLNPOO
Start—StopSLNPSS
BlankSLNPBQ
Up—DownSLNPUDQ
Run—JogSLNPRJQ
Auto—HandSLNPAHQ
Off—RemoteSLNPORQ
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3R, 4X, 9EFG, 12
SLNPHAQ
DescriptionSuffix
Three Position Selection Switch Nameplates
Forward—Off—ReverseSLNPFORQ
Hand—Off—Auto
Run—Off—JogSLNPROJQ
BlankSLNPB3
Reverse—Off—ForwardSLNPROFQ
Auto—Off—HandSLNPAOHQ
Hand—Off—RemoteSLNPHORQ
1—Off—2SLNP102Q
Jog—Off—RunSLNPJORQ
Stop—Run—StartSLNPSRSQ
Local—Off—RemoteSLNPLORQ
Momentary Push Buttons
For Rectangular Weatherboot Style Only (Not for round weatherboot style)
Blank
ForwardSNPFWDQ
JogSNPJOGQ
RunSNPRUNQ
Stop
Start
DownSNPDOWNQ
FastSNPFASTQ
SlowSNPSLOWQ
RaiseSNPRAISEQ
LowerSNPLOWERQ
ResetSNPRESETQ
OffSNPOFFQ
OnSNPONQ
ReverseSNPREVQ
CloseSNPCLOSEQ
OpenSNPOPENQ
UpSNPUPQ
TestSNPTESTQ
LowSNPLOWQ
HighSNPHIGHQ
SLNPHOAQ
SNPBQ
SNPSPQ
SNPSTQ
Custom nameplates are not available.
Included as standard (no need to use suffix).
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
113
Page 8
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
Furnished with 3/4” to 1/2” NPT reducer.
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
114
Page 9
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
Selector Switch Control Stations and Fire Alarm Station. Nonmetallic
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D
NEMA 3R, 4X, 7CD, 12
Pilot Light and Selector Switch
Selector Switch
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3R, 4X, 9EFG, 12
Pilot
Hub Size (Inches)
Dead-End
1/2 or 3/4 — Pilot Light and
2-Pos., 2-Cir. Selector Switch
1/2 or 3/4 — Pilot Light and
2-Pos., 4-Cir. Selector Switch
Note: Standard legend plate reads Hand/Auto
1/2 or 3/4 — Pilot Light and
3-Pos., 2-Cir. Selector Switch
1/2 or 3/4 — Pilot Light and
3-Pos., 4-Cir. Selector Switch
Note: Standard legend plate reads Hand/Off/Auto
Feed-Thru
1/2 or 3/4 — Pilot Light and
2-Pos., 2-Cir. Selector Switch
1/2 or 3/4 — Pilot Light and
2-Pos., 4-Cir. Selector Switch
Note: Standard legend plate reads Hand/Auto
1/2 or 3/4 — Pilot Light and
3Pos., 2-Cir. Selector Switch
1/2 or 3/4 — Pilot Light and
3-Pos., 4-Cir. Selector Switch
Note: Standard legend plate reads Hand/Off/Auto
Light
Diagram
Switch DiagramCatalog Number
LeftCenterRight
None
None
None
None
With
Pilot Light
N1D75-J112N1D75-12
N2D75-J112N2D75-12
N1D75-J135N1D75-35
N2D75-J135N2D75-35
N1D75-J1102N1D75-102
N2D75-J1102N2D75-102
N1D75-J1345N1D75-345
N2D75-J1345N2D75-345
N1DC75-J112 N1DC75-12
N2DC75-J112 N2DC75-12
N1DC75-J135 N1DC75-35
N2DC75-J135 N2DC75-35
N1DC75-J1102 N1DC75-102
N2DC75-J1102 N2DC75-102
N1DC75-J1345 N1DC75-345
N2DC75-J1345 N2DC75-345
With Out
Pilot Light
Fire Alarm Station, Factory Sealed — Universal Contacts, with hammer on chain
Catalog Number
Hub Size
(Inches) Description
Dead-End
1/2 or 3/4Universal 2 Position, 1 Circuit
Feed-Thru
1/2 or 3/4Universal 2 Position, 1 Circuit
Replacement Glass
(For N1 or N2)NFA-G
Furnished with a 3/4” to 1/2” NPT reducer.
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs. Do not use in atmospheres containing
electrically conductive dusts (most coal dusts are not electrically conductive).
N1 Series
(Neutral Color)
N1D75FA-U1N2D75FA-U1
N1DC75FA-U1 N2DC75FA-U1
N2 Series
(Red Color)
115
Page 10
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
Momentary contact left position. Spring return to center. Maintained contact right position.
3 Position, 2
Circuit
3 Position, 4
Circuit
Momentary contact right position. Spring return to center. Maintained contact left position.
