Appleton Instruction Sheet: Stylmaster Strobe Luminaires, 650400001 | Appleton Manuals & Guides

Description
The Stylmaster signaling appliances are intended for general utility signaling use. The strobes are available in pendant, bracket or ceiling mount congurations and in 120V 60 Hz and 240V 60 Hz. The beacons are UL and cUL Listed for use in Class I, Division 2, Group A, B. C and D haz­ardous locations; pendant-mount versions are also Listed for Class II, Division 1, Group E, F and G; Class II, Division 2 Group F and G; and Class lIl Division 1 and 2 hazardous locations. Operating Temperature Codes are per the follow­ing chart.
Temperature Codes
NOTE: Class II and Class III Listings
only apply to Pendant Mount
wire leads through the 3/4" (19 mm) NPT threaded conduit (not supplied). Secure the 3/4" (19 mm) threaded conduit to the mounting hood.
Ground the unit in accordance with National Electrical Code (NFPA 70) and local requirements.
Connect red positive (+) wire lead to incoming positive (+) and connect black negative (-) wire lead to incoming negative using wire nuts (not supplied).
Secure the 3/4" (19 mm) threaded conduit to the outlet box.
2. Bracket Mount Models (Figure 2): Remove the outlet box from the end of the mounting bracket. Install the outlet box using appropriate hardware (not supplied) for the mounting sur­face. Pull the field wiring through the outlet box.
Ground the unit in accordance with National Electrical Code (NFPA 70) and local requirements.
Connect red positive (+) wire lead to incoming positive (+) and connect black negative (-) wire lead to incoming negative using wire nuts (not supplied).
Mount the wall bracket back onto the outlet box.
3. Ceiling Mount Models (Figures 3 and 4): Unscrew and remove the clear outer globe. Remove the two screws holding the circuit assembly to the bottom of the xture. To separate the ceiling junction box from the xture housing, remove the remaining two screws at the bottom of the fixture.
Mount the ceiling junction box using appropriate hardware. Pull power source wiring through the ceiling junction box.
Ground the unit in accordance with National Electrical Code (NFPA 70) and local requirements.
Connect the positive (+) power source wire to the positive (+) terminal and the negative (-) power source wire to the negative (-) terminal.
They are UL and cUL listed as Type 3R and 4. AC rated strobes are also UL and cUL Listed and Marine Rated.
The strobe ashes a 360-degree beam of light approximately 65 times per minute.
EGS Electrical Group • 7770 N. Frontage Rd. • Skokie, IL 60077 Rev. A 650400-001 9/7/00 Page 1
Install this unit in accordance with the applicable requirements in the latest edition of the National Electrical Code or Canadian Electrical Code, using supply wire rated per Table 2.
1. Pendant Mount Models (Figure 1): Install explo­sion-proof hanger box (not supplied). Pull the unit's
650400-001
Installation Instructions for Stylmaster Strobe Light
for Use in Hazardous Locations
Ambient Class I, Div. 2 Class II, Div. 1 & 2
Temp. Groups A, B, C & D Class III, Div. 1 & 2
40˚C 280˚C (T2A) 120˚C (T4A)
55˚C 300˚C (T2) 135˚C (T4)
65˚C 300˚C (T2) 135˚C (T4)
WARNING
To reduce the risk of ignition of hazardous atmospheres and shock, do not apply power to the unit until installation has been complet­ed and unit is tightly assembled and secured.
!
4. Where applicable, install the optional guard assembly over the clear outer globe and secure using three screws (provided).
Maintenance
Disassemble the unit as follows (Figure 4):
1. Where applicable, remove the guard by
rotating counterclockwise
2. Unscrew and remove the clear outer globe.
3. To replace the strobe tube, remove the inner
lens and replace the appropriate tube as listed in Ta ble 1.
4. Reinstall the inner lens. Screw the clear outer globe back onto the xture housing.
5. Where applicable, install the guard assembly over the clear outer globe by rotating clockwise until it snaps into place.
Figure 2. Detail of Bracket Mounting.
Page 2 Rev. A 650400-001 9/7/00 EGS Electrical Group • 7770 N. Frontage Rd. • Skokie, IL 60077
Figure 3. Detail of Ceiling Mounting.
Figure 1. Detail of Pendant Mounting.
Secure the xture housing on the junction box by replacing the two screws removed above. Reinstall the circuit assembly to the bottom of the xture using the two screws removed above.
Screw the clear outer globe back on the xture housing.
WARNING
To reduce the risk of ignition of hazardous atmospheres and shock, keep assembly tight­ly closed when circuits are energized.
!
WARNING
To reduce the risk of ignition of hazardous atmospheres and shock, keep assembly tight­ly closed when circuits are energized.
To reduce the risk of ignition of hazardous atmospheres and shock, disconnect from the supply and circuit and allow five (5) minutes for stored energy to dissipate before disas­sembling the unit.
!