3 Position, 4
Circuit
Two Position NameplatesThree Position Nameplates
Two or Three Positions — Permit locking in any position.SBL-3-Q
LeftCenterRightN1 SwitchN2 Switch
Diagram
SLNP-HAQ
N1/N2 Switch
Assembly Only
SSBA1-2QN1K-12N2K-12
SSBA2-2QN1K-35N2K-35
SSBA1-3QN1K-102N2K-102
SSBA2-3QN1K-345N2K-345
SSBAS-1-3N1K-102SRC N2K-102SRC
SSBAS-2-3N1K-345SRC N2K-345SRC
SSBASL-1-3N1K-102SLC N2K-102SLC
SSBASL-2-3N1K-345SLC N2K-345SLC
SSBASRA-2-3 N1K-637SRC N2K-637SRC
Hand—Off—Auto
Stop—Run—StartSLNP-SRSQ
Local—Off—RemoteSLNP-LORQ
Assembly with Cover
SLNP-HOAQ
Supplied as standard with Maintained Contact Selector Switches.
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
116
Page 11
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
For use with N1 and N2 Series Bodies Only. All Covers Supplied with Four Bolts and Blank Nameplate. N1 Series– Neutral Color; N2 Series– Blue Color.
NEC — N1 Series (Non-Factory Sealed):
Class I, Division 1 and 2, Groups C, D
NEMA 3R, 4X, 7CD, 12
Covers Only — for Use with Nonmetallic Mounting Bodies Below
NEC — N2 Series (Factory Sealed):
Class I, Division 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3R, 4X, 9EFG, 12
Description
Pilot Light or Push Button Covers
3/4” tapped openings
One opening: one pilot light or one push button
Two openings: two pilot lights; two push buttons —
one pilot light and one push button
Push Button or Selector Switch Covers
1/2” tapped openings
Two openings: selector switch or two push buttonsN1K-2SPN2K-2SP
Push Button, Pilot light or Selector Switch Covers
One 3/4” top and two 1/2” bottom tapped openings
One top and two bottom openings — one pilot light,
two push buttons; one pilot light, one selector switch;
or three push buttons
Catalog Number
N1 SeriesN2 Series
N1K-1PLN2K-1PL
N1K-2PLN2K-2PL
N1K-3JPBN2K-3JPB
1-Gang Nonmetallic Mounting Bodies — for use with Covers Above
DescriptionHub Size (Inches)
Dead-End1/2 or 3/4N1D75QN2D75Q
Feed-Thru1/2 or 3/4N1DC75QN2DC75Q
Nameplate Mounting Bracket
DescriptionCatalog Number
Bracket for N1, N2 SeriesNPBRKT-N1N2
To order bracket with control station, add suffix –NPBRKT to end of catalog number.
Note: Secure mount bracket using cover nameplate screws.
Furnished with 3/4” to 1/2” NPSM reducer.
Furnished with a 3/4” to 1/2” NPT reducer.
For Class I, Division 1 applications, sealing fittings must be field installed adjacent to enclosure on all conduit runs.
Catalog Number
N1 SeriesN2 Series
117
Page 12
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES
10 Ampere, 600 Vac Max. for Heavy Duty Use. N1 Series – Neutral Color; N2 Series – Blue Color.
NEC:
Class I, Division 1 and 2, Groups B,C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
Push Button Accessories and Parts
DescriptionCatalog Number
Push Button Securing Rod with Chain — Stainless Steel
For use with Single Guard OnlyNBL-SR
Mushroom Head Button with Weather Boot for Use with Momentary Contact — Gasketed
BlackNMRB-BL
GreenNMRB-GR
RedNMRB-RE
Mushroom Head Push Button
For Use with Mushroom Head Push Button — Maintained Contact — Solid-Colored Nonmetallic
RedNMRBM-RE
MNPESTPQ
Pilot Light, Factory Sealed
Pilot LightChamber Only
Nameplates — Mushroom Head Push Button For Momentary and Maintained
StartMNPSTQ
StopMNPSPQ
Emergency StopMNPESTPQ
BlankMNPBQ
Incandescent
Furnished with 6S6 120 Vac incandescent lamp, jewel and guard. Has 457 mm (18”) long, type SFF-2 pigtail leads;
+150 °C (+302 °F). Body has 3/4” straight thread (NPSM).
With Red JewelSPLSREB
With Green JewelSPLSGRB
With Amber JewelSPLSAMB
With Blue JewelSPLSBLB
With Clear JewelSPLSCLB
With Opal JewelSPLSOPB
LED
Furnished with candelabra base 120 Vac LED, jewel and guard. Has 457 mm (18”) long, type SFF-2 pigtail leads; +150
°C (+302 °F). Body has 3/4” straight thread (NPSM).
With Red LED, Clear JewelSPLNSREB
With Green LED, Clear JewelSPLNSGRB
With Amber LED, Clear JewelSPLNSAMB
Chamber Only
(Same as above, less jewel, guard and lamp)SPLSSCB
Suitable for Class I, Group B when installed in an enclosure rated for Class I, Group B.
119
Page 14
Intraground™ N1 and N2 Series Control Stations
CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